• 제목/요약/키워드: Islanding Protection

검색결과 33건 처리시간 0.03초

AFD 기법의 출력전력 분석 (Output Power Analysis for Active Frequency Drift Method)

  • 이기옥;최주엽;최익;유권종
    • 한국태양에너지학회:학술대회논문집
    • /
    • 한국태양에너지학회 2009년도 추계학술발표대회 논문집
    • /
    • pp.297-302
    • /
    • 2009
  • As the grid-connected photovoltaic power conditioning systems (PVPCS) are installed in many residential areas, these have raised potential problems of network protection on electrical power system. One of the numerous problems is an Islanding phenomenon. In this paper, active frequency drift (AFD) method, one of the anti-islanding analyzed by current magnitude compensation and calculation of RMS value of the output power.

  • PDF

Islanding Detection for Distributed Generation

  • Ding, X.;Crossley, P.A.;Morrow, D.J.
    • Journal of Electrical Engineering and Technology
    • /
    • 제2권1호
    • /
    • pp.19-28
    • /
    • 2007
  • The paper discussed various techniques for islanding detection and described in detail the working principles of ROCOF and vector shift relays. A simulator was used to investigate why the stability of both types of relays maybe affected by network and load switching, short-circuit faults and in the case of a ROCOF relay the loss of bulk generation or the tripping of a transmission feeder. Finally, to enhance the reliability of Loss of Mains protection, a new islanding detection technique based on a GPS synchronized phasor measurement system was proposed.

분산전원의 고립운전 검출 알고리즘 적용에 관한 연굴 (A Study on Application of Islanding Detection Algorithm for Dispersed Generation Unit.)

  • 정원욱;정일엽;문승일
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.217-219
    • /
    • 2004
  • The installation of small sized dispersed generation(DG) units operating in parallel with the utility supply presents several technical problems for the protection and control of the system. One of the critical concerns is the occurrence of islanding. Hence, this paper propose the Digital Universal Relay(DUR) including anti-islanding function as DG interconnection interface. The existent islanding detection algorithms are examined. And the most effective and reliable method of those is modified for DUR application. The modified algorithm is evaluated through the modeling of the test system by PSCAD/EMTDC.

  • PDF

분산전원시스템의 계통연계를 위한 새로운 단독운전 방지기법 (A New Anti-Islanding Method for Utility Interconnection of Distributed Power Generation System)

  • 황인호
    • 전력전자학회논문지
    • /
    • 제9권6호
    • /
    • pp.568-576
    • /
    • 2004
  • 본 논문은 신$.$재생에너지를 이용한 분산전원시스템을 위한 새로운 단독운전 방지기법을 제시한다. 유효전력과 무효전력 불균형의 개념에 근거해서 3가지 다른 단독운전 조건이 분석된다. 단독운전 전압이 유효전력의 함수이고 그 주파수는 유효전력과 무효전력의 함수임이 분석을 통해 보여준다. 이 분석결과를 이용해서 새로운 단독운전 방지기법이 개발되었다. 제안된 보호 알고리즘은 분산전원에 의해 공급되는 무효전력을 계속적으로 $\pm$5% 변화시키면서 동시에 계통전압과 주파수를 관측한다. 만일 단독운전에 의해 측정할 정도의 주파수 이탈이 발생하면 더 나아가 분산전원의 유효전력을 80%로 감소시킨다. 이 검출기법은 공진부하에서도 빠르게 동작됨을 보여준다. 가능한 단독 운전조건이 모의되고 분석 증명된다. 0.5 kW 연계형 연료전지 시스템의 실험결과가 제시된다.

시간영역에서의 유효/무효전력을 이용한 마이크로그리드의 단독운전의 판단 알고리즘 (Islanding detection algorithm for a micro-grid based on the active and reactive power in the time domain)

  • 이영귀;이혜원;김연희;정태영;강용철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.145-146
    • /
    • 2011
  • A micro-grid (MG) is usually interconnected to the main grid through the dedicated line. Immediately after the removal of the grid supply, the MG should be disconnected and remain disconnected until the main grid is re-energized. It should detect islanding condition as soon as it happens to adjust the setting of the protection relays in the MG. This paper proposes an islanding detection algorithm for the MG based on the active and reactive power delivered to the dedicated line in the time domain. The performance of the proposed algorithm is verified under islanding conditions and fault conditions using the PSCAD/EMTDC simulator. The results indicate that the proposed algorithm can discriminate the islanding conditions from the various fault conditions.

  • PDF

액티브 필터기능을 갖는 3상 태양광 발전시스템의 단독운전 방지기능의 분석 (Analysis results of the Anti-islanding Function for PV-AF System)

  • 김경훈;서효룡;장성재;박상수;박민원;유인근;전진홍;김슬기;조창희;안종보
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.1085-1086
    • /
    • 2008
  • Shunt active filter can compensate harmonic current of utility results from non-linear loads such as rectifiers, cycloconverters and arc furnaces. It has the same structure as photovoltaic(PV) generation system. So, It was proposed the system that generates PV power and also has active filter function. It is called PV-AF(Photovoltaic and Active Filter) power generation system. Islanding can be occurred in an inverter based dispersed generation system, when the system disconnected from utility and loads are entirely supplied by PV system only. Islanding may result in interference to grid protection devices, equipment damage, and even personnel safety hazards. Therefore, islanding has to be detected and protected. The conventional anti-islanding methods have NDZ(None-Detection Zone) or power quality degradation. But PV-AF power generation system has the function of not only shunt active filter but also anti-islanding method without NDZ. In this paper, a novel anti-islanding method for PV-AF system is proposed and analysed in detail.

  • PDF

단상 계통연계형 PCS의 단독운전 검출기법 비교 분석 (Analysis of Active Islanding Dectetion Methods for a Single-phase Photovoltaic Power Conditioning Systems)

  • 정영석;소정훈;유권종;강기환;최재호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 B
    • /
    • pp.1477-1479
    • /
    • 2004
  • Increasing numbers of photovoltaic arrays are being connected to the power utility through the power conditioning systems (PCS). This has raised potential problems of network protection. If, due to the action of the PCS, the local network voltage and frequency remain within regulatory limits when the utility is disconnected, then islanding is said to occur. In this paper, the representative methods to prevent the islanding are described and a PSIM-based model and analysis of the reactive power variation (RPV) method are presented. A novel phase detector using the all-pass filter and digital phase locked loop (DPLL) is proposed especially for the single-phase PCS. Finally, this paper provides the simulation and experimental results with a single-phase 3kW prototype PCS. Islanding test method of IEEE Std. 929-2000 was performed for verification.

  • PDF

분산 전원의 고립 운전 검출 기법 개발 (Development of a Loss of Mains Detection Method for Distributed Resources)

  • 장성일;김광호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 춘계학술대회 논문집 전력기술부문
    • /
    • pp.42-45
    • /
    • 2001
  • The islanding protection for distributed resources (DR) becomes an important and emerging issue in power system protection since the distributed generator installations are rapidly increasing and most of the installed systems are interconnected with distribution network. In order to avoid the negative impacts on distributed network resulting from islanding operations of DR, it is necessary to detect the loss of mains (LOM) effectively. This paper presents a new LOM detection method using the rate of change in total harmonic distortion (THD) of current. The proposed method effectively detects LOM of the DR unit operating in parallel with the distribution network. We also verified the efficiency of the proposed method using the radial distribution network of IEEE 34 bus model.

  • PDF

태양광 발전과 ESS 시스템의 연계운전시 단독운전 방지 사례 연구 (A Case Study on the Islanding Detection Protection of PV System and ESS System)

  • 임종록;황혜미;신우균;주영철;정영석;강기환;고석환
    • 한국태양에너지학회 논문집
    • /
    • 제39권1호
    • /
    • pp.59-66
    • /
    • 2019
  • BIPV or BAPV installation applied to building is increasing through public utility mandates enterprise. Solar PV energy generates only during the day, but if it is operated in convergence with ESS, which stores electrical energy, it can restrain the fossil energy used in buildings throughout the day. A solution is to converge with PV system and ESS. However, PV systems and ESS connected to the power grid in parallel can cause problems of electrical stability. A study was conducted on the case of failure to detect islanding operation under the parallel operation of PV generation and ESS that are connected in parallel to power grid. Experiments conducted various non-islanding detections under the operating conditions. In the experiment results, when one PCS - PV inverter or ESS inverter - was operating under the islanding condition, it stopped working within 0.5 seconds of the Korean grid standard. However, when both of PV inverter and ESS inverter were operating at the same time under the islanding situation, the anti-islanding algorithm did not operate normally and both inverters continuously supplied power to the connected RLC loads. islanding detection Algorithm developed by each inverter manufacturer has caused this phenomenon. Therefore, this paper presented a new test standard for islanding detection.

Analysis of IEC 61727 Photovoltaic (PV) systems Characteristics of the utility interface

  • Lee, Jeong Hyeon;Yoon, Yong Ho;Kim, Jae Moon
    • International Journal of Internet, Broadcasting and Communication
    • /
    • 제7권2호
    • /
    • pp.90-95
    • /
    • 2015
  • This paper describes IEC 61727 standard of Photovoltaic (PV) systems -Characteristics of the utility interface. IEC 61727 standard tests include utility compatibility and personnel safety and equipment protection of PV inverter performance functions. Especially utility compatibility part includes test items of 1) voltage, current and frequency, 2) normal voltage operating range, 3) flicker, 4) DC injection, 5) normal frequency operating range, 6) harmonics and 7) waveform distortion, 8) power factor of PV inverter. Also personnel safety and equipment protection part includes test items 1)loss of utility voltage, 2)over/under voltage and frequency, 3)Islanding protection, 4)response to utility recovery, 5)earthing, 6)short circuit protection, 7)Isolation and switching of PV inverter. In this paper, each item of IEC 61727 standard test is studied and analyzed and finally full tested by PV inverter performance function.