• 제목/요약/키워드: Partial discharge source

검색결과 98건 처리시간 0.023초

모노폴 안테나를 이용한 유중 부분방전의 검출 (Detection of Partial Discharges by a Monopole Antenna in Insulation Oil)

  • 박대원;이정윤;길경석
    • 한국전기전자재료학회논문지
    • /
    • 제25권9호
    • /
    • pp.727-731
    • /
    • 2012
  • This paper dealt with the measurement and analysis of electromagnetic waves radiated from a partial discharge (PD) source in insulation oil to apply condition monitoring of oil-immersed transformers. Two types of narrow-band monopole antennas with the resonant frequency of a 500 MHz and a 1 GHz were designed and fabricated. Also, a needle-plane electrode system was manufactured to simulate PDs and the curvature radius of the needle is 10 ${\mu}m$ and the diameter of the plane is 60 mm. Electromagnetic wave was measured by the PD measurement system with the monopole antennas. Detection sensitivity of the fabricated antenna was compared for the same PD magnitude; 620 $mV_{peak}$ for the 500 MHz antenna and 960 $mV_{peak}$ for the 1 GHz antenna to the PD magnitude of 74 pC. Consequently, the 1 GHz monopole antenna is more effective to detect PDs in oil-immersed transformers.

PPS 소자가 삽입된 N형 SCR 소자에서 부분웰 구조가 정전기 보호 성능에 미치는 영향 (Effects on the ESD Protection Performance of PPS(PMOS Pass Structure) Embedded N-type Silicon Controlled Rectifier Device with different Partial P-Well Structure)

  • 양준원;서용진
    • 한국위성정보통신학회논문지
    • /
    • 제9권4호
    • /
    • pp.63-68
    • /
    • 2014
  • PPS 구조를 갖는 N형 실리콘 제어 정류기 소자에서 부분웰 구조가 정전기 보호 성능에 미치는 영향을 고찰하였다. 종래의 NSCR 표준소자는 온-상태 저항, 스냅백 홀딩 전압 및 열적 브레이크다운 전압이 너무 낮아 정전기 보호소자의 필요조건을 만족시키지 못해 적용이 어려웠으나, 본 연구에서 제안하는 부분웰 구조를 갖도록 변형 설계된 NSCR-PPS 소자는 안정한 정전기보호 성능을 나타내어 고전압 동작용 마이크로 칩의 정전기보호 소자로 적용 가능함을 확인하였다.

유중 부분방전의 음향검출에 관한 연구 (A Study on the Acoustic Detection of Partial Discharges in Insulation Oil)

  • 길경석;김성욱;박대원;김선재;송재만
    • 한국전기전자재료학회논문지
    • /
    • 제23권1호
    • /
    • pp.53-60
    • /
    • 2010
  • This paper dealt with the acoustic detection of partial discharge (PD) in insulation oil for insulation diagnostics of oil immersed transformers. Electrode systems such as needle to plane, plane to plane, and floating were fabricated to simulate some defects in transformers. A wide band acoustic emission(AE) sensor with the frequency ranges of 100 kHz~1 MHz and a narrow band AE sensor with the resonant frequency of 140 kHz were used in the experiment. Also, a decoupler and an amplifier were designed to detect and amplify the acoustic signal only. The decoupler separates acoustic signal from DC source without any distortion, and the amplifier has the gain of 40 dB in frequency ranges of 11 kHz~4 MHz. In the experiment, frequency components and propagation characteristics of acoustic signal were analyzed, and an algorithm of positioning of PD occurrence by the time difference of arrival was proposed. From the results, the frequency components of the acoustic signal exist from 50 kHz to 200 kHz and the positioning error of PD calculated by three AE sensors was within 1%.

대기압하에서 액체질소(LN2)방전특성에 관한 연구 (A study on the discharge characteristics of liquid nitrogen at atmospheric pressure)

  • 이영근;주재현;김상구;이광식;이동인
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 1993년도 추계학술발표회논문집
    • /
    • pp.58-62
    • /
    • 1993
  • This paper shows the discharge characteristics of liquid nitrogen under plane to plane electrode, needle to plance electrode, inserting teflon insulator in plane to plane electrode at atmospheric pressure. The main experimental device of this paper is cryostat. The important results obtained from this study are sa follows. Breakdown voltage of LN2 under N-P electrode is higher than that of under P-P electrode at atmospheric pressure. Breakdown duration time is longer with increase of electode gap under the P-P, N-P electrodes. The formation of bubbles by evaporation is observed in spite of non-applying source at atmospheric pressure and the creation of corona confirmed. Breakdown voltage and breakdown duration time are in proportion to increase of diameter in case of inserting teflon insulator. Partial discharge characteristics of thickness 0.5[mm] is that 채굼 voltage of teflon insulator rose with increase of diameter in each [pps].

  • PDF

Numerical Study of Estimating the Arrival Time of UHF Signals for Partial Discharge Localization in a Power Transformer

  • Ha, Sang-Gyu;Cho, Jeahoon;Lee, Juneseok;Min, Byoung-Woon;Choi, Jaehoon;Jung, Kyung-Young
    • Journal of electromagnetic engineering and science
    • /
    • 제18권2호
    • /
    • pp.94-100
    • /
    • 2018
  • Partial discharges (PDs) are electrical sparks that occur inside insulation between two conducting electrodes and can lead to the disastrous failure of insulation systems. To determine the location of a PD, a distributed array of UHF PD sensors is used to detect the electromagnetic (EM) signals emitted from the PD source, and the localization of the PD source can be estimated using the time difference of arrival (TDOA) between EM signals captured by the UHF PD sensor array. There are four popular methods to estimate the TDOA-the first peak method, the cross-correlation method, the energy criterion method, and the average time window threshold method. In this work, we numerically investigate the influence of noise on estimating the TDOA for the four different methods. Numerical results show that the energy criterion method is more robust against noise than other methods.

METHOD TO REDUCE THE SPURIOUS PEAKS IN THE CROSS-CORRELATION FOR THE PD LOCATING

  • Chung C.S.;Kim, J.C.;Kwak, H.R.
    • 한국음향학회:학술대회논문집
    • /
    • 한국음향학회 1994년도 FIFTH WESTERN PACIFIC REGIONAL ACOUSTICS CONFERENCE SEOUL KOREA
    • /
    • pp.781-784
    • /
    • 1994
  • Detecting partial discharge(PD) and locating its source are one of many diagnosis methods. Location the PD source is very important to reduce the time and cost of repairing power transformers. And to locate the PD source, the cross-correlation method is a well known one. But there many spurious peaks in cross-correlation, and occasionally, some peaks could be bigger than the true one. In order to analysis these spurious peaks and to reduce them, we have done many experiments and simulations. As the results we could reduce the spurious peaks, and get well defined cross-correlation from which it is easy to locate the PD source accurately.

  • PDF

SF6 가스 중 직류 고전압 하에서 부분방전 특성 (Characteristics of Partial Discharge Under HVDC in SF6 Gas)

  • 김민수;김선재;정기우;조향은;길경석
    • 한국전기전자재료학회논문지
    • /
    • 제27권4호
    • /
    • pp.238-243
    • /
    • 2014
  • This paper dealt with the measurement and analysis of partial discharge (PD) under high voltage direct current (HVDC) in SF6 gas. Electrode systems such as a protrusion on conductor (POC), a protrusion on enclosure (POE), a crack on epoxy plate and a free particle (FP) were fabricated to simulate the insulation defects. The analysis system was designed with a Time-Frequency (T-F) map algorithm programed based on LabVIEW. This can arrange the acquired PD pulses into frequency and time domain. A HVDC power source is composed of a transformer (220 V/50 kV), a diode (100 kV) and a capacitor (50 kV, 0.5 ${\mu}F$). The gap between the electrodes is 3 mm, and the $SF_6$ gas was set at 5 bar. PD pulses were detected by a 50 ${\Omega}$ non-inductive resistor. In the analysis, PD pulses were distributed below 0.5 MHz and 20 ns ~ 35 ns for the POC, 0.7 MHz ~ 1.7 MHz, below 0.6 MHz and 10 ns ~ 40 ns and 60 ns ~125 ns for the POE, below 0.1 MHz and 135 ns ~ 215 ns for the crack, and below 1.6 MHz and 250 ns for the FP.

부분방전원 분류기법의 패턴분류율 비교 (Comparison of Classification rate of PD Sources)

  • 박성희;임기조;강성화
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2005년도 하계학술대회 논문집 Vol.6
    • /
    • pp.566-567
    • /
    • 2005
  • Until now variable pattern classification methods have been introduced. So, variable methods in PD source classification were applied. NN(neural network) the most used scheme as a PD(partial discharge) source classification. But in recent year another method were developed. These methods is present superior to NN in the field of image and signal process function of classification. In this paper, it is show classification result in PD source using three methods; that is, BP(back-propagation), ANFIS(adaptive neuro-fuzzy inference system), PCA-LDA(principle component analysis-linear discriminant analysis).

  • PDF

Microphone Array를 이용한 고압설비의 고장위치인식 알고리즘 (An Accidental Position Detection Algorithm for High-Pressure Equipment using Microphone Array)

  • 김득권;한순신;하현욱;이장명
    • 전기학회논문지
    • /
    • 제57권12호
    • /
    • pp.2300-2307
    • /
    • 2008
  • This study receives the noise transmitted in a constant audio frequency range through a microphone array in which the noise(like grease in a pan) occurs on the power supply line due to the troublesome partial discharge(arc). Then by going through a series of signal processing of removing noise, this study measures the distance and direction up to the noise caused by the troublesome partial discharge(arc) and monitors the result by displaying in the analog and digital method. After these, it determines the state of each size and judges the distance and direction of problematic part. When the signal sound transmitted by the signal source of bad insulator is received on each microphone, the signal comes only in the frequency range of 20 kHz by passing through the circuit of amplification and 6th low pass filter. Then, this signal is entered in a digital value of digital signal processing(TMS320F2812) through the 16-bit A/D conversion. By doing so, the sound distance, direction and coordinate of bad insulator can be detected by realizing the correlation method of detecting the arriving time difference occurring on each microphone and the algorithm of detecting maximum time difference.

광섬유 Mach-Zehnder 간섭계를 이용한 부분방전 초음파 검출특성 (Detecting Characteristics of Ultrasonics Generated by Partial Discharge in Insulating Oil Using the Optical Fiber Mach-Zehnder Interferometer)

  • 이상훈;심승환;이광식;김달우
    • 조명전기설비학회논문지
    • /
    • 제17권4호
    • /
    • pp.50-56
    • /
    • 2003
  • 본 논문에서는 유입변압기 진단을 목적으로 부분방전시 발생하는 여러 가지 물리적 화학적 현상중 초음파를 검출하기 위하여 광섬유 Mach-Zehnder 간섭계를 구성하였다. 구성된 광섬유 센서의 초음파 검출 평가 실험을 실시하고, 절연유 중에 배치한 침-평판전극에 교류 고전압을 인가하여 방전시 발생하는 초음파를 측정하고 퓨리에 변환 및 wavelet 변환을 이용한 데이터 분석 결과를 나타냈다.