• Title/Summary/Keyword: Korea Fire Safety Institute

검색결과 1,261건 처리시간 0.03초

Fire Safety Labeling System for Household Goods to Prevent House Fires

  • Kyong-Jin Park;Bong-Kil Kim;Hyun-Mi Kim
    • 한국산업융합학회 논문집
    • /
    • 제27권4_1호
    • /
    • pp.735-740
    • /
    • 2024
  • Data released by the National Fire Agency showed that the total incidence of fires from 2014 to 2023 was 410,497, among which 75,215 were house fires, constituting 18% of the total occurrences. The fatalities resulting from house fires numbered 1,435. Fatalities stemming from prior house fires occurred between midnight and 6 am, coinciding with periods of sleep and diminished responsiveness to fire emergencies. A fire safety labeling system is proposed to prevent fire hazards associated with household products. This system primarily entails indicators of thermal energy and inherent fire attributed to household products. Furthermore, the Korea Fire Safety Institute has suggested adopting a risk label as a concrete measure plan for implementing the fire safety labeling system for household products. The results promise to safeguard the public against fires and increase the exports of household commodities by enhancing the corporate reputation through positive association with fire safety measures.

CFAST 모델을 이용한 이중격실화재 모사 (Simulation of Pool Fire with Two Rooms Using CFAST Model)

  • 류수현;금오현;김위경;김윤일;배용범;박종석
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 추계학술논문발표회 논문집
    • /
    • pp.444-449
    • /
    • 2008
  • Fire model shall be verified and validated to reliably predict the consequences of fires within its limitations. This study aims to predict pool fire phenomena with two rooms using CFAST and to compare CFAST simulation results with PRISME experimental data which can be applicable to the fire of nuclear power plant facility. Five different mass loss rate(MLR) are used in the simulation and the simulated results of specific quantities such as temperature, chemical composition are compared to the experimental data. From this study, the CFAST simulation results with the proper MLR show better similarity and trend with pool fire experimental data.

  • PDF

Simulation and Damage Analysis of an Accidental Jet Fire in a High-Pressure Compressed Pump Shelter

  • Jang, Chang Bong;Choi, Sang-Won
    • Safety and Health at Work
    • /
    • 제8권1호
    • /
    • pp.42-48
    • /
    • 2017
  • Background: As one of the most frequently occurring accidents in a chemical plant, a fire accident may occur at any place where transfer or handling of combustible materials is routinely performed. Methods: In particular, a jet fire incident in a chemical plant operated under high pressure may bring severe damage. To review this event numerically, Computational Fluid Dynamics methodology was used to simulate a jet fire at a pipe of a compressor under high pressure. Results: For jet fire simulation, the Kemeleon FireEx Code was used, and results of this simulation showed that a structure and installations located within the shelter of a compressor received serious damage. Conclusion: The results confirmed that a jet fire may create a domino effect that could cause an accident aside from the secondary chemical accident.

외부화염에 의해 단락된 비닐코드 및 고무코드의 화재 패턴 (The fire patterns of vinyl and rubber cords shorted by external flame)

  • 김동우;송길목;김동욱;김영석;최충석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 C
    • /
    • pp.1655-1657
    • /
    • 2004
  • The electrical fire frequently happens through carelessness of a vinyl and rubber cords such as a poor contact, a mechanical stress and so on. Electrical fire occupies the greater part(about 30%) of all fires in Korea. In this paper, we compared to the fire dispersive patterns of vinyl and rubber cords according to the external flame in the wall-model. The fire progress and dispersive patterns were measured by a high speed imaging system(HG-100K, REDLAKE, USA). From the results, short-circuit of the vinyl cords are easy to happen than the rubber cords by the external flame. The pattern of fire was progressed a flashover, scattering and disconnection. The fire progress on the vinyl cord is not observed because the ignition energy decreases. However, the fire was progressed continuously on the rubber cord.

  • PDF

일반용 전기설비 안전점검의 전기화재 예방효과에 대한 정량적 분석 (Quantitative Analysis on the Electrical Fire Preventive Effect of Safety Inspection for Electrical Facilities for General Use)

  • 김택희;유재근;전정채
    • 전기학회논문지P
    • /
    • 제64권2호
    • /
    • pp.45-49
    • /
    • 2015
  • This paper presents a quantitative analysis method to quantitatively indicate a electrical fire preventive effect of safety inspection for electrical facilities for general use. Logic model was developed based on whether enforcement of safety inspection for electrical facilities, and then the developed analysis model was converted to hydraulic model by using mathematical logic. The electrical fire preventive effect of safety inspection for electrical facilities was quantitatively calculated by applying electrical safety inspection results and fire statistics for five years to the developed hydraulic model. The results show that electrical fire preventive effects of 5,542 cases on annual average for five years.

화재분석모델을 이용한 이중격실화재 검증분석 (Simulation of Pool Fire with Two Rooms Using FDS Model)

  • 김봉현;배용범;류수현;이공희;김윤일;문찬기;박종석
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.1332-1337
    • /
    • 2008
  • Fire model shall be verified and validated to reliably predict the consequences of fires within its limitations. This study aims to predict pool fire with two rooms using FDS and to coompare FDS simulation results with PRISME experimental data which can be applicable to the fire of nuclear power plant facility. Four different sizes of grid (0.08m, 0.1m, 0.125m, 0.2m) are used in the simulation and the simulated results of specific quantities such as temperature, chemical composition, heat flux and heat release rate are compared to the experimental data. From this study, the FDS simulation results with the finer grid resolution show better similarity and trend with pool fire experimental data. The sensitivity analysis and the selection of the proper size grid are essential to predict the consequences of pool fire with two rooms reliably.

  • PDF

환기가 제한된 두 개 격실 화재에서 FDS 검증분석 (Validation of FDS for Fire in Underventilated Condition with Two rooms)

  • 배용범;금오현;김윤일;류수현;김위경;박종석
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 추계학술논문발표회 논문집
    • /
    • pp.438-443
    • /
    • 2008
  • Fire model shall be verified and validated to reliably show the predictive capabilities for a specific use. In the process of model verification and validation, both the acceptable uses and limitation of fire model are established. In this study, the results of FDS simulation are compared with the data of PRISME experiment such as temperature, heat release rate, heat flux, product concentrations in the under-ventilated two-room condition. Furthermore, the sensitivity of FDS under ventilation condition changes are evaluated. FDS provide the reliable prediction for under-ventilated two-room fire scenario with slightly deviation.

  • PDF

디지털 방식 무선 화재알림설비의 신호 패턴 인식기법 적용 (Application of Signal Pattern Recognition Technique of Digital Wireless Fire Alarm System)

  • 박승환;김두현;김성철
    • 한국안전학회지
    • /
    • 제37권5호
    • /
    • pp.14-21
    • /
    • 2022
  • The purpose of this study was to apply the signal pattern recognition technique to the digital wireless fire-alarm system and to reduce unwanted fire alarms. In this study, the fire alarms of the K Institute, which operates the largest digital wireless fire-alarm system in Korea, were classified into normal operations and unwanted fire alarms, and these were analyzed and compared with actual fire signals. In addition, by designing a non-fire signal filter and applying it to the K Institute, we confirmed that the monthly unwanted fire alarm rate of all 5,713 detectors decreased sharply. In particular, the unwanted fire alarm rate for flame decreased from 1.09% to 0.11% and the unwanted fire alarm rate for smoke decreased from 0.65% to 0.035%.

도로터널 화재안전기준 기반 항만 지역 도로터널 화재 안전성 분석 (Evaluation of Fire Safety for Road Tunnels in Port Area based on Fire Safety Guidelines)

  • 하예진;전준호
    • 융복합기술연구소 논문집
    • /
    • 제11권1호
    • /
    • pp.25-28
    • /
    • 2021
  • Recently, the fire safety of road tunnels has been important issues in South Korea. However, proper fire safety regulations has not made for road tunnels. Due to geographical challenges in South Korea, road tunnels should be constructed to secure stable traffic flows. In the Guidelines for Installing and Managing Disaster Prevention Facilities of Road Tunnels (NFSC 603), main target vehicles are passenger cars. This guidelines cannot support big fires from larger vehicles such as cargo, oil trucks. In this study, fire safety for a road tunnel in port area was analyzed with fire dynamics theory under cargo truck fire scenario. Sujunsan road tunnel in Busan city was chosen as a target tunnel, which links between Busan port and highways to increase cargo shipping. The results show the limitations of present guidelines (NFSC 603) for road tunnel from large fire situations.

환기가 제한된 세 개 격실에서 Pool Fire에 대한 FDS 검증분석 (Validation of FDS for Pool Fire in Three Rooms Connected to Ventilation Network)

  • 배용범;이상규;신병수;김남석;금오현;박종석
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2011년도 춘계학술논문발표회 논문집
    • /
    • pp.9-15
    • /
    • 2011
  • This study aims to validate predictive capabilities of FDS for the pool fire in three rooms connected to ventilation network. The three rooms in real scale fire test facility are configured to be similar to that of nuclear power plant in size, ventilation condition, construction material, etc. Basically three rooms are confined to the other area except two open doors and two ventilation duct in each room. The real scale fire test was conducted with these conditions and the predictive capabilities of FDS will be validated by comparing FDS simulation results with experimental data from the temperature, heat flux, and concentration point of view. This study concludes that temperature from FDS is about 25 % lower deviation from the experiment, and heat flux from FDS is about 5% deviation.

  • PDF