Abstract
It is increased electrical energy consumption with the development of intelligence society in the once buildings and thus an energy conservation through efficient use of electricity became more important. This paper shows a reasonable design demand factor in office buildings, that was made by the systematic and statistical way considering actual conditions, such as investigated electric equipment capacity, peak power consumption, demand factor, etc., for 54 office buildings and 34 electrical design offices. In this dissertation it is necessary to analyse the key features and general trend from the investigated data. It made an analysis of the feature parameters, such as average, standard deviation, median, maximum, minimum and thus it was carried the linear and nonlinear regression analysis.
사무소용 빌딩과 같은 전력다소비 건물에서는 전력의 효율적 이용에 의한 에너지절감을 위해서 설계 단계부터 합리적인 전기설비 설계가 요청되고 있다. 본 연구에서는 사무소용 빌딩을 중심으로 부하종류별 전력소비특성을 조사 분석하였고, 전기설계사무소의 설계단계에서 적용하는 수용률값을 조사하였다. 조사된 자료의 전체 특징과 중심적인 경향을 알아보기 위해서 평균값, 표준편차, 최대값, 최소값, 중앙값 등의 특징파라메터를 분석하였고, 회귀분석을 통한 선형적인 방법과 비선형적인 방법으로 그 경향을 확인하였다. 그 결과 합성 수용률/부등률 평균값은 $46.4[\%]$로 나타나 전력용변압기는 용량에 있어서 많은 여유를 가지고 있는 것으로 나타났다. 이를 토대로 변전설비 용량의 합리적인 설계를 위하여 부하종별 수용률 기준(안)을 제시하였고, 변전설비용량 산정에 필요한 자료를 데이터 베이스화하였다.