• 제목/요약/키워드: Overcurrent Ground Relay

검색결과 8건 처리시간 0.022초

DC 급전시스템의 지락보호계전시스템 개발 (Development of Ground Fault Protective Relaying Schemes for DC Traction Power Supply System)

  • 정상기;정락교;조홍식;이안호;권삼영
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제54권9호
    • /
    • pp.427-433
    • /
    • 2005
  • In DC tracking power supply system, ground faults are currently detected by the potential relay, 64P. Though 64P relay detects ground fault, it cannot Identify the faulted region which causes long traffic delays and safety problem to passengers. Two new ground fault protective relay schemes that can identify the faulted region are presented in this paper. One is bus differential protective relay and the other is ground overcurrent protective relay. Both type of relays is similar in principle to the ordinary bus differential protective relay and the ground overcurrent relay used in other power system. In DC traction power supply system, since it is ungrounded, ground fault current is not big enough to operate those relays. To solve the problem, a current control device, called device 'X', is newly introduced in both system, which enables large amount of ground fault current flow upon the positive line to ground fault. Algorithms for these relays are developed and their validity are verified by EMTP simulation.

비상발전기 보호용 원판형 지락과전류계전기의 고조파영향에 관한 연구 (A Study on the Harmonics Effect of Disc-Type Over Current Ground Relay for Emergency Generator Protection)

  • 김경철;고훈
    • 조명전기설비학회논문지
    • /
    • 제29권6호
    • /
    • pp.58-62
    • /
    • 2015
  • When an emergency generator is running, it supplies the power for critical loads. Generator protection requires the consideration of many abnormal conditions that may occur with generators include overvoltages and ground faults. Modern day power systems create harmonics within the electrical network that can have an impact upon the associated protective system. This paper focuses on the analysing of the cause and development of a solution for the malfunction of induction disc type overcurrent ground relay by generation of harmonics during emergency generator operation.

웨이브렛 변환을 이용한 철도 고압배전선로의 고장검출기법 (Fault Detection Technique in Railway High Voltage Distribution Lines using Wavelet Transform)

  • 정호성;한문섭;이장무;김주락;이한민
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2004년도 춘계학술대회 논문집
    • /
    • pp.1274-1279
    • /
    • 2004
  • This paper proposes technique to detect ground fault in railway high voltage distribution lines. Overcurrent relay technique is widely used for detecting one line ground fault that occurs most frequently in railway high voltage distribution lines. However, ground fault in distribution line is usually high impedance fault with arc. Because the fault current magnitude measured in substation is very small, the conventional overcurrent relay can't detect the high impedance ground fault. Therefore this paper proposes the advanced technique using wavelet transform. It extracts D1 component from fault signals and detects fault comparing magnitude of D1 component in each phase. To evaluate this proposed technique, we model distribution system using PSCAD/EMTDC and extract various fault data. In conclusion this technique can detect ground fault including high impedance fault regardless of fault distance, fault impedance etc.

  • PDF

방향지락과전류계전기를 이용한 고저항지락사고 검출능력의 향상방안 (A New Scheme to Improve High Impedance Fault Detection Capability Using Directional Over-Current Ground Relay)

  • 이승재;임종윤;김일동;한경남
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 D
    • /
    • pp.1000-1002
    • /
    • 1997
  • In this paper we proposes a scheme which can improve the detecting capability of the high impedance fault of the conventional distance relaying. It utilizes the directional ground overcurrent relay called HIFR together with the distance relay in order to secure the security and selectivity.

  • PDF

분산전원 연계선로에서 지락고장시 중성선의 과전류 해석 및 보호계전기의 새로운 알고리즘 (An Overcurrent Analysis in Neutral Line and Algorithm to Prevent Malfunction of Relay in Distributed Generations)

  • 신동열;김동명;차한주
    • 전기학회논문지
    • /
    • 제58권10호
    • /
    • pp.1916-1922
    • /
    • 2009
  • Introducing distributed generators(DGs) to utility distribution system can cause malfunction of relay on the grid when ground faults or severe load unbalances are occurred on the system. Because DGs interconnected to the grid can contribute fault currents and make bidirectional power flows on the system, fault currents from DGs can cause an interference of relay operation. A directional over current relay(DOCR) can determine the direction of power flow whether a fault occurs at the source side or load side through detecting the phases of voltage and current simultaneously. However, it is identified in this paper that the contributed fault current(Ifdg) from the ground source when was occurred to contribute single-line-to-ground(SLG) fault current, has various phases according to the distances from the ground source. It means that the directionality of Ifdg may not be determined by simply detecting the phases of voltage and current in some fault conditions. The magnitude of Ifdg can be estimated approximately as high as 3 times of a phase current and its maximum is up to 2,000 A depending on the capacity of generation facilities. In order to prevent malfunction of relay and damage of DG facilities from the contribution of ground fault currents, Ifdg should be limited within a proper range. Installation of neutral ground reactor (NGR) at a primary neutral of interconnection transformer was suggested in the paper. Capacity of the proposed NGR can be adjusted easily by controlling taps of the NGR. An algorithm for unidirectional relay was also proposed to prevent the malfunction of relay due to the fault current, Ifdg. By the algorithm, it is possible to determine the directionality of fault from measuring only the magnitude of fault current. It also implies that the directionality of fault can be detected by unidirectional relay without replacement of relay with the bidirectional relay.

풍력발전단지 연계 전용선로 보호계전방식의 향상에 대한 연구 (A Study on the Improved Protective Relaying Algorithm Applied in the Linked System Interconnecting Wind Farm with the Utilities)

  • 장성일;김광호;권혁완;김대영;권혁진
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제52권12호
    • /
    • pp.675-683
    • /
    • 2003
  • This paper describes the correction strategy of an overcurrent relay applied in the linked line for interconnecting wind farm with utility power networks in order to improve the capability of a fault detection. The fault current measured in a relaying point might vary according to the fault conditions. Generally, the current of the line to line fault or the line to ground fault in the linked line is much higher than the set value of protective relay due to the large fault level. However, when the high impedance fault occurs in the linked line, we can't detect it by conventional set value because its fault level may be lower than the generating capacity of wind farm. And, the protective relay with conventional set value may generate a trip signal for the insertion of wind turbine generators due to the large transient characteristics. In order to solve above problems and improve protective relaying algorithms applied in the linked line, we propose a new correction strategy of the protective relay in the linked line. The presented method can detect the high impedance fault which can't be detected by conventional relay set value and may prevent the mis-operation of protective relay caused by the insertion of wind farm.

발전기 고장보호를 위한 디지털 계전기에 관한 연구 (A Study on the Digital Protective Relay for Generator Fault Protection)

  • 장낙원;박정도;이성환
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제33권8호
    • /
    • pp.1232-1238
    • /
    • 2009
  • 전력설비의 대용량, 고전압화 됨에 따라 발전기 고장 예방을 위한 고장보호시스템의 필요성이 점차 증대되고 있다. 신속하고 신뢰성 있게 운전하며 보호하는 발전기 보호제어 시스템의 개발이 시급히 요구된다. 본 논문에서는 전력 공급의 안정을 도모하고 대용량, 고전압화 되는 발전기의 고장 예방을 위한 발전기 보호기능을 갖춘 디지털 보호계전기 설계에 관한 연구를 수행하였다. 디지털 계전기의 발전기 고장보호에 사용되는 고장보호 알고리즘을 개발하였고 디지털보호계전기 H/W를 설계 제작하였다.

송전계통 고저항지락사고 보호를 위한 지락과전류계전기 적용방안 (The application of Overcurrent Ground Relay(OCGR) for High Impedance Fault Protection in Transmission Systems)

  • 이승재;임종윤;이종범;김철환;김영한;김일동;한경남
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 추계학술대회 논문집 학회본부
    • /
    • pp.127-129
    • /
    • 1996
  • 고저항지락사고시 선로의 지락후비보효용인 지락거리계전기 및 변압기 후비보호용 방향지락과 전류계전기의 비협조 문제로 인하여 광범위한 정전이 유발될수 있다. 본 논문에서는 이에 대한 대책으로 고저항지락보호용 과전류계전기의 도입과 적용방안에 대하여 제안한다.

  • PDF