DOI QR코드

DOI QR Code

Experimental Study on the Toxicity Characteristics of Non-Class 1E Cables according to Accelerated Deterioration

가속열화에 따른 비안전등급 케이블의 독성특성에 관한 실험적 연구

  • Jang, Eun-Hui (Dept. of Safety Engineering, Incheon National Univ.) ;
  • Kim, Min-Ho (Dept. of Safety Engineering, Incheon National Univ.) ;
  • Lee, Min Chul (Dept. of Safety Engineering/Fire Disaster Prevention Research Center, Incheon National Univ.) ;
  • Lee, Sang-Kyu (Dept. of Reactor System Performance, Korea Institute of Nuclear Safety) ;
  • Moon, Young-Seob (Dept. of Reactor System Performance, Korea Institute of Nuclear Safety)
  • 장은희 (인천대학교 안전공학과) ;
  • 김민호 (인천대학교 안전공학과) ;
  • 이민철 (인천대학교 안전공학과/소방방재연구센터) ;
  • 이상규 (한국원자력안전기술연구원) ;
  • 문영섭 (한국원자력안전기술연구원)
  • Received : 2019.11.08
  • Accepted : 2019.11.27
  • Published : 2019.12.31

Abstract

This study investigates the toxicity characteristics of two Non-Class 1E Cables (For security reasons, we refer to company A and company B) used in nuclear power plants according to the accelerated deterioration period. In accordance with NES 713 test equipment and standards, tests were carried out on non-aged cables and the cables subjected to 20- and 40-year-accelerated-deterioration; each of the cables was further classified into sheath and insulation. The test results showed that the toxicity indices of 20- and 40-year-accelerated-aged cables were higher than those for the non-aged cables, and 20-year-aged cables of both A and B companies showed the highest toxicity indices. This is attributed to the extensive emissions of carbon monoxide and halide gases such as hydrogen chloride and hydrogen bromide. Furthermore, to analyze the toxicity indices of sheath and insulation in detail, the US Department of Defense standard (MIL-DTL) was applied to determine whether the Toxicity index (T.I.) allowance was exceeded, and the results showed that the insulating materials emitted considerably more than the allowable limit.

본 연구에서는 원자력발전소용 비안전등급케이블 2종(보안상 A사, B사로 지칭키로 함)을 대상으로 가속열화 기간에 따른 독성 특성을 분석하였다. NES 713 시험장비 및 규격에 의거하여 비노화, 20년, 40년으로 가속열화한 케이블에 대해 피복재 및 절연재로 구분하여 시험하였다. 시험결과 20년, 40년 가속열화 케이블의 독성지수가 비노화 케이블의 독성지수보다 높았으며 A, B사 케이블 공통적으로 20년 가속열화 케이블에서의 독성지수가 높게 산출되었다. 이는 급증한 일산화탄소의 방출량과 더불어 염화수소와 브롬화수소의 할로겐계 가스 방출량이 높은 것이 주된 원인으로 파악되었다. 또한, 피복재와 절연재를 구분하여 분석 시 A, B사 케이블 일부 피복재의 독성지수가 높게 나타났다. 또한, 피복재와 절연재의 독성지수를 구체적으로 분석하고자 미국 국방성 규격인 MIL-DTL을 적용하여 독성지수 허용치 초과 여부를 판단하였으며, 이 중 절연재의 경우 상당량 초과하여 방출되는 결과를 보였다.

Keywords

References

  1. S. K. Song, "A Study on the Combustion Characteristics According to the Aging of Communication Cables and Power Cables", Master's Thesis, Kangwon National University (2010).
  2. M. S. Ho, J. Y. Lee and D. I. Kang, "Development of Fire Ignition Frequency Calculation program Using NUREG/CR-6850 Method", Proceedings of 2010 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp. 109-112 (2012).
  3. S. K. Lee, Y. S. Moon and S. Y. Yoo, "A Study on Validation Methodology of Fire Retardant Performance for Cables in Nuclear Power Plants", Korean Society of Safety, Vol. 32, No. 1, pp. 140-144 (2017).
  4. K. Y. Kim, C. Lee, J. H. Kim and J. M. Seo, "Accelerated Aging Test of Cable Materials used in Nuclear Power Plants for the Evaluation of lifetime", KAERI/TR-2424/2003, Korea Atomic Energy Research Institute (2003).
  5. E. M. Shin, " Technology of Electrical Barrier Material", Elastomers and Composites Vol. 46, No. 1, pp. 22-28 (2011).
  6. K. Y. Kim, C. Lee, P. J. Kim, J. A. Kim and B. H. Ryu, "Evaluation on Thermal Ageing of Cable in Nuclear Power Plant", Proceedings of 2004 Spring Annual Conference, Korean Nuclear Society, pp. 1-12 (2004).
  7. Y. J. Park and H. P. Lee, "Identification on Carbon Oxide and Smoke Release Change of Aging Wire Cables", Journal of the Korean Society of Hazard Mitigation, Vol. 15, No. 4, pp. 107-113 (2015). https://doi.org/10.9798/KOSHAM.2015.15.4.107
  8. KFPA, "Fire Prevention Education Gide Book", Korea Fire Protection Association, pp. 68-74 (2014).
  9. J. H. Park and J. H. Kim, "The Measures for Operators Habitability Against Smoke Inflow to NPP's Control Room", Proceedings of 2017 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp. 117-118 (2017)
  10. H. S. Lim and D. H. Kim, "A Study on Heat-Flux Evaluation for Cable Fire Including Diagnostic Methodology for Degradation in Nuclear Power Plants", Korean Society of Safety, Vol. 26, No. 2, pp. 20-25 (2011).
  11. B. G. Kim, H. S. Lim, Y. S. Lee and M. S. Kim, "Effect of the HVAC Conditions on the Smoke Ventilation Performance and Habitability for a Main Control Room Fire in Nuclear Power Plant", Fire Science and Engineering, Vol. 30, No. 5, pp. 74-81 (2016). https://doi.org/10.7731/KIFSE.2016.30.5.074
  12. H. S. Lim, I. H. Kim and M. S. Kim, "Cable Functional Failure Time Evaluation for a Main Control Room Fire using Fire Dynamic Simulator", Fire Science and Engineering, Vol. 30, No. 3, pp. 79-85 (2016). https://doi.org/10.7731/KIFSE.2016.30.3.079
  13. H. J. Seo, N. K. Kim, J. M. Jo, M. C. Lee, S. K. Lee and Y. S. Moon, "A Study on the Human Toxicity of Combustion Products for Non-Class 1E Cables", Journal of the Korean Society of Hazard Mitigation, Vol. 18, No. 2, pp. 215-222 (2018). https://doi.org/10.9798/kosham.2018.18.2.215
  14. Ministry of Defence Defence Standard 02-713, Issue 3 Publication (2012).
  15. MIL-DTL-24640/15D, Cable, Electric, 600 Volts, Lightweight, Multi-pair, AWG 22, Type 2XSAW (Including Variation type 2XSAOW) (2002).
  16. T. Hull, A. A. Stec, K. Lebek and D. Price, "Factors Affecting the Combustion Toxicity of Polymeric Materials", Polymer Degradation and Stability, Vol. 92, No. 12, pp. 2239-2246 (2007). https://doi.org/10.1016/j.polymdegradstab.2007.03.032
  17. H. Kissinger, "Variation of Peak Temperature with Heating Rate in Differential Thermal Analysis", Journal of Research of the National Bureau of Standards, Vol. 57, No. 4, 217-221 (1956). https://doi.org/10.6028/jres.057.026
  18. C. H. Kim, S. P. An, S. M. Yeo, Y. S. Kang, S. M. An, I. S. Kim, D. S. Kim and J. S. Kang, "A Study on the Condition Monitoring for the Safety-related Electric Cables", KINS/HR-351, Korea Institute of Nuclear Safety (2001).
  19. S. R. Turns, "An introduction to Combustion : Concepts and Applications", McGraw-Hill, (2012).
  20. B. N. Raol, R. Arunjothi and A. R. Srinivasan, "Evaluation of Fire Gases from Polymeric Materials", 2012 IEEE 10th International Conference on the Properties and Applications of Dielectric Materials, pp. 24-28 (2012).
  21. Final Report of a Co-ordinated Research Project. Stability and Stabilization of Polymers Under Irradiation, IAEATECDOC-1062 (1994-1997).
  22. J. G. Calvert, J. A. Kerr, K. L. Demerjian and R. D. McQuigg, "Photolysis of Formaldehyde as a Hydrogen Atom Source in the Lower Atmosphere", Science, Vol. 175, pp. 751-752 (1972). https://doi.org/10.1126/science.175.4023.751