• 제목/요약/키워드: Pressure drop rate

검색결과 652건 처리시간 0.023초

자동차용 공기분배장치의 성능개선에 관한 실험적 연구 (An Experimental Study on Performance Improvement of Automotive Air Handling System)

  • 유성연;이대웅;김진혁
    • 설비공학논문집
    • /
    • 제19권9호
    • /
    • pp.622-629
    • /
    • 2007
  • Compact semi-center type automotive air handling system(AHS) is developed in this study and it's performance is compared with the conventional 3-pieces type air hand-ling system. The pressure drop is measured at component level and system level, and air flow rate and air distribution of discharge air through each ducts from air handling system are measured. System level characteristics of pressure drop at face and windshield discharge mode and air flow rate are investigated, and also temperature control linearities are tested. The volume of the air handling system package is reduced about 20%. And air flow rate increase about 5 to 20% compared to the conventional 3-pieces type air handling system at each discharge mode with significantly improved air pressure drop both component and system level. Also, air distribution and temperature controllability meet to evaluation criteria.

운전조건 변화에 따른 루버휜 열교환기 성능변화에 관한 실험적 연구 (An Experimental Study on the Performance of the Louver Fin Type Heat Exchanger by the Change of the Driving Condition)

  • 김정국;소산번;상원헌;김동휘;박병덕
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.440-445
    • /
    • 2008
  • The present study was investigated the effect of the driving condition on the performance of a louver fin and tube type heat exchanger under frosting condition. Heat transfer rate and pressure drop by frost were experimentally investigated. Effects of the wet blub temperature and the shape of a fin on heat transfer performances has been also investigated. The key parameters were fin type(louver and corrugate fin) and the wet blub temperature of air (0.5, 1.0, $1.5^{\circ}C$). The heat transfer performance of the louver fin and tube type heat exchanger was higher by 0.89% than the corrugate fin type. As the wet blub temperature of air were increased, the heat transfer rate, pressure drop and mass of frost of three test models(Type A, B, C) were increased. Especially, the maximum heat transfer rate and maximum pressure drop were shown for the louver fin and tube type heat exchanger. As a experimental result, the enhancement factor(EF) of louver fin and tube type heat exchanger was $0.2{\sim}0.4$ due to the high pressure drop.

  • PDF

착상에 의한 휜관형 열교환기의 성능변화에 관한 실험적 연구 (Experimental Study on the Performance Change of the Fin and Tube Type Heat Exchanger by the Frosting)

  • 김정국;소산번;상원헌;박병덕;김동휘;사용철
    • 설비공학논문집
    • /
    • 제21권2호
    • /
    • pp.79-86
    • /
    • 2009
  • The present study was investigates the effect of the parameters on the frost formation and heat transfer performance such as fin shape, air temperature and air velocity. Heat transfer rate and pressure drop by frost were experimentally investigated. Effect of the wet blub temperature and air velocity on the heat transfer performance has been also investigated. The heat transfer performance of the louver fin and tube type heat exchanger was higher by maximum of 0.85% than the corrugate fin type at the air temperature of $2.0/1.5^{\circ}C$. As the wet blub temperature of air were increased, the heat transfer rate, pressure drop and mass of frost of three test models were increased. Especially, the maximum heat transfer rate and maximum pressure drop were shown for the Type B louver fin heat exchanger. As an experimental result, the enhancement factor(EF) of louver fin and tube type heat exchanger was only $0.2{\sim}0.4$ due to the high pressure drop.

초전도 케이블 냉각유로에서의 압력강하 특성 (Pressure Drop Characteristics on HTS Power Cables with LN2 Flow)

  • 고득용;염한길;이관수
    • 설비공학논문집
    • /
    • 제18권1호
    • /
    • pp.81-86
    • /
    • 2006
  • High temperature superconducting (HTS) power cable requires forced sub-cooled LN2 flow cooling. Liquid nitrogen is circulated by a pump and cooled back by cooling system. Typical operating temperature range is expected to be between 65 K and 77 K. The HTS power cable needs sufficient cooling to overcome its low temperature heat load. For successful cooling, the hydraulic characteristics of the HTS power cable must be well investigated to design the cables. Especially, the pressure drop in the cable is an important design parameter, because the pressure drop decides the length of the cable, size of the coolant circulation pump and circulation pressure, etc. This paper describes measurement and investigation of the pressure drop of the cooling system. In order to reduce the total pressure drop of the cooling system, the flow rate of liquid nitrogen must be controlled by rotational speed of the circulation pump.

이등변삼각형 단면을 갖는 파이프 내의 Pseudo-Plastic 유체유동에 대한 압력강하의 연구 (Investigation of Pressure Drop for a Pseudo-plastic Fluid Flow in Isosceles Triangle Pipes)

  • 이동렬
    • 동력기계공학회지
    • /
    • 제13권2호
    • /
    • pp.30-35
    • /
    • 2009
  • Numerical Calculations for dimensionless pressure drop (friction factor times Reynolds number) have been obtained for fully developed laminar flow of MPL(Modified Power Law) fluid in isosceles triangle pipes. The solutions are valid for Pseudoplastic fluids over a wide range from Newtonian behavior at low shear rates through transition region to power law behavior at higher shear rates. The analysis identified a dimensionless shear rate parameter which for a given set of operating conditions specifies where in the shear rate range a particular system is operating, i.e., Newtonian, transition or power law region. The numerical calculation data of the dimensionless pressure drop for the Newtonian and power law regions are compared with previously published asymptotic results presenting within 0.16 % in Newtonian region and 2.98 % in power law region.

  • PDF

아이스슬러리형 빙축열 시스템을 이용한 냉각 시스템의 특성 분석 (Characteristic Analysis of the Cooling System Using Ice Slurry Type Heat Storage System)

  • 이동원;이순명
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.111-115
    • /
    • 2006
  • To clarify the hydraulic and thermal characteristics of ice slurry which made from 6.5% ethylene glycol-water solution flow in the double tube and plate type heat exchanger, experimental studies were performed. The mass flux and Ice fraction of ice slurry were varied from 800 to $3,500 kg/m^2s$(or 7 to 17 kg/min) and from 0 to 25%, respectively. During the experiment, it was found that the measured pressure drop and heat transfer rate increase with the mass flux and ice fraction; however the effect of ice fraction appears not to be significant at high mass flux region. At the region of low mass flux, a sharp increase in the pressure drop and heat transfer rate were observed depends on mass flux.

  • PDF

PGSFR 제어봉집합체 낙하성능시험 (Drop Performance Test of Control Rod Assembly for Prototype Gen-IV Sodium-cooled Fast Reactor)

  • 이영규;김회웅;이재한;구경회;김종범;김성균
    • 한국압력기기공학회 논문집
    • /
    • 제12권1호
    • /
    • pp.134-140
    • /
    • 2016
  • The Control Rod Assembly (CRA) controls the reactor power by adjusting its position in the reactor core during normal operation and should be quickly inserted into the reactor core by free drop under scram condition to shut down chain reactions. Therefore, the drop time of the CRA is one of important factors for the safety of the nuclear reactor and must be experimentally verified. This study presents the drop performance test of the CRA which has been conceptually designed for the Proto-type Generation IV Sodium-cooled Fast Reactor. During the test, the CRA was free dropped from a height of 1 m under different flow rate conditions and its drop time was measured. The results showed that the drop time of the CRA increased as the flow rate increased; the average drop times of the CRA were approximately 1.527 seconds, 1.599 seconds and 1.676 seconds at 0%, 100% and 200% of design flow rates, respectively.

혈관 내 폐 보조장치 설계를 위한 압력손실 특성 평가 (Evaluations on the Characteristics of Pressure Drop f3r the Design of Intravascular Artificial Lung Assist Device)

  • 김기범;권대규;박재관;정경락;이삼철
    • 멤브레인
    • /
    • 제13권1호
    • /
    • pp.20-28
    • /
    • 2003
  • 본 연구에서는, 혈관 내 폐 보조장치를 설계할 때 혈액의 압력손실에 대한 영향을 받지 않는 최적의 설계조건을 찾기 위하여 압력손실을 예측할 수 있는 관계식을 유도하고자 하였다. 정맥 내경의 직경을 3 cm로 고정하고 삽입되는 중공사 개수의 변화에 따른 압력손실을 측정하였으며 실험에 의하여 얻어진 압력손실과 장치의 전면면적과의 상관관계를 curve fitting을 통하여 유도하였고, 유도되어진 관계식을 이용하여 정맥 내에 삽입되는 중공사 개수의 변화에 따른 압력손실을 예측하였다. 그리고 실험을 통하여 예측되어진 값과 비교 검토하여 유사성을 찾고자 하였다. 실험결과 장치에서 액체 유속의 변화에 따라 압력손실은 2차 함수 형태로 변화됨을 알 수 있었다. 또한 장치의 전면면적이 감소하면 압력손실은 증가하였고 충진율이 증가하면 압력손실도 증가함을 알 수 있었다. 장치 내에서의 압력손실에 대한 관계식을 장치의 전면면적과 충진율의 함수로 유도할 수 있었으며, 관계식에 의하여 압력손실을 예측할 수 있었다. 또한, 실험에 의한 압력손실과 비교하였을 때 유사한 경향성을 보여 줌으로써 압력손실 예측의 신뢰성을 얻을 수 있었다.

소형 직교류형 냉각탑의 성능 특성에 관한 연구 (Performance Characteristics of Small Sized Cross-flow Cooling Tower)

  • ;김은필;김재돌;전절호;문춘근;윤정인
    • 동력기계공학회지
    • /
    • 제9권2호
    • /
    • pp.93-98
    • /
    • 2005
  • The performance of cooling tower is dependent on the thermal performance of the packings. It's assessed by heat transfer rate and fan power. In this study, new packing was developed for application in compact type cross-flow cooling tower. The packing characteristic curve and the pressure drop curve were obtained by measuring packing characteristic values and pressure drops of small sized filler in comparison to existing mid-large sized filler. The heat transfer characteristics on small sized filler are about 66% higher than existing mid-large sized filler. The pressure drop characteristics on small sized filler are about two times of the pressure drop characteristics on existing mid-large sized filler.

  • PDF

증발기의 압력강하에 대한 상대습도의 영향 (Effects of Relative Humidity on the Evaporator Pressure Drop)

  • 김창덕;강신형;박일환;이진호
    • 설비공학논문집
    • /
    • 제16권5호
    • /
    • pp.397-407
    • /
    • 2004
  • It is well known that some key parameters, such as evaporating temperature, refrigerant mass flow rate, face velocity and inlet air temperature, have significant influence on the evaporator performance. However performance studies related to a humid environment have been very scarce. It is demonstrated that the refrigerant mass flow rate, heat flux, water condensing rate and air outlet temperature of the evaporator significantly increase with air inlet relative humidity. As the air inlet relative humidity increases, the latent and total heat transfer rates increase, but the sensible heat transfer rate decreases. The purpose of this study is to provide experimental data on the effect of air inlet relative humidity on the air and refrigerant side pressure drop characteristics for a slit fin-tube heat exchanger. Experiments were carried out under the conditions of inlet refrigerant saturation temperature of 7 $^{\circ}C$ and mass flux varied from 150 to 250 kg/$m^2$s. The condition of air was dry bulb temperature of 27$^{\circ}C$, air Velocity Varied from 0.38 to 1.6 m/s. Experiments Showed that air Velocity decreased 8.7% on 50% of relative humidity 40% of that at degree of superheat of 5$^{\circ}C$, which resulted that pressure drop of air and refrigerant was decreased 20.8 and 8.3% for 50% of relative humidity as compared to 40%, respectively.