A Development of Web-based Safety Evaluation System of Motor-Operated-Valve in Nuclear Power Plant (웹기반 원전 동력구동밸브 안정성 평가 시스템 개발)

  • Bae, J.H.;Lee, K.N.;Kim, W.M.;Park, S.K.;Lee, D.H.;Kim, J.C.;Hong, J.S.
    • Proceedings of the KSME Conference
    • /
    • 2001.06d
    • /
    • pp.903-908
    • /
    • 2001
  • A web-based client/server program, MOVIDIK(Motor-Operated-Valve Integrated Database Information of KEPCO) has been developed to perform a design basis safety evaluation for a motor-operated-valve(MOV) in the nuclear power plant. The MOVIDIK consists of seven analysis modules and one administrative module. The analysis module calculates a differential pressure on the valve disk, thrust/torque acting at a valve stem, maximum allowable stress, thermal-overload-relay selection, voltage degradation, actuator output and margin. In addition, the administrative module manages user information, approval system and code information. MOVIDIK controls a huge amount of evaluation data and piles up the safety information of safety-related MOV. The MOVIDIK will improve the efficiency of safety evaluation work and standardize the analysis process for the MOV.

  • PDF

Categorization of Motor Operated Valve Safety Significance for Its Periodic Safety Verification (모터구동 밸브 주기적 안전성 확인을 위한 중요도 분류)

  • Sung, Tae-Young;Kim, Kil-Yoo;Kang, Dae-Il
    • Journal of the Korean Society of Safety
    • /
    • v.17 no.2
    • /
    • pp.92-99
    • /
    • 2002
  • Safety-related motor operated valve(MOV) safety significance for Ulchin Unit 3 was categorized. The safety evaluation of MOV of domestic nuclear power plants affects the generic data used for the quantification of MOV common cause failure(CCF) events in Ulchin Units 3&4 PSA. Therefore, in this paper, MGL(multiple greek letter)parameter ${\beta}$, used for the evaluation of MOV CCF probabilities in Ulchin Units 3&4 probabilistic safety assessment(PSA), was re-estimated and the MOV safety significance was categorized. The re-estimation results of MGL parameter show that the value of(is decreased by 30% compared with the current value used in Ulchin Unit 3&4 PSA. The categorization results of MOV safety significance using the changed value of MGL parameter(show that the number of HSSCs(high safety significant components) is decreased by 54.5% compared with those using the current value of it used in Ulchin Units 3&4 PSA.

Development of a Diagnostic System for Motor-Operated Valves (모터구동밸브 진단장비 개발)

  • Kang, Seong-Ki;Choi, Hyun-Woo;Park, Sung-Keun;Kang, Shin-Chul;Chai, Jang-Bom
    • Proceedings of the Korean Society for Noise and Vibration Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.420-424
    • /
    • 2008
  • The new MOV(motor-operated valve) diagnostic system MOVIDS(MOV intelligent diagnostic system) was developed. Its remote diagnostic methods with high accuracy have improved the applicability. This enables the diagnostic tests and the evaluations of many MOVs not only at the valves but also in remote places like MCCs(motor control centers). The remote diagnostic ability of the new system reduces the cost and the man power for diagnosing MOVs and eliminates the danger of the toxic or radioactive environments to which workers might be exposed.

  • PDF

Analysis of Thrust/Torque Signature of MOV (원자력 발전소 모터구동밸브의 쓰러스트/토크 신호 분석)

  • Ryu, Ho-Geun;Park, Seong-Keun;Kim, Dae-Woong
    • Proceedings of the KSME Conference
    • /
    • 2001.06e
    • /
    • pp.613-618
    • /
    • 2001
  • For the evaluation of operability of MOV(Motor Operated Valve), the precision prediction of thrust/torque acting on the valve is important. In this paper, the analytical prediction method of thrust/torque was proposed. The design basis stem thrust calculation typically considers the followings: Packing thrust, Stem rejection load, design basis differential pressure load. In general, test results show that temperature, pressure, fluid type, and differential pressure, independently and combination, all have an effect on the friction factor. The prediction results of thrust/torque are well agrement with dynamic test results.

  • PDF

Non-Invasive Diagnostic Singature Extraction for Motor-Operated Valves (모터 구동 밸브의 비침투 진단 신호 추출에 관한 연구)

  • ;Richard H. Lyon
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 1994.10a
    • /
    • pp.360-364
    • /
    • 1994
  • This paper is concerned with extracting the diagnostic signature for motor-operated valves (MOV's) noninvasively. A torque estimator is developed and tested to obtain electical torque of the induction motors which are attached to the MOV's. Inverse filter is used to recover the gear meshing forces from the measured actuator housing vibration, which contain the gear rotation information. Frequency demodulation techniques are performed and an adaptive linear bandpass filter is implemented to improve signal-to-noise ratio. Finally, stand-alone valve experiments are carried out to validate the signature extraction scheme.

  • PDF

A Study for the Improvement Method of Flexible Wedge Gate Valve Operation Capability (Flexible Wedge Gate 밸브의 운전 성능향상 방안에 관한 연구)

  • Kim, Dae-Woong;Lee, Do-Hwan;Kang, Sin-Chul;Kim, In-Whan;Park, Sung-Keun
    • Proceedings of the KSME Conference
    • /
    • 2001.06a
    • /
    • pp.644-651
    • /
    • 2001
  • The purpose of this study is to develop the improvement method of MOV(Motor Operated Valve) operability without major modification or change of MOV which needs a great expense and manpower. We studied valve stem lubrication, stem packing thrust and actuator control switch which could give an major effect to MOV operability, and found the some consequences. First, the stem/stem-nut friction coefficient and stem factor is significantly effected by stem lubrication state. Second, the measured packing thrust value is appeared higer than the design value for tested valves and the preparation of optimal value selection criteria is needed. Finally, optimization of MOV control switch is another major factor for MOV operability and structual integrity.

  • PDF

Study on the Condition and Performance Monitoring Technology of Motor-Operated Valve (모터구동밸브의 고장 및 성능감시 기술에 대한 연구)

  • Kwon, Seok-Jun;Sung, Key-Yong;Lee, Heung-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2003.07d
    • /
    • pp.2778-2780
    • /
    • 2003
  • 본 논문에서는 모터구동밸브의 모터 토크를 전기적인 신호만으로 예측하고, 계산된 모터 토크신호를 주파수영역에서 분석하여 Motor Speed, Slip pole 주파수, WGTM(Worm Gear Tooth Mesh)과 같은 MOV의 기계적 특성 성분을 확인하였다. 또한 모의 고장 실험을 통해 MOV 기계적 고장이 이 특성성분의 변화로 나타나는 것을 확인하므로, 이 정보를 MOV의 고장 감시 기술로 적용할 수 있다. 아울러 전기 신호를 이용하여 Condition Monitoring 기법을 개발하고, MOV 고장 감시 Software를 개발하므로, MOV 주기적 확인에 대비한 규제검증 기술 및 정보를 제공하고자 한다.

  • PDF

MOTOR CONTROL CENTER (MCC) BASED TECHNOLOGY STUDY FOR SAFETY-RELATED MOTOR OPERATED VALVES

  • Kang, Shin-Cheul;Park, Sung-Keun;Lee, Do-Hwan;Kim, Yang-Seok
    • Nuclear Engineering and Technology
    • /
    • v.38 no.2
    • /
    • pp.155-162
    • /
    • 2006
  • It is necessary to monitor periodically the operability of safety-related motor-operated valves (MOVs) in nuclear power plants. However, acquiring diagnostic signals for MOVs is very difficult, and doing so requires an excessive amount of time, effort, and expenditure. This paper introduces an accurate and economical method to evaluate the performance of MOVs remotely. The technique to be utilized includes electrical measurements and signal processing to estimate the motor torque and the stem thrust, which have been cited as the two most effective parameters in diagnosing MOVs by the US Nuclear Regulatory Commission. The motor torque is calculated by using electrical signals, which can be measured in the motor control center (MCC). Some advantages of using the motor torque signature over other signatures are examined. The stem thrust is calculated considering the characteristics of the MOV and the estimated motor torque. The basic principle of estimating stem thrust is explained. The developed method is implemented in diagnostic equipment, namely, the Motor Operated Valve Intelligent Diagnostic System (MOVIDS), which is used to obtain the accuracy of and to validate the applicability of the developed method in nuclear power plants. Finally, the accuracy of the developed method is presented and some examples applied to field data are discussed.