바닥 난방공간의 다인자 제어에 관한 실험적 연구 (An experimental study on the multiple parameter switching control for floor heating system)

  • 조성환;태춘섭;장철용
    • 설비공학논문집
    • /
    • 제9권4호
    • /
    • pp.472-483
    • /
    • 1997
  • An experimental facility consisting of two $3{\times}4.4{\times}3.8m$ rooms identical in construction is built. Each room has a control system and storage tank supplying hot water to the radiant floor heating system. The facility enables simultaneous comparision of two different control stratigies each implemented in a separate room. The operating performance of three kinds of flow control scheme is tested and compared in this study : (i) conventional on-off control based on feedback from room air temperature (ii) TPSC(two parameter switching control) (iii) TPOC(two parameter on-off control). Results show that TPSC and TPOC using room air and surface temperature sequentially as feedback signal to control hot water supply is the better temperature regulation scheme than conventional control based on feedback from only room air temperature. They are good candidates for the room with radiant floor heating system under continuous and intermittent heating mode.

  • PDF

기계 환기시스템의 실내 환기성능 특성 해석에 관한 연구 (A Study on Characteristic Analysis for Indoor Ventilation Performance of Mechanical Ventilation System)

  • 구재현
    • 한국가스학회지
    • /
    • 제16권2호
    • /
    • pp.31-37
    • /
    • 2012
  • 본 연구는 실내 쾌적성 제어를 위하여 룸 에어컨의 환기성능을 분석한다. 실험장치는 환경공조챔버, 룸 에어컨, 추적가스 측정시스템, 급기팬과 제어기로 구성된다. 환기성능은 ASTM Standard E741-83 기준에 근거하여 환경공조챔버 내 CO2 추적가스기법을 사용한 체강법에 의해 재실자와 급기 환기량에 따라 평가된다. 급기 환기량 증가에 따라 환기성능이 증가함을 파악하였으며 재실자가 없는 경우 CO2 가스는 빠르게 감소하며 이때의 환기성능은 55%까지 증가한다. 그리고 1명의 재실자가 있는 경우 1시간 경과후 급기량 570 lpm에서 환기성능은 자연감쇠와 비교하여 25%까지 증가한다. 실험 데이터를 사용하여 환경공조챔버 내 룸 에어컨의 환기성능 모델링을 도출하였다.

수술중 감염방지를 위한 공조시스템의 개선방안에 대한 연구 (A Study on the Air Ventilation System of Operation Room for the Prevention of Hospital Infection)

  • 김천숙;권순정;주영철
    • 한국산학기술학회논문지
    • /
    • 제5권6호
    • /
    • pp.552-557
    • /
    • 2004
  • 수술중 감염방지를 위해 수술실의 공조시스템의 개선방안에 대한 연구를 수행하였다. 대학병원들의 수술실과 공조 시스템을 조사하였다. 수술실 내부의 여러 부위에서 공기 샘플을 채취하여 세균을 배양함으로써 수술실내 세균의 분포를 측정하였다. 수술실 단면을 2차원 모델화 하여 공기의 유동을 전산유체해석하였다. 준공한지 오래된 병원의 수술실은 공조시스템이 정화된 신선한 공기를 수술이 진행되는 부위에 효과적으로 공급하지 못하는 것으로 판단되어졌다. 시설비의 큰 증가 없이 환자의 수술부위에 효율적으로 신선한 공기를 공급할 수 있는 시스템을 제안하였다.

  • PDF

슬래브축열의 최적제어방책에 관한 연구 -평가함수의 선택이 결과에 미치는 영향- (A Study on the Optimal Control Strategy of Air-Conditioning System with Slab Thermal Storage - Results Influenced by the Choice of a Criterion Function -)

  • 정재훈;신영기
    • 설비공학논문집
    • /
    • 제18권11호
    • /
    • pp.896-905
    • /
    • 2006
  • An optimal control of an air-conditioning system with slab thermal storage is investigated by making use of the Maximum Principle. An optimal heat input to a plenum chamber and an air-conditioned room is determined by minimizing a criterion function which is given as integral sum of two terms. The first term is the square of the deviation in the room air temperature from the set-point value, and the second is the absolute value of the heat input. The result indicates that it tries to keep a room air temperature in set-point value by heating as much as possible at the time of a setup of a room air temperature or just before that, in order to avoid a heat loss arising at the time of the non-air conditioning. The result is compared with that of the case when the square of the heat input is used as a criterion.

초청정 클린룸의 공기이온화에 대한 실험적 연구 (Experimental Study on Air Ionization Phenomena in the Super Clean Room)

  • 오명도;배태식;김선창
    • 설비공학논문집
    • /
    • 제4권2호
    • /
    • pp.72-81
    • /
    • 1992
  • Experimental study on air ionization phenomena has been conducted to analyze the propagation behavior and dischargeability of polarity air ions under the super clean room environments with the operation of prototype of Air Ionization System. Varying humidity and air velocity, the distribution of air ion density and the discharge time are measured and analyzed.

  • PDF

클린룸의 상부 플레넘 설계를 위한 유동특성 실험 (Airflow Characteristic Experiments for the Upper Plenum Design of Clean Room)

  • 오명도;배귀남;김석철;이춘식
    • 설비공학논문집
    • /
    • 제1권4호
    • /
    • pp.276-289
    • /
    • 1989
  • The airflow characteristics in both the upper plenum and the clean space of clean room are investigated by measuring the pressure distribution of the upper plenum and the velocity profile in the clean space, at the various conditions of the supplied airflow rate, the volume of upper plenum and the air supply type. The performance of vertical air supply type and horizontal air supply type is analyzed in terms of the airflow uniformity which is frequently used in indicating the clean room performance, and the relations among the volume of upper plenum, the supplied airflow rate and the airflow uniformity are confirmed. The results of this experimental study can be applied to the designing of the upper plenum of clean room.

  • PDF

공조기 덕트 내의 자연대류가 실내 유입유량에 미치는 영향 (The Effect of Flow Rate into Room by Natural Convection in Air Conditioner Duct)

  • 공태우;정한식;정효민
    • 설비공학논문집
    • /
    • 제13권3호
    • /
    • pp.160-166
    • /
    • 2001
  • A numerical analysis has been performed for natural convection in an air conditioner duct system. The governing equations were solved a finite volume method using a SIMPLE algorithm. In the calculation mode of duct, the room temperature was preserved at $25.0^{\circ}C$ and duct wall temperature had a temperature of 15, 20.0, 22.5, 23.75, 26.25, 27.5 30 and $35^{\circ}C$. The results of velocity vectors and contours have been represented for various parameters. Based on the numerical data, the relationships between temperature difference and flow rate into room was represented. In the case of $T_\gamma>T_\omega$, the equation for temperature difference and flow rate was $Q=0.0285\triangleT^0.4005$, and in the case of $T_\gamma>T_\omega$, the equation was $Q=0.0099\triangleT^0.4752$. The duct system has an important relation to room temperature and duct wall temperature.

  • PDF

난류유동해석을 통한 환기효율의 수치해석적 연구 (Numerical Analysis of Ventilation Effectiveness using Turbulent Airflow Modeling)

  • 한화택
    • 설비공학논문집
    • /
    • 제4권4호
    • /
    • pp.253-262
    • /
    • 1992
  • A numerical procedure is introduced to calculate local ventilation effectiveness using the definitions of local decay rate and local mean age. A low Reynolds number $k-{\varepsilon}$ model is implemented to calculate steady state turbulent velocity distributions, and a step-down method is used to calculate transient concentration distributions. Simulations are carried out for several different values of air change rates and several different diffuser angles in a two-dimensional model of a half scale office room. The results show that the local ventilation effectiveness within a room could vary significantly from one location to another. The nominal air change rate based on the assumption of complete mixing of room air does not provide the local ventilation effectiveness information. It is numerically proved that the local mean age distribution obtained from the transient calculation is equivalent to the steady state concentration distribution with homogeneously distributed contaminant sources.

  • PDF

반도체 클린룸용 배기 열회수식 외기공조시스템의 에너지절감에 관한 실험적 연구 (An Experimental Study on Energy Reduction of an Exhaust Air Heat Recovery Type Outdoor Air Conditioning System for Semiconductor Manufacturing Clean Rooms)

  • 송근수;유경훈;강신영;손승우
    • 설비공학논문집
    • /
    • 제21권5호
    • /
    • pp.273-281
    • /
    • 2009
  • In recent semiconductor manufacturing clean rooms, the energy consumption of outdoor air conditioning systems represents about 45% of the total air conditioning load required to maintain a clean room environment. Meanwhile, there is a large amount of exhaust air from a clean room. From an energy conservation point of view, heat recovery from the exhaust air is therefore useful for reducing the outdoor air conditioning load for a clean room. In the present work, an energy-efficient outdoor air conditioning system was proposed to reduce the outdoor air conditioning load by utilizing an air washer to recover heat from the exhaust air. The proposed outdoor air conditioning system consisted mainly of a preheating coil, an air washer, two stage cooling coils, a reheating coil, a humidifier and two heat recovery cooling coils inserted into the air washer and connected to a wet scrubber. It was shown from the lab-scale experiment with outdoor air flow of $1,000\;m^3/h$ that the proposed system was more energy-efficient for the summer and winter operations than an outdoor air conditioning system with a simple air washer.