• 제목/요약/키워드: Power Consumption Capacity

검색결과 365건 처리시간 0.023초

종합병원의 전력소비 특성을 고려한 회귀분석이론을 이용한 수용률 기준 설정 (Recommended Practice for Demand Factor using Regression Analysis Theory depending on Power Consumption Characteristics in General Hospitals)

  • 김세동;신효섭;김수길;오기봉
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2005년도 학술대회 논문집
    • /
    • pp.233-237
    • /
    • 2005
  • It is increased electrical energy consumption with the development of intelligence society in the general hospitals and thus an energy conservation through efficient use of electricity became more important. This paper shows a reasonable design demand factor in office buildings, that was made by the systematic and statistical way considering actual conditions, such as investigated electric equipment capacity, peak power consumption, demand factor, etc., for 32 general hospitals and 9 electrical design offices. In this dissertation, it is necessary to analyse the key features and general trend from the investigated data. It made an analysis of the feature parameters, such as average, standard deviation, median, maximum, minimun and thus it was carried linear and nonlinear regression analysis.

  • PDF

회귀분석이론을 이용한 지하철 역사의 조명부하밀도 분석 (Recommended Practice for Lighting Load Density by Feature Parameters and Regression Analysis depending on Power Consumption Characteristics in Subway Stations)

  • 정현기;김세동
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2006년도 춘계학술대회 논문집
    • /
    • pp.254-259
    • /
    • 2006
  • It is increased electrical energy consumption with the development of intelligence society in the subway station and thus an energy conservation through efficient use of electricity became more important. This paper shows a reasonable design load density in subway stations, that was made by the systematic and statistical way considering actual conditions, such as investigated electric equipment capacity, peak power consumption, demand factor, etc., for 34 subway stations and 10 electrical design offices. In this dissertation, it is necessary to analyse the key features and general trend from the investigated data. It made an analysis of the feature parameters, such as average, standard deviation, median, maximum, maximum and thus it was carried linear and nonlinear regression analysis.

  • PDF

UML 상태 기계를 이용한 임베디드 소프트웨어의 소모 전력 분석 (Analysis of Power Consumption for Embedded Software using UML State Machine Diagram)

  • 이재욱;홍장의
    • 정보처리학회논문지D
    • /
    • 제19D권4호
    • /
    • pp.281-292
    • /
    • 2012
  • 스마트 폰과 같은 모바일 기기에서 동작하는 응용 소프트웨어는 제한된 배터리 용량으로 인하여 안정적인 서비스를 지속적으로 제공하는데 어려움을 갖는다. 과거에는 배터리의 수명을 연장 시키거나 소모전력이 적은 하드웨어 장치들을 개발하는 것으로 모바일 기기의 소모전력을 관리하였다. 그러나 시스템에 탑재되는 소프트웨어가 복잡해짐에 따라 소프트웨어에 대한 소모전력 분석 연구도 관심을 갖게 되었다. 이러한 연구들 중에서 모델 기반의 소모전력 분석은 코드가 개발되기 이전에 미리 소모전력을 분석하고, 분석 결과를 기반으로 소프트웨어를 개발한다는 측면에서 소모전력 감소를 위한 하나의 중요한 전략으로 인식되어 오고 있다. 따라서 본 논문에서는 소프트웨어의 행위 모델인 UML의 상태기계(State Machine) 다이어그램을 이용하는 소모전력 분석 기법을 제안한다. 제안하는 분석기법은 상태기계 다이어그램을 페트리 넷으로 변환하고, 이의 시뮬레이션을 통해 소모전력을 예측하게 된다.

배전선로 부하량 및 발전량 분석을 통한 신재생 접속허용용량 기준 상향에 대한 연구 (Increasing Hosting Capacity of Distribution Feeders by Analysis of Generation and Consumption)

  • 김성만
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제5권4호
    • /
    • pp.295-309
    • /
    • 2019
  • 본 논문은 신재생을 배전계통에 추가 수용하기 위해 배전계통의 접속허용기준을 상향하여 운전하는 방안을 검토하고 실증한 결과를 분석하는 내용을 다룬다. 대한민국의 배전계통의 경우, 일반적인 공용배전선로는 최대 10 MVA까지 신재생이 접속할 수 있도록 규정하고 있으며 신재생으로 인해 발생하는 역조류에 의해 계통전압이 전기사업법에서 지정한 범위를 초과하지 않아야 한다. 그러나 배전계통에 상시 존재하는 최소부하 및 발전원의 발전 특성에 따라 신재생을 추가 접속할 수 있는 여유용량이 존재할 수 있음을 고려해야 한다. 따라서 배전계통의 접속허용용량 기준 상향 검토를 위해, 신재생이 접속허용한도인 10 MVA만큼 최대한 접속된 상황에서 모든 신재생이 배전계통운영자에 의해 감시되고 있는 배전선로를 선정하여 단계적인 추가 접속을 시행하였다. 신재생으로 인한 배전계통의 전력조류와 전압 프로파일 영향을 분석함으로써 현재의 기준을 초과하여 신재생을 접속 시킬 때 발생 가능한 계통영향 분석과 더불어 향후 고려해야할 요인을 정의한다.

지하상가 부하설비의 사용특성과 전력관리 방안 연구 (A Study on the Reasonable Power Demand Method and Load Characteristics in Underground Streets)

  • 김세동;최도혁;류승기
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 A
    • /
    • pp.235-237
    • /
    • 1996
  • This paper shows a reasonable power demand method and load characteristics in underground streets, that was made by the systematic and statistical way considering actual conditions, such as investigated electric equipment capacity, electric power consumption, load characteristics, etc for 13 underground streets.

  • PDF

Evaluation of the Wind Power Penetration Limit and Wind Energy Penetration in the Mongolian Central Power System

  • Ulam-Orgil, Ch.;Lee, Hye-Won;Kang, Yong-Cheol
    • Journal of Electrical Engineering and Technology
    • /
    • 제7권6호
    • /
    • pp.852-858
    • /
    • 2012
  • This paper describes evaluation results of the wind power penetration limit (WPPL) and the wind energy penetration (WEP) in the Mongolian central power system (MCPS). A wind power plant (WPP) in a power system possesses an output power limit because the power system must maintain a balance between the generation and consumption of electricity at all times in order to achieve an adequate level of quality. The instantaneous penetration limit (IPL) of wind generation at a load is determined as the minimum of the three technical constraints: the minimum output, the ramp rate capability, and the spinning reserve of the conventional generating units. In this paper, a WPPL is defined as the maximum IPL divided by the peak load. A maximal variation rate (VR) of wind power is a major factor in determining the IPL, WPPL, and WEP. This paper analyzes the effects of the maximal VR of wind power on the WPPL, WEP, and capacity factor (CF) in the MCPS. The results indicate that a small VR can facilitate a large amount of wind energy while maintaining a high CF with increased wind power penetration.

상황인지 기반 데이터센터의 전력절감 모니터링 시스템에 관한 연구 (A Study on Energy Saving Monitoring System of Data Center based on Context Awareness)

  • 이화정;정민영;김창근;김현주
    • 융합정보논문지
    • /
    • 제9권1호
    • /
    • pp.19-27
    • /
    • 2019
  • 최근 IT기술의 발전에 따라 2025년 전 세계의 데이터 규모가 현재보다 10배 정도 증가할 것으로 예상한다. 이러한 인터넷 기술의 급속한 발전은 데이터센터 내에서 서버시스템의 고사양화와 저장매체의 대용량화 등을 초래하며, 이는 데이터센터의 전력 소비를 증가시키는 원인이 되고 있다. 이에 본 논문에서는 데이터센터의 서버시스템에 대한 전력 소모패턴을 분석하여 에너지 절전정책을 추천하고 이를 실시간으로 모니터링하는 시스템을 제안한다. 제안한 시스템은 데이터센터의 개별 서버시스템에 대한 전력 소모패턴을 모니터링하고 분석할 수 있으며, 서버시스템의 실제 동작 시간을 효율적으로 관리하여 데이터센터의 전체 전력소모량 대비 10% 내외 정도가 절감될 것으로 기대한다.

임대아파트의 전력소비특성을 고려한 변압기최대이용률 분석과 단위세대의 부하용량 적용 개선에 관한 연구 (A Study on the Application of Load Capacity by Unit Household and Analysis of Maximum Utilization Factor of Transformer with respect to Power Consumption Characteristics in the Lease Apartment)

  • 서승관;김세동;나채동;오용택
    • 조명전기설비학회논문지
    • /
    • 제24권2호
    • /
    • pp.127-132
    • /
    • 2010
  • 임대아파트의 전력용변압기 용량을 산정하는데 있어서 수용률 및 부등률, 단위세대의 표준 부하용량은 매우 중요한 기준이다. 본 연구에서는 60[$m^2$] 이하의 임대아파트를 대상으로 각 수용가의 계약전력과 최근 5년 동안의 최대전력을 조사하였다. 조사된 자료의 전체 특징과 중심적인 경향을 알아 보기 위해서 평균값 등의 특징파라미터를 분석하였고, 회귀분석을 통하여 그 경향을 분석하였다. 모든 단지가 전력용변압기의 여유가 많은 것으로 확인하였고, 적정용량 산정을 위한 단위세대의 부하용량 기준을 제안하였다.

유압펌프용 SRM 구동 시스템의 특성해석 (Characteristics Analysis of SRM Drive System for Hydraulic Pump)

  • 이주현;김봉철;김태형;안진우
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 춘계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.83-86
    • /
    • 2005
  • This paper proposed a hydraulic pump system which uses a variable SR drive and constant capacity pump. The base and maximum speed, torque are determined from displacement capacity of the pump and maximum pressure. The drive system is set to have a minimum power consumption having hydraulic preset pressure, which is operated within a maximum capacity and maximum preset pressure. This is achieved by controlling motor speed and power with feedback signal of pressure of the hydraulic pump. A 2.2kw, 12/8-pole SR motor and DSP based digital controller are designed and prototype drive system is manufactured. The proposed variable speed SR drive system is simulated and tested with experimental set-up. The test results show that the system has some good features such as high efficiency and high response characteristics.

  • PDF

사무소용 빌딩의 부하종별 전력소비특성 분석 및 수용률 기준 정립에 관한 연구 (Recommended Practice for o Reasonable Design Demand Factor and Analysis of Power Consumption Characteristics by Loads in Office Buildings)

  • 김세동;이진
    • 조명전기설비학회논문지
    • /
    • 제19권3호
    • /
    • pp.111-118
    • /
    • 2005
  • 사무소용 빌딩과 같은 전력다소비 건물에서는 전력의 효율적 이용에 의한 에너지절감을 위해서 설계 단계부터 합리적인 전기설비 설계가 요청되고 있다. 본 연구에서는 사무소용 빌딩을 중심으로 부하종류별 전력소비특성을 조사 분석하였고, 전기설계사무소의 설계단계에서 적용하는 수용률값을 조사하였다. 조사된 자료의 전체 특징과 중심적인 경향을 알아보기 위해서 평균값, 표준편차, 최대값, 최소값, 중앙값 등의 특징파라메터를 분석하였고, 회귀분석을 통한 선형적인 방법과 비선형적인 방법으로 그 경향을 확인하였다. 그 결과 합성 수용률/부등률 평균값은 $46.4[\%]$로 나타나 전력용변압기는 용량에 있어서 많은 여유를 가지고 있는 것으로 나타났다. 이를 토대로 변전설비 용량의 합리적인 설계를 위하여 부하종별 수용률 기준(안)을 제시하였고, 변전설비용량 산정에 필요한 자료를 데이터 베이스화하였다.