Abstract
This paper describes to analyze the ventilation performance of a room air conditioner for indoor comfort control. An experimental apparatus consists of a test room, the room air conditioner, a tracer gas measurement system, a supply fan and a controller. Ventilation performance as a function of human occupancy is evaluated with supply ventilation air using a tracer gas technique of CO2 gas in the test room. The ventilation performance is evaluated in a step-down method based on ASTM Standard E741-83 and is found to increase with increasing supply ventilation rate. The CO2 gas concentration is decayed rapidly without human occupancy. The ventilation performance without human occupancy increases up to 55% and the ventilation performance with one person increases up to 25% at the supply air of 570 lpm comparing with a natural reduction after one hour. A modeling for ventilation performance of a room air conditioner in a test room is presented using experimental datum.
본 연구는 실내 쾌적성 제어를 위하여 룸 에어컨의 환기성능을 분석한다. 실험장치는 환경공조챔버, 룸 에어컨, 추적가스 측정시스템, 급기팬과 제어기로 구성된다. 환기성능은 ASTM Standard E741-83 기준에 근거하여 환경공조챔버 내 CO2 추적가스기법을 사용한 체강법에 의해 재실자와 급기 환기량에 따라 평가된다. 급기 환기량 증가에 따라 환기성능이 증가함을 파악하였으며 재실자가 없는 경우 CO2 가스는 빠르게 감소하며 이때의 환기성능은 55%까지 증가한다. 그리고 1명의 재실자가 있는 경우 1시간 경과후 급기량 570 lpm에서 환기성능은 자연감쇠와 비교하여 25%까지 증가한다. 실험 데이터를 사용하여 환경공조챔버 내 룸 에어컨의 환기성능 모델링을 도출하였다.