Abstract
This paper presents a new anti-islanding method for distributed power generation system (DPGS) using renewable energy. Based on the concept of real and reactive power mismatch, three different islanding conditions are analyzed. It is shown via analysis that islanding voltage is a function of real power alone, where as its frequency is a function of both real and reactive power. Using this analysis, a new anti-islanding method is developed. The proposed protection algorithm continuously perturbs ($\pm$5%) the reactive power supplied by DPGS while simultaneously monitoring the utility voltage and frequency. If a measurable frequency deviation took place by islanding, the real power of DPGS is further reduced to 80%. This detection method is shown to be fast acting under resonant loads. Possible islanding conditions are simulated and verified with analysis. Experimental results on a 0.5kW utility-interactive fuel cell system are suggested.
본 논문은 신$.$재생에너지를 이용한 분산전원시스템을 위한 새로운 단독운전 방지기법을 제시한다. 유효전력과 무효전력 불균형의 개념에 근거해서 3가지 다른 단독운전 조건이 분석된다. 단독운전 전압이 유효전력의 함수이고 그 주파수는 유효전력과 무효전력의 함수임이 분석을 통해 보여준다. 이 분석결과를 이용해서 새로운 단독운전 방지기법이 개발되었다. 제안된 보호 알고리즘은 분산전원에 의해 공급되는 무효전력을 계속적으로 $\pm$5% 변화시키면서 동시에 계통전압과 주파수를 관측한다. 만일 단독운전에 의해 측정할 정도의 주파수 이탈이 발생하면 더 나아가 분산전원의 유효전력을 80%로 감소시킨다. 이 검출기법은 공진부하에서도 빠르게 동작됨을 보여준다. 가능한 단독 운전조건이 모의되고 분석 증명된다. 0.5 kW 연계형 연료전지 시스템의 실험결과가 제시된다.