• Title/Summary/Keyword: NES 713 test

Search Result 6, Processing Time 0.018 seconds

Experiments on the Behavior of Underground Utility Cable in Fire (지하구 케이블의 연소특성 실험)

  • 박승민;김운형;윤명오
    • Fire Science and Engineering
    • /
    • v.16 no.2
    • /
    • pp.75-80
    • /
    • 2002
  • In this paper, some experiments of a heat release rate and toxicity for underground utility 22.9kv cable in fire was conducted and analysed applying plume equation and smoke chamber test separately, A 22.9 ㎸ power cable is selected for testing heat release in ISO 9705 geometry and toxicity production is measured with NES 713 (British-Naval Engineering Standard)test. In test results, Cable heat release reached about 60 ㎾ above 1.2 m from heptane pan and CO generated lethal concentration under 30 min. exposure condition.

A Study on the Toxic Gases and Smoke Hazard of PASCON Trough (파스콘 트로프의 연기유독성에 관한 연구)

  • Lee, Chang-Woo;Hyun, Seong-Ho;Choi, Don-Mook
    • Fire Science and Engineering
    • /
    • v.20 no.2 s.62
    • /
    • pp.1-7
    • /
    • 2006
  • The aim of the research is to estimate the effect of smoke and combustion gases on humane body indirectly through measuring the toxicity of those. For this purpose, the toxic index of smoke and combustion gases was investigated by smoke hazard test and analysis of smoke which were conducted by KS F 2271 and NES 713 method respectively. It i s proved by KS F 2271 method that PASCON trough is suitable to the testing standard of interior material and construction of building. In addition, it is identified by NES 713 method that combustion gases occurring in PASCON product were only carbon dioxide and carbon monoxide, and the smoke index of those was 0.944. This value means that the hazard effect of smoke gases on humane ! body can possibly happens when exposed to the smoke gases for more than 30 min. In aspect of the domestic situation that have not regulated the hazard estimation and the emissions of smoke when the flame retarding ability of the products have been requested, the toxic indexes of PASCON products are comparatively low.

Hazard Assessment of Combustion Gases from Interior Materials (주요 건축 내장재의 연소가스 유해성 평가)

  • Seo, Hyun Jeong;Son, Dong Won
    • Fire Science and Engineering
    • /
    • v.29 no.4
    • /
    • pp.49-56
    • /
    • 2015
  • Toxic gases from five types of interior building materials were investigated according to Naval Engineering Standard (NES) 713. The materials were plywood, indoor wall coverings (wood wall plate members and pine wood), reinforced Styrofoam insulation, laminate flooring, and PVC. Specimens were measured using an NES 713 toxicity test apparatus to analyze the hazardous substances in combustion gas from the materials. We used the US Department of Defense standard (MIL-DTL, Military Standard) to calculate the toxicity index of the combustion gas. Emissions of $CO_2$ from all specimens did not exceed the NES 713 limit of 100,000 ppm. The amount of CO gas emissions from reinforced Styrofoam insulation was 6,098 ppm. 25 ppm and 49 ppm of formaldehyde were released from the reinforced Styrofoam insulation and PVC flooring, respectively. These values were less than the limit of 400 ppm. The highest emissions were from $NO_X$ emitted by plywood and were above the limit of 250 ppm. The toxicity index of the specimens were calculated as 5.19 for plywood, 4.13 for PVC flooring, 2.35 for reinforced Styrofoam insulation, 2.34 for laminate flooring, and 1.22 for indoor wall coverings (pine wood). Our research helps us to understand the properties of these five interior materials by analyzing the combustion gas and explaining the toxicity of constituents and the toxicity index. Also, it would be useful for giving fundamentals to guide the safe use of interior materials for applications.

A Toxicity of Interior Upholstery in Apartment Housing (아파트 마감재의 연기 유독성)

  • Ham, Sang-Keun;Kim, Hong;Han, Sang-Bum;Kim, Woon-Hyung
    • Fire Science and Engineering
    • /
    • v.15 no.3
    • /
    • pp.36-43
    • /
    • 2001
  • Several types of widely used interior upholsteries including wallpaper, veneer board and floor cover, were selected to be evaluated by using the method of NES 713 text. Test results indicates that a fire with retardant wallpaper release a large amount of toxic gases when constantly exposed to a fire source. When evaluated in terms of the masses of released gases, the release of Carbon monoxide appears the highest in case of wallpaper fire, while the ratio of CO/Mass loss appears the highest in case of floor cover fire. Therefore, it can be concluded that, a large amount of toxic gas will release from a floor cover fire with even a small quantity of fuel.

  • PDF

Experimental Study on the Toxicity Characteristics of Non-Class 1E Cables according to Accelerated Deterioration (가속열화에 따른 비안전등급 케이블의 독성특성에 관한 실험적 연구)

  • Jang, Eun-Hui;Kim, Min-Ho;Lee, Min Chul;Lee, Sang-Kyu;Moon, Young-Seob
    • Fire Science and Engineering
    • /
    • v.33 no.6
    • /
    • pp.105-113
    • /
    • 2019
  • This study investigates the toxicity characteristics of two Non-Class 1E Cables (For security reasons, we refer to company A and company B) used in nuclear power plants according to the accelerated deterioration period. In accordance with NES 713 test equipment and standards, tests were carried out on non-aged cables and the cables subjected to 20- and 40-year-accelerated-deterioration; each of the cables was further classified into sheath and insulation. The test results showed that the toxicity indices of 20- and 40-year-accelerated-aged cables were higher than those for the non-aged cables, and 20-year-aged cables of both A and B companies showed the highest toxicity indices. This is attributed to the extensive emissions of carbon monoxide and halide gases such as hydrogen chloride and hydrogen bromide. Furthermore, to analyze the toxicity indices of sheath and insulation in detail, the US Department of Defense standard (MIL-DTL) was applied to determine whether the Toxicity index (T.I.) allowance was exceeded, and the results showed that the insulating materials emitted considerably more than the allowable limit.

A Study for Bioassay on the HBr Combustion Toxity (생물학적 분석을 통한 HBr의 연소 독성에 관한 연구)

  • Cho, Nam-Wook;Shin, Hyun-Joon;Lee, In-Ku;Oh, Eun-Ha
    • Journal of the Korean Applied Science and Technology
    • /
    • v.29 no.4
    • /
    • pp.545-551
    • /
    • 2012
  • Due to the use of polymeric materials in construction materials, the fire combustion gases that occur in the fire are various. The one of combustion gases, HBr is measured to evaluate the toxicity of the combustion gases in the FTP Code Part 2, Standard NES 713 and Standard BS 6853. According to the MSDS, Inhalation of HBr gas especially cause burn, respiratory dysfunction, headache, etc. The people who are exposed to 50ppm of HBr gas, very irritant gas may also frequently result in both immediate death and post-exposure deaths due to pulmonary complications. In this paper, we conduct a research on the combustion toxicity of HBr gas hazardous test which is motility measurement of the mice exposed to the HBr standard gas comparing the biological analysis result.