• 제목/요약/키워드: Phasor Estimation

검색결과 57건 처리시간 0.029초

Algorithm for Fault Location Estimation on Transmission Lines using Second-order Difference of a Positive Sequence Current Phasor

  • Yeo, Sang-Min;Jang, Won-Hyeok;Kim, Chul-Hwan
    • Journal of Electrical Engineering and Technology
    • /
    • 제8권3호
    • /
    • pp.499-506
    • /
    • 2013
  • The accurate estimation of a fault location is desired in distance protection schemes for transmission lines in order to selectively deactivate a faulted line. However, a typical method to estimate a fault location by calculating impedances with voltages and currents at relaying points may have errors due to various factors such as the mutual impedances of lines, fault impedances, or effects of parallel circuits. The proposed algorithm in this paper begins by extracting the fundamental phasor of the positive sequence currents from the three phase currents. The second-order difference of the phasor is then calculated based on the fundamental phasor of positive sequence currents. The traveling times of the waves generated by a fault are derived from the second-order difference of the phasor. Finally, the distance from the relaying point to the fault is estimated using the traveling times. To analyze the performance of the algorithm, a power system with EHV(Extra High Voltage) untransposed double-circuit transmission lines is modeled and simulated under various fault conditions, such as several fault types, fault locations, and fault inception angles. The results of the simulations show that the proposed algorithm has the capability to estimate the fault locations with high speed and accuracy.

디지털주파수계전기의 고속 샘플링추정기법 (A Technique for Fast Sampling Measurement of Digital Frequency Relay)

  • 남시복;이훈구;마석범;김진수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 학술대회 논문집 전문대학교육위원
    • /
    • pp.185-190
    • /
    • 2006
  • Frequency and phasor are the most important quantities in power system operation because they can reflect the whole power system situation. Frequency reflects the dynamic energy balance between load and generating power, while operators use phasor to constitute the state of system and, moreover, phasor based line relays are currently used in most power systems. So frequency and phasor are regarded as indices for the operating power systems in practice. The proposed technique is suitable for estimation near-nominal, nomina), and off-nominal frequencies. It is useful in designing microprocessor-based relays and meters that need to measure power system frequency. Performance test results, using signals from EMTP source and Excel program, indicate that the proposed technique can provide accurate estimates within 16ms. Maximum estimation errors observed during testing are of the order of 0.006Hz for nominal, near-nominal, and off-nominal frequencies. The proposed technique provides accurate estimates in presence of noise and harmonics and in case ground fault. The rate change of the phase angle is used for estimation. To confirm the validity of the proposed algorithm, the simulation studies carried out on a typical 154[KV] double T/L system by using EMTP software. Some test results are presented in the paper.

  • PDF

지수 감쇄하는 DC 옵셋 영향을 제거한 푸리에 변환 기반 페이져 연산 기법 기법 (Fourier Transform-Based Phasor Estimation Method Eliminating the Effect of the Exponentially Decaying DC offsets)

  • 이동규;김철훈;강상희
    • 전기학회논문지
    • /
    • 제57권9호
    • /
    • pp.1485-1490
    • /
    • 2008
  • This paper proposes a new Fourier transform-based phasor estimation method to eliminate the adverse influence of the exponentially decaying dc offsets when Discrete Fourier Transform (DFT) is used to calculate the phasor of the fundamental frequency component in a relaying signal. By subtracting the result of odd-sample-set DFT from the result of even-sample-set DFT, the information of dc offsets can be obtained. Two dc offsets in a relaying signal are treated as one dc offset which is piecewise approximated in one cycle data window. The effect of the dc offsets can be eliminated by the approximated dc offset. The performance of the proposed algorithm is evaluated by using computer-simulated signals and EMTP-generated signals. The algorithm is also tested on a hardware board with TMS320C32 microprocessor. The evaluation results indicate that the proposed algorithm has the stable and accurate eliminating performance even if the input signal contains two decaying dc components having different time constants.

DC 옵셋의 영향을 제거한 페이저 연산 기법 (Phasor Estimation Method Eliminating the Effect of the DC offsets)

  • 이동규;김형규;권영진;강상희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.203_204
    • /
    • 2009
  • In this paper, we propose a Fourier transform-based modified phasor estimation method to eliminate the adverse influence of exponentially decaying DC offsets. Discrete Fourier Transform (DFT) is generally used to calculate the phasor of the fundamental frequency component in digital protective relays. However, the output of the DFT contains an error due to exponentially decaying DC offsets. Therefore, the decaying DC components should be taken into consideration when calculating the phasor of the fundamental frequency component of a relaying signal. In this paper, the error due to DC offsets in a DFT is calculated and eliminated using the outputs of quaternity DFT, so that the phasor of the fundamental component can be accurately estimated. The performance of the proposed algorithm is evaluated by using computer-simulated signals and EMTP-generated signals. A performance evaluation showed that the proposed algorithm was not affected by system and fault conditions. Thus, the proposed algorithm can effectively suppress the adverse influence of DC offsets in a relaying signal.

  • PDF

An Improved Technique for Fault Location Estimation Considering Shunt Capacitance on Transmission Line

  • Kim Hyun-Houng;Jeong Yun-Won;Lee Chan-Joo;Park Jong-Bae;Shin Joong-Rin
    • Journal of Electrical Engineering and Technology
    • /
    • 제1권3호
    • /
    • pp.295-301
    • /
    • 2006
  • This paper presents a new two-terminal numerical algorithm for fault location estimation using the synchronized phasor in time-domain. The proposed algorithm is also based on the synchronized voltage and current phasor measured from the PMUs (Phasor Measurement Units) installed at both ends of the transmission lines. In this paper, the algorithm is given without shunt capacitance and with shunt capacitance using II -model and estimated using DFT (Discrete Fourier Transform) and LES (Least Error Squares Method). The algorithm uses a very short data window and classification for real-time transmission line protection. To verify the validity of the proposed algorithm, the Electro-Magnetic Transient Program (EMTP) and MATLAB are used.

A Method for Estimating an Instantaneous Phasor Based on a Modified Notch Filter

  • Nam Soon-Ryul;Sohn Jin-Man;Kang Sang-Hee;Park Jong-Keun
    • Journal of Electrical Engineering and Technology
    • /
    • 제1권3호
    • /
    • pp.279-286
    • /
    • 2006
  • A method for estimating the instantaneous phasor of a fault current signal is proposed for high-speed distance protection that is immune to a DC-offset. The method uses a modified notch filter in order to eliminate the power frequency component from the fault current signal. Since the output of the modified notch filter is the delayed DC-offset, delay compensation results in the same waveform as the original DC-offset. Subtracting the obtained DC-offset from the fault current signal yields a sinusoidal waveform, which becomes the real part of the instantaneous phasor. The imaginary part of the instantaneous phasor is based on the first difference of the fault current signal. Since a DC-offset also appears in the first difference, the DC-offset is removed trom the first difference using the results of the delay compensation. The performance of the proposed method was evaluated for a-phase to ground faults on a 345kV 100km overhead transmission line. The Electromagnetic Transient Program was utilized to generate fault current signals for different fault locations and fault inception angles. The performance evaluation showed that the proposed method can estimate the instantaneous phasor of a fault current signal with high speed and high accuracy.

A DFT Based Filtering Technique to Eliminate Decaying dc and Harmonics for Power System Phasor Estimation

  • Oh Yong- Taek;Balamourougan V.;Sidhu T.S.
    • KIEE International Transactions on Power Engineering
    • /
    • 제5A권2호
    • /
    • pp.138-143
    • /
    • 2005
  • During faults, the voltage and current signals available to the relay are affected by the decaying dc component and harmonics. In order to make appropriate and accurate decisions, most of the relaying algorithms require the fundamental frequency phasor information that is immune to decaying dc effect and harmonics. The conventional Fourier ph as or estimation algorithm is affected by the presence of decaying-exponential transients in the fault signal. This paper presents a modified Fourier algorithm, which effectively eliminates the decaying dc component and the harmonics present in the fault signal. The decaying dc parameters are estimated by means of an out-of-band filtering technique. The decaying dc offset and harmonics are removed by means of a simple computational procedure that involves the design of two sets of Orthogonal digital OFT filters tuned at different frequencies and by creating three off-line look-up tables. The technique was tested for different decay rates of the decaying dc component. It was also compared with the conventional mimic plus the full cycle OFT algorithm. The results indicate that the proposed technique has a faster convergence to the desired value compared to the conventional mimic plus OFT algorithms over a wide range of decay rates. In all cases, the convergence to the desired value was achieved within one cycle of the power system frequency.

칼만필터링에 의한 디지털 거리계전 기법에 관한 연구 (A Study on the Digital Distance Relaying Techniques Using Kalman Filtering)

  • 김철환;박남옥;신명철
    • 대한전기학회논문지
    • /
    • 제41권3호
    • /
    • pp.219-226
    • /
    • 1992
  • In this study, Kalman filtering theory is applied to the estimation of symmetrical components from fault voltage and current signal when it comes to faults with the power system. An algorithm for estimating fault location accurately and quickly by calculating the symmetrical components from the extracted fundamental voltage phasor and current phasor is presented. Also, to confirm the validity of digital distance relaying techniques using Kalman filtering, the experimental results obtained by using the digital simulation of power system is shown.

  • PDF

아크 지락 사고에 대한 사고거리추정 및 사고판별에 관한 자동 적응자동재폐로 기법 (Adaptive AutoReclosure Technique for Fault Location Estimation and Fault Recognition about Arcing Ground Fault)

  • 김현홍;이찬주;채명석;박종배;신중린
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.283-285
    • /
    • 2005
  • This paper presents a new two-terminal numerical algorithm for fault location estimation and for faults recognition using the synchronized phasor in time-domain. The proposed algorithm is also based on the synchronized voltage and current phasor measured from the PMUs(Phasor Measurement Units) installed at both ends of the transmission lines. Also the arc voltage wave shape is modeled numerically on the basis of a great number of arc voltage records obtained by transient recorder. From the calculated arc voltage amplitude it can make a decision whether the fault is permanent or transient. In this paper the algorithm is given and estimated using DFT(Discrete Fourier Transform) and the LES(Least Error Squares Method). The algorithm uses a very short data window and enables fast fault detection and classification for real-time transmission line protection. To test the validity of the proposed algorithm, the Electro-Magnetic Transient Program(EMTP/ATP) and MATLAB is used.

  • PDF

송전선로 파라메터 정밀 예측을 위한 페이저 측정기의 응용 (Estimation Technique of Power Transmission Line Parameter by Phasor Measurement Units)

  • 조기선;박종배;신중린
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 A
    • /
    • pp.193-195
    • /
    • 2003
  • This paper presents an approach to estimate the power transmission line parameter by phasor measurement units(PMUs), which are synchronized to 1 pps signal of GPS. Existing approaches to estimate power transmission line parameter, are mainly off-line ones, based on faults or switching events on other neighboring lines. In this paper, to obtain static and dynamic properties of power transmission line parameter in service, the prototype of pmu-based Transmission Line Parameter Monitoring System (TLPMS) is proposed. Also, an technique to estimate parameters of transmission line described as 2-port network model and the soundness of estimated parameters are addressed.

  • PDF