• Title/Summary/Keyword: Limiting load

Search Result 172, Processing Time 0.024 seconds

The Computer Simulation on the Characteristics of the Non-Inductive Superconducting Fault Current Limiter (무유도성 초전도전류제한기의 특성 해석 및 컴퓨터 시뮬레이션)

  • 주민석;이상진;오윤상;고태국
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.43 no.7
    • /
    • pp.1050-1060
    • /
    • 1994
  • This paper is a study on the computer simulation of the characteristics of the superconducting fault current limiter. Input variable parameters are apparent power, load resistance value, line resistance value and so on. Initial fault current 2 times larger than the trigger current is required to reduce the switching time of SFCL. The propagation velocity increases abruptly, the transport current is several times larger than the ciritical current. In this paper, the switching time is calculated to be 323$\mu$ sec, and the initial fault current is 19 times larger than the critical current. Because the trigger coils are bifilar winding, they have little impedance in superconducting state. After fault occurred, the limiting coil acts as a superconducting reactor and the trigger coils quench at a critical current. Without the SFCL in the circuit, fault current after the load impedence is shorted might be increased to 1100A. The fault current is, therefore, successfully limited by the superconducting limiting coil to 100A determined by the coil inductance.

  • PDF

ESTIMATION OF REQUIRED CAPACITY OF SHUNT TYPE ACTIVE POWER FILTER WITH A THYRISTOR CONVERTER LOAD

  • Jeong, Seung-Gi;Kim, Dong-Ha
    • Proceedings of the KIPE Conference
    • /
    • 1998.10a
    • /
    • pp.802-807
    • /
    • 1998
  • The main drawback of parallel type active power filters (APF) is the large capacity required for harmonic compensation. This paper evaluates the APF capacity requirement of harmonic/reactive power compensation for thyristor converter load. Theoretically achievable maximum power factor under partial load is evaluated. And it is shown that the APF capacity can be considerably reduced while slightly sacrificing the filtering performance by deliberately limiting the peak current of the APF.

  • PDF

Design of Direct Load Controller for use of Demand Side (수용가용 직접부하제어장치 설계)

  • Park, J.C.;Kim, H.G.;Jeong, B.H.;Kang, B.H.;Choe, G.H.
    • Proceedings of the KIPE Conference
    • /
    • 2005.07a
    • /
    • pp.149-151
    • /
    • 2005
  • Recently, power supply-demand instability due to the dramatic increase in power usage suchas air-conditioning load at summertime has brought forecasts of decrease in power supply capability. Therefore improving the load factor through systematic load management, in other words, Direct Load Control became necessary. Direct Load Control(DLC) system is kind of a load management program for stabilization of electric power supply-demand. It's purpose is limiting the demand of the demand side selected at peak load or other time periods. The paper presented a Design of Direct Load Controller for control the amount of power demand in demand side. The proposed Controller is cheaper and has ability of storing more power data than pre-existing device.

  • PDF

A Study on the Development of Force Limiting Devices of Cross-Section Cutting Types (단면절삭형 응력제한 장치의 개발에 관한 연구)

  • Kim, Cheol Hwan;Chae, Won Tak
    • Journal of Korean Society of Steel Construction
    • /
    • v.27 no.1
    • /
    • pp.77-85
    • /
    • 2015
  • This paper describes the development of force limiting device(FLD). The FLD could induce compressive yield before occurring elastic buckling for slender member under compressive load. Therefore, it might prevent reduction of load carrying capacity by elastic buckling and the structures with the devices would behave stable. A new type of FLD reduced cross area is proposed in this study different to existing studies like as out of plane type, slit type and folded plate type. The parameters of specimens are depth, width and number of cutting. The structural capacity and characteristics of proposed types were verified by experiment and FEM analysis. The FLD of cutting type is efficient in compressive member.

Operational Characteristics of a Flux-Lock Type SFCL Integrated with Voltage-Controlled Voltage Source Inverter

  • Lee, Su-Won;Lim, Sung-Hun;Ko, Sung-Hun;Lee, Seong-Ryong
    • Journal of Electrical Engineering and Technology
    • /
    • v.3 no.4
    • /
    • pp.546-551
    • /
    • 2008
  • In this paper, a flux-lock type superconducting fault current limiter(SFCL) integrated with a voltage-controlled voltage source inverter(VC-VSI) is proposed. The suggested equipment, which consists of a flux-lock type SFCL and a VCVSI, can perform the fault current limiting operation from the occurrence of a short-circuit. In addition, it can compensate the reactive power that the non-linear load requires and also perform the uninterruptible power supply(UPS) as well as the load voltage stabilization by controlling the amplitude and the phase of the inverter's output voltage. The specification for a test model was determined and its various functions such as the fault current limiting and the power conditioning operations were presented and analyzed via computer simulation. Through the analytical results based on the computer simulation, the validity of the analysis was confirmed and its multi-operation was discussed.

Plastic Limit Loads of 90° Elbows with Local Wall-Thinning Using Small Strain FE Limit Analyses (II)- Bending Moment - (소변형 이론에 입각한 감육이 존재하는 90 도 곡관의 소성 한계 하중 (II)- 굽힘 -)

  • Kim, Jong-Hyun;An, Joong-Hyok;Hong, Seok-Pyo;Park, Chi-Yong;Kim, Yun-Jae
    • Transactions of the Korean Society of Mechanical Engineers A
    • /
    • v.31 no.4
    • /
    • pp.496-505
    • /
    • 2007
  • This paper proposes closed-form plastic limit load solutions for elbows under in-plane bending, via three-dimensional (3-D), small strain FE limit analyses using elastic-perfectly plastic materials. A wide range of elbow and thinning geometries are considered. For systematic analyses of the effect of the axial thinning length on limit loads, two limiting cases are considered; a sufficiently long wall thinning, and the circumferential part-through surface crack. Closed-form plastic limit load solutions for wall thinning with intermediate longitudinal extents are then obtained from these two limiting cases. The effect of the axial extent of wall thinning on plastic limit loads for elbows is highlighted by comparing that for straight pipes. Although the proposed solutions are developed for the case when wall thinning exists in the center of elbows, it is also shown that they can be applied to the case when wall thinning exists anywhere within the elbow.

Comparative study on the behavior of lime-soil columns and other types of stone columns

  • Malekpoor, Mohammadreza;Poorebrahim, Gholamreza
    • Geomechanics and Engineering
    • /
    • v.7 no.2
    • /
    • pp.133-148
    • /
    • 2014
  • An experimental study is carried out to evaluate the performance of Lime mortar-Well graded Soil (Lime-WS) columns for the improvement of soft soils. Tests are conducted on a column of 100 mm diameter and 600 mm length surrounded by soft soil in different area ratios. Experiments are performed either with the entire area loading to evaluate the load - settlement behavior of treated grounds and only a column area loading to find the limiting axial stress of the column. A series of tests are carried out in soaking condition to investigate the influence of moisture content on the load - settlement behavior of specimens. In order to compare the behavior of Lime-WS columns with Conventional Stone (CS) columns as well as Geogrid Encased Stone (GES) columns, the behavior of these columns have been also considered in the present study. Remarkable improvement in the behavior of soft soil is observed due to the installation of Lime-WS columns and the performance of these columns is significantly enhanced by increasing the area ratio. The results show that CS columns are not suitable as a soil improvement technique for extremely soft soils and should be enhanced by encasing the column or replaced by rigid stone columns.

Composition and Operation of Direct Load Control(DLC) System for use of Demand Side (수용가용 직접부하제어시스템의 구성 및 운영)

  • Park J.C.;Choi M.G.;Lee Y.G.;Kim S.J.;Jeong B.H.;Choe G.H.
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.1260-1262
    • /
    • 2004
  • Direct Load Control(DLC) system is a load management program for stablization of electric power supply-demand. It is a series of acts limiting the demand of selected demand side at peak load or other time periods. Recently, power supply-demand instability due to dramatic increase in power usage such as summertime air-conditioning load has brought forecasts of decrease in power supply capability. Therefore heightening the load factor through systematic load management, in other words, Direct Load Control became necessary. By examining the composition and operation of the DLC system, this paper provides conceptional understanding of the DLC system and help in system research.

  • PDF

PWM Controller of Power Factor Correction Circuit to Improve Efficiency for Wide Load Range (넓은 부하범위에서 고효율 특성을 갖는 역율개선회로의 PWM 제어기)

  • Son, Min-soo;Kim, Hong-jung;Park, Gwi-chul;Choi, Jaeho
    • Proceedings of the KIPE Conference
    • /
    • 2016.07a
    • /
    • pp.75-76
    • /
    • 2016
  • This paper proposes a power factor correction circuit with a high efficiency over a wide load range characteristics for a communication power supply. And the characteristic verification is applied to produce a design of prototype. Power factor correction circuit can reduce conduction losses by applying Bridgeless Boost Converter for efficiency. Over a wide load range to maintain the efficient, the control method of a PWM controller is divided by two sections according to the load area. In the low-load region, it was reduced switching losses by applying the critical conduction mode control method. On the other hand, in the heavy-load area, the hysteresis current control method is used to maintain the high efficiency over a wide load range by limiting the peak noise of the inductor.

  • PDF

Current Limiting and Voltage Sag Compensation Characteristics of Flux-Lock Type SFCL Using a Transformer Winding (변압기 권선을 이용한 자속구속형 초전도 전류제한기의 전류제한 및 전압강하 보상 특성)

  • Ko, Seok-Cheol
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.25 no.12
    • /
    • pp.1000-1003
    • /
    • 2012
  • The superconducting fault current limiter (SFCL) can quickly limit the fault current shortly after the short circuit occurs and recover the superconducting state after the fault removes and plays a role in compensating the voltage sag of the sound feeder adjacent to the fault feeder as well as the fault current limiting operation of the fault feeder. Especially, the flux-lock type SFCL with an isolated transformer, which consists of two parallel connected coils on an iron core and the isolated transformer connected in series with one of two coils, has different voltage sag compensating and current limiting characteristics due to the winding direction and the inductance ratio of two coils. The current limiting and the voltage sag compensating characteristics of a SFCL using a transformer winding were analyzed. Through the analysis on the short-circuit tests results considering the winding direction of two coils, the SFCL designed with the additive polarity winding has shown the higher limited fault current than the SFCL designed with the subtractive polarity winding. It could be confirmed that the higher fault current limitation of the SFCL could be contributed to the higher load voltage sag compensation.