선박 신호회로용 서지방호장치의 개발 (Development of a Surge Protective Device for Signal Lines on Shipboard)

  • 서황동;송재용;한주섭;김윤식;길경석
    • 한국마린엔지니어링학회:학술대회논문집
    • /
    • 한국마린엔지니어링학회 2005년도 전기학술대회논문집
    • /
    • pp.1161-1165
    • /
    • 2005
  • Due to the miniaturization of electrical components and assembles on signal circuits, transient overvoltages caused by switching operation or lightning surges have become more interesting concern to the field of electrical engineering. In this paper, the development of surge protective devices(SPDs) that can protect sensitive signal device on shipboard from overvoltages are described. Two kinds of SPDs are designed and tested by using a combination surge generator which can produce the standard impulse current of 8/20${\mu}s$ 2.1kA according to the IEC 61000-4-5 standard. From the simulation and experimental results, it is confirmed that the proposed SPDs have an enough protection performance with a low insertion loss and a low clamping voltage.

  • PDF

서지보호기의 상태 감시를 위한 MOV의 고장률 예측 (Failure Rate Estimation of MOV for Condition Monitoring of Surge Protective Devices)

  • 김동진;김영선;박재준;이기식
    • 전기학회논문지
    • /
    • 제62권9호
    • /
    • pp.1302-1307
    • /
    • 2013
  • MOV(Metal Oxide Varistor) is the most important part of SPD(Surge Protective Device) which can protect electric facilities from an impulse current such as a lightning. So far, the fault of MOVs have decided only by surge count without considering magnitude of surge current and an amount of input energy. This paper proposed the fault prediction algorithm for the MOV using look up table made by surge count and input current data which have non-linear characteristics for input current and are estimated by high voltage experimental results. Proposed algorithm was proved by experiment on verification at a high voltage laboratory.

고성능 서지보호 시스템 개발 및 성능 평가 (Development and/or Characteristics Evaluation of High Performance SPD(Surge Protective Device))

  • 김재훈;김주한;한상옥;김선호;구경완
    • 전기학회논문지P
    • /
    • 제58권3호
    • /
    • pp.328-333
    • /
    • 2009
  • In this paper, we have developed high performance SPD(surge protective device) and evaluated the characteristics in comparison with typical SPD used in the inside and outside of the country. The new SPD was composed of MOV(metal oxide varistor), GDT(gas discharge tube) and impedance such as resistors, capacitors or varistors. To estimate operating the characteristic of the SPD which was developed, it was measured surge voltage caused by fault current or surge according to IEC 61000-4-5. As a result it was found that the power supply was cut off by high performance SPD when caused a short-circuit. In addition we could know that it could prevent ELB(earth leakage breaker)'s malfunction caused by surge.

A New Approach to On-Line Monitoring Device for ZnO Surge Arresters

  • Lee Bok-Hee;Gil Hyoung-Jun;Kang Sung-Man
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제5C권3호
    • /
    • pp.131-137
    • /
    • 2005
  • This paper describes a new approach to the algorithm and fundamental characteristics of the device for monitoring the leakage currents flowing through zinc oxide (ZnO) surge arresters. In order to obtain a technique for a new on-line monitoring device that can be used in the deterioration diagnosis of ZnO surge arresters, the new algorithm and on-line leakage current detection device for extracting the resistive and capacitive currents using the phase shift addition method were proposed. The computer-based on-line monitoring device can sense accurately the power frequency leakage currents flowing through ZnO surge arresters. The on-line leakage current monitoring device of ZnO surge arresters proposed in this work has the high sensitivity compared to the third harmonic leakage current detection devices. As a consequence, it was found that the proposed leakage current monitoring device would be useful for forecasting the defects and degradation of ZnO surge arresters.

주택용 분전반에 설치되는 서지보호기의 열적 안전성 시험 및 분석 (A thermal stability testing and analysis for a surge protector installed in residential distribution board)

  • 김주철;박장범;기채옥
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2009년도 추계학술대회 논문집
    • /
    • pp.339-341
    • /
    • 2009
  • 개별세대 내 정보통신기기 및 홈네트워크 장비증가로 인하여 서지보호장치(SPD : Surge Protective Device)가 설치되고 있고 산업규격개정 및 등전위 접지시스템 강화에 따라 서지보호기 사용량은 점진적으로 증가하고 있다. 주택용 분전반에 설치되는 서지보호기의 부품은 전압제한형 소자인 $Z_nO$배리스터가 사용되고 있으나 일시적 과전압특성 (Temporary Overvoltage Characteristic) 위험에 노출되어있다. 본 논문은 일반주택에 사용되는 서지보호기의 열적 안전성 (Thermal Stability) 특성시험을 통하여 제품을 분석하였고 이를 토대로 개선안을 제시하였다. 분석결과 누설전류를 차단하기위한 가스 방전관(GDT) 사용 및 열폭주(Thermal Runaway) 현상을 막기 위한 안전장치가 2종 이상 필요하였다.

  • PDF

진공차단기 스위칭 써지 특성 해석 및 저감 방안 (Surge Characteristics Analysis and Reduction Method of Vacuum Circuit Breaker)

  • 김종겸
    • 전기학회논문지
    • /
    • 제62권2호
    • /
    • pp.190-195
    • /
    • 2013
  • Vacuum circuit breaker(VCB) has been widely used for interruption of load current and fault current for high voltage motor in the industrial field. Its arc extinguishing capability is excellent compared to other breakers. But it has the potential to cause multi reignition surge by high extinguishing capability. Surge voltage is generated by the opening and closing of VCB. Multi reignition surge of VCB is steep-fronted waveform. It may have a detrimental effect on the motor winding insulation. So, most of users install a protection device to limit steep-front waveform at the motor terminal or breaker side. So, most of users install a protection device at the motor terminal or breaker side. This protective device is surge absorber(SA) such as ZnO and RC type. In this study, we analyzed whether there is any effect when two type SA is applied to the VCB multi reignition surge. We confirmed that ZnO SA is slightly more effective than RC SA for reduction of multi reignition surge.

신뢰도 향상을 위해 SCR을 응용한 서지 보호회로 개발 (The Development of Surge Protection Circuit Applying SCR for Improving Reliability)

  • 남궁업;추광욱
    • 조명전기설비학회논문지
    • /
    • 제26권8호
    • /
    • pp.96-101
    • /
    • 2012
  • A surge protection device of the metal oxide varistor(MOV) has been commonly used for preventing electrical damage in many electronic equipments. The MOV has a property that leakage current is increased and might be permanently damaged when it is exposed continuously to the electrical stresses such as lightening surges. In this paper, we propose a novel surge protection circuit adopting a silicon controlled rectifier(SCR) in the traditional protection circuits using the MOV device simultaneously. When lightning surges are injected to the proposed circuit, the MOV lets the surge pulses bypassing through the ground at first up to the level that SCR begins to operate. Above the threshold level of turning on the SCR, the SCR operates bypasses large surge currents to the ground. Proposed circuit was verified with a leakage current experiment and PSpice circuit simulations under the repeated surge injection environment.

저압용 서지 보호 장치(SPD)의 보호 거리 해석 (Analysis of the Protective Distance of Low-Voltage Surge Protective Device(SPD) to Equipment)

  • 이정우;오용택
    • 조명전기설비학회논문지
    • /
    • 제26권4호
    • /
    • pp.28-34
    • /
    • 2012
  • Installing surge protection devices for a low-voltage system is important to ensure the survival of electric or electronic devices and systems. If surge protection devices (SPD) are installed without consideration of the concept of lightning protection zones, the equipment to be protected might be damaged despite the correct energy coordination of SPDs. This damage is induced by the reflection phenomena on the cable connecting an external SPD and the load protected. These reflection phenomena depend on the characteristics of the output of the external SPD, the input of the loads, and the cables between the load and the external SPD. Therefore, the SPD has an effective protection distance under the condition of the specific load and the specific voltage protection level of SPD. In this paper, PSCAD/EMTDC software is used to simulate the residual voltage characteristics of SPD Entering the low-voltage device. And by applying a certain voltage level, the effective protection distances of SPD were analyzed according to the each load and length of connecting cable, and the effectiveness of SPD were verified.

전원회로용 서지방호장치의 설계 및 제작 (Design and Fabrication of a Surge Protective Device for Electrical Mains on Shipboard)

  • 문승보;박대원;송재용;길경석
    • 한국마린엔지니어링학회:학술대회논문집
    • /
    • 한국마린엔지니어링학회 2005년도 전기학술대회논문집
    • /
    • pp.1035-1040
    • /
    • 2005
  • This paper deals with the design rule and performance results of the surge protective devices (SPDs) for low-voltage mains on shipboard. The proposed SPDs consists of a metal oxide varistors (MOV) and a L-C filter to improve noise-elimination performance. Three kinds of SPDs are fabricated and tested by using a combination surge generator which produce the standard impulse current of 8/20${\mu}s$ 2.1kA. As a results, the proposed SPDs with series L-C filter have more excellent transient blocking and noise reduction performance than the conventional ones.

  • PDF

Failure Prediction of Metal Oxide Varistor Using Nonlinear Surge Look-up Table Based on Experimental Data

  • Kim, Young Sun
    • Transactions on Electrical and Electronic Materials
    • /
    • 제16권6호
    • /
    • pp.317-322
    • /
    • 2015
  • The metal oxide varistor (MOV) is a major component of the surge protection devices (SPDs) currently in use. The device is judged to be faulty when fatigue caused by the continuous inflow of lightning accumulates and reaches the damage limit. In many cases, induced lightning resulting from lightning strikes flows in to the device several times per second in succession. Therefore, the frequency or the rate at which the SPD is actually exposed to stress, called a surge, is outside the range of human perception. For this reason, the protective device should be replaced if it actually approaches the end of its life even though it is not faulty at present, currently no basis exists for making the judgment of remaining lifetime. Up to now, the life of an MOV has been predicted solely based on the number of inflow surges, irrespective of the magnitude of the surge current or the amount of energy that has flowed through the device. In this study, nonlinear data that shows the damage to an MOV depending on the count of surge and the amount of input current were collected through a high-voltage test. Then, a failure prediction algorithm was proposed by preparing a look-up table using the results of the test. The proposed method was experimentally verified using an impulse surge generator