• 제목/요약/키워드: Street lamp

검색결과 59건 처리시간 0.034초

가로등설비 누전시 건조상태와 침수상태에 대한 전위분포 분석 (The Analysis on the Electric Potential Distribution of Dry and Submerged Condition by Electric Leakage in Street Lamp)

  • 홍성호;박상태;김상철
    • 한국안전학회지
    • /
    • 제23권6호
    • /
    • pp.44-50
    • /
    • 2008
  • This paper presents study on the electric potential distribution when have a short in street lamp. In order to measure electric potential testing ground is built in. A experiment is conducted to simulate dry and submerged situation of street lamp. The street lamp is leaked by artificial means. And electric potential is measured in grounded street lamp and street lamp alone. The results show that touch voltage of grounded street lamp is possible more high than street lamp alone. And the electric shock hazard is high because high electric potential is distributed near submerged street lamp. Also if street lamp is submerged ground is not useful to decrease electric shock hazard.

가로등설비 누전시 전위분포에 대한 실험연구 (The Experimental Study on the Electric Potential Distribution by Electric Leakage in Street Lamp)

  • 박상태;이복영;홍성호;최충석;길형준;한운기
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2005년도 춘계학술대회논문집
    • /
    • pp.222-227
    • /
    • 2005
  • This paper presents study on the electric potential distribution when have a short in skeet lamp. In order to measure electric potential testing ground is built in. A experiment is conducted to simulate dry and submerged situation of street lamp. The street lamp is leaked by artificial means. And electric potential is measured in grounded street lamp and street lamp alone. The results show that touch voltage of grounded street lamp is possible to more high than street lamp alone. And the electric shock hazard is high because high electric potential is distributed near submerged street lamp. Also if street lamp is submerged ground is not useful to decrease electric shock hazard.

  • PDF

가로등 회로 손상 선별 장치 개발 (Development of Selecting Equipment for Damage of Street Lamp Circuit)

  • 조현섭
    • 한국산학기술학회논문지
    • /
    • 제12권5호
    • /
    • pp.2294-2297
    • /
    • 2011
  • 본 연구는 현재 사용되고 있는 가로등 회로의 손상을 선택적으로 점검하기 위한 다이오드를 개발하였다. 개발된 가로등 진단기는 LED 표시 체계의 점등 유무를 파악하여 선택적으로 점검할 수 있으며, 가로등이 점등되지 않을 경우 어느 부분에 고장이 발생했는지 LED 소등의 관계로 표시 할 수 있다. 회로는 PCB 기판을 제작하여 가로등 개별단의 고장점 위치를 확인할 수 있는 시스템을 개발하였다.

하이브리드 태양광 LED 가로등 컨트롤러의 효율 개선 (Improve the Efficiency of Hybrid Solar LED Street Lamp Controller)

  • 윤중현;김진사
    • 한국전기전자재료학회논문지
    • /
    • 제28권2호
    • /
    • pp.131-136
    • /
    • 2015
  • We develop the 60 W class hybrid solar LED street lamp controller. The controller is providing power via an inverter in the day with the least solar cell and battery and charging the battery for the ESS, acts as a power failure, the built-in battery. Rated output of the fabricated LED street lamp is 300 W or greater battery capacity 300 Wh, discharge time 10 hr, LED street lamp efficiency showed a very high level of light efficiency by about 127 lm/W. In addition, as a result of light distribution pattern according to the distance and the light intensity measurement will be able to ensure a very high quality, show the constant brightness in the distance from the road lights 6 m is about 35~40 lux in uniformity ratio. The proposed hybrid solar LED street lamp system showed a high energy capacity of approximately 1.5 to 152.7% power generation efficiency than typical conventional solar street lamp.

LED 가로등의 발열 패턴 및 전류 특성에 관한 연구 (Study on Thermal Pattern and Current Characteristics of an LED Street Lamp)

  • 김향곤;최충석
    • 전기학회논문지P
    • /
    • 제58권3호
    • /
    • pp.357-361
    • /
    • 2009
  • This study performed analysis on the thermal pattern and current characteristics of an LED ((Light Emitting Diode) street lamp. It did this using a TVS (Thermal Video System) to analyze the LED street lamp's thermal pattern, and measured its characteristics using an oscilloscope. The ambient temperature and humidity during the experiment were maintained at $24{\pm}2[^{\circ}C]$ and 50~60[%]. The capacity of the LED street lamp was 120[W] and nine sets of modules were arranged at uniform intervals. On one module, 24 LED lamps were arranged in a radial pattern. The analysis of the thermal diffusion pattern at the front of the LED lamp showed that the maximum surface temperature was approximately $34[^{\circ}C]$. In addition, there was almost no change in the temperature of the upper cover, and the temperature at the side showed a uniform thermal diffusion pattern. The surface temperature of the converter converting AC to DC increased to approximately $46[^{\circ}C]$. The analysis results of the thermal characteristics of one LED indicated uniform thermal characteristics for an initial eight minutes. However, the temperature at the center of the LED increased to approximately $82[^{\circ}C]$ after 12 minutes had elapsed. It can be seen from this that the temperature at the center of the LED was higher than the allowable temperature, $70[^{\circ}C]$ of the insulating material for general electrical devices. Therefore, it is necessary to design a lamp in such a way that the plastic insulating material does not come into contact with or get close to the LED lamp. The voltage of the LED lamp converted by the AC/DC converter was measured at DC 27[V] and the current was DC 13[A]. Consequently, it can be seen that in order to secure an adequate light source, it is important to supply a stable current that was greater than the current of other light sources. Therefore, appropriate radiation of heat is required to secure the stability and reliability of the system.

가로등 회로 손상 선별 장치 개발 (Development of Selecting Equipment for Damage of Street Lamp Circuit)

  • 조현섭;오명관
    • 한국산학기술학회:학술대회논문집
    • /
    • 한국산학기술학회 2008년도 추계학술발표논문집
    • /
    • pp.160-163
    • /
    • 2008
  • This study developed selecting equipment for damage of street lamp circuit used by current transform and diode. To develop this system, current check used current transform and indication system used LED device. As faulted, current of street lamp circuit change with fault decivce. This chage of current detected and indicated by selecting equipment

  • PDF

주요간선 도로에 설치된 가로등의 현장실태조사를 통한 정성적 분석 (The Qualitative Analysis through the Investigation of the Field Condition at Street Lamps on the Main Street)

  • 최충석;김향곤;한운기
    • 조명전기설비학회논문지
    • /
    • 제19권1호
    • /
    • pp.101-108
    • /
    • 2005
  • 도로에 설치된 가로등설비는 감전위험성에 노출된 취약한 구조로 급격한 호우로 인한 침수발생으로 매년 감전사고자가 다수 발생하고 있는 실정이다. 이에 가로등설비에서의 감전사고를 방지하기 위해, 실제 주요간선 도로 현장에서의 조사가 수행되었다. 가로등 분전함의 회로구성, 배선방법, 접지도체, 등주 등에 대해 실태조사가 실시되었고 관련 규정의 분석 및 문제점이 제시되었다. 또한 국내${\cdot}$외 가로등설비의 실태조사를 통해 비교 및 분석되었고, 이를 토대로 관련 규격이 개정되었다. 현장실태조사 및 관련규정의 분석을 통해, 주요간선 도로에 설치된 가로등설비에서의 감전사고에 대한 효과적인 예방대책을 확립하는데 실질적 자료를 제시하고자 한다. 향후 분석 자료는 가로등설비 뿐만 아니라 도로상의 다른 전기설비의 안정화 및 전기재해를 감소시키는데 활용될 수 있다.

저 가격형 Zigbee 통신 네트워크 기반 HID 가로등의 원격 제어 및 감시 시스템 개발 (Development of Remote Control and Monitoring System for HID Street-lamp Based on Low Cost Zigbee Communication Network)

  • 정완섭;김양배;손진근
    • 전기학회논문지P
    • /
    • 제63권2호
    • /
    • pp.69-73
    • /
    • 2014
  • In this paper, remote control and surveillance monitoring system of HID street-lamp using low-cost type of Zigbee communication module was developed. A plurality of capacitors with different capacity are attached to magnetic ballast for HID lamps. Changes in the amount of illumination can be adjusted by the changes in capacity so that the electric energy can be reduced. In Zigbee communication module, a ATmega128L microprocessor is used and in main CPU, ARM9 Core is used to construct a low-cost smart system. In surveillance monitoring systems, the system was configured to remote monitoring of presence of error in the lamp abnormalities, the status of leakage current and abnormalities of ballasts and capacitors and the validity of the proposed empirical experiment was confirmed.

기상예보를 이용한 태양광 LED 가로등의 효율적 운용에 관한 연구 (A Study on Efficient Management of Solar Powered LED Street Lamp Using Weather forecast)

  • 표세영;권오석;김기환
    • 한국인터넷방송통신학회논문지
    • /
    • 제15권2호
    • /
    • pp.129-135
    • /
    • 2015
  • 본 논문에서는 가로등 운용에 있어서 일기예보 및 일조량을 고려한 알고리즘을 제안하였다. 이 알고리즘에 의해 생성된 Weather Factor를 적용하여 보행자가 있을 시에는 가로등의 광량을 최대로 유지하고 보행자가 없을 경우 최대전력을 사용하지 않고 일정한 밝기를 유지하는 대기전력모드를 사용하여 전력소비를 줄였다. 이렇게 함으로써 배터리의 잔량을 확보할 수 있으며 이를 이용하여 부조일이 지속될 경우 운용일수를 최대한 연장하기 위한 적절한 알고리즘을 제안하였다. 또한 이러한 알고리즘에 필요한 Weather Factor의 값을 실험을 통하여 결정하였으며. 모의실험을 통해 알고리즘의 적합성을 확인하였다.

가로등 전용 누전 개폐기의 차단효과에 대한 고찰 (Characteristics of Street Lamp Controller with Earth Leakage Contactor)

  • 이성재;신재식
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2010년도 하계학술대회 논문집
    • /
    • pp.283-283
    • /
    • 2010
  • Smart street light controller is a product with advance micro controller base for energy saving in conventional street lighting systems. Intelligent Street light controller are specially developed for automation and energy saving in conventional street light systems and lighting systems. It is so designed that it operates on sunrise & sun set timings according to longitude of particular location with facilitate to set month wise civil twilight timings to cope up with all seasons. Dimming (Power down) mode selection switch on/off at fixed times with relay or contactor. Night dimming, staggering and intelligent control reduces burn hours and increases the lifetime of lamps with about 30% and low annual operating cost type base are among the most inexpensive wireless technologies available. Low initial costs As PLC wireless, there is no need to establish cable connection.

  • PDF