A Study on the Condition Diagnosis for the Stator Coil of Traction Motor by Transient Surge (과도서지에 의한 견인전동기 고정자 코일의 상태진단 연구)

  • 박현준;장동욱;김길동;최종선;김정수
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.8 no.3
    • /
    • pp.247-252
    • /
    • 2003
  • Aging and failure of motor insulation depend on the stresses imposed on it. The insulation life time depends on the severity of the stresses. The electrical aging by transient surge is very important to traction motor in EMU(electric multiple unit). This paper presents the insulation characteristics of stator coil by transient surge from inverter. There are several nondestructive tests available for checking the condition of motor insulation, the probable extent of aging, and the rate of which aging is taking place. So the insulation characteristics of stator coil were each analyzed by measurement of leakage current, dielectric loss(tan $\delta$), capacitance, polarization index(PI) and partial discharge. The method of diagnosis is able to analyze the aging condition and predict the life of the traction motor in EMU.

Experimental Investigation of Composite Insulator for Insulation Design of HTS Cable (고온 초전도 케이블의 절연설계를 위한 복합절연물의 시험 연구)

  • Nguyen, Van Dung;Baek, Seung-Myeong;Cheon, Hyeon-Gweon;Kwag, Dong-Sun;Kim, Sang-Hyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.331-336
    • /
    • 2004
  • Due to the outstanding insulating characteristics, Laminated Polypropylene paper (LPP) and Kraft paper have been used as ac power insulation for conventional cable. Recently, both of LPP and Kraft has been studied as main insulation fur high temperature superconducting (HTS) cable. Ifowever, studies on the use of LPP/Kraft paper for HTS cables are thinly scattered. In this paper, the comparison among LPP, Kraft and LPP/Kraft Samples impregnated with liquid nitrogen $(LN_2)$ on dielectric insulation characteristics was investigated. It was found from the experimental data that the breakdown strength becomes lower in the order LPP, Lpp/Kraft and Kraft but the lifetime indices n becomes lower in the order Kraft, LPP/Kraft, LPP. Moreover, partial discharge inception and dielectric loss tangent become lower in the order Kraft, LPP, LPP/Kraft.

  • PDF

Insulation Breakdown Characteristics of Inverter Surge Resistant Enameled Wire Prepared with Organic/Inorganic Hybrid Nanocomposite

  • Park, Jae-Jun;Shin, Seong-Sik;Lee, Jae-Young;Han, Se-Won;Kang, Dong-Pil
    • Transactions on Electrical and Electronic Materials
    • /
    • v.16 no.4
    • /
    • pp.190-193
    • /
    • 2015
  • Insulation breakdown characteristics of an inverter surge resistant enameled wire were investigated in a twisted pair prepared with organic/inorganic hybrid nanocomposite. Organic polymer was polyesterimide-polyamideimide (EI/AI) and inorganic material was a nano-sized silica. The enamel thickness was 50 μm and the diameters of enameled copper wires were 0.75, 1.024, and 1.09 mm, respectively. There were many air gaps in a twisted pair. Therefore, when the voltage was applied to the twisted pair, enamel erosion took place in the air gap area because of partial discharge according to Paschen’s law. The insulation lifetime of the hybrid wire (HW) was 41,750 sec, which was 515.4 times more than the 81 sec of EI/AIW. In addition, the shape parameter of HW was 2.58, which was 3.4 times higher than 0.75 of EI/AIW.

Assessment of Insulation Deterioration in Stator Windings of High Voltage Motor (고압전동기 고정자 권선의 절연열화 평가)

  • Kim, Hee-Dong;Kong, Tae-Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.5
    • /
    • pp.711-716
    • /
    • 2012
  • To assess the insulation deterioration of stator windings, diagnostic and AC breakdown tests were performed on the eleven high voltage (HV) motors rated at 6kV. After completing the diagnostic tests, the AC overvoltage test was performed by gradually increasing the voltage applied to the stator windings until electrical insulation failure occurred, to obtain the breakdown voltage. Stator winding of motors 1, 3, and 8 failed at above rated voltage at 14 kV, 13.8kV, and 16.4kV, respectively. The breakdown voltage of three motors was higher than expected for good quality windings in 6kV motors. Based on deterioration evaluation criteria, the stator winding insulation of eleven HV motors are confirmed to be in good condition. The turning point of the current, $P_{i2}$, in the AC current vs. voltage characteristics occurred between 5kV and 6kV, and the breakdown voltage was low between 13.8kV and 16.4kV. There was a strong correlation between the breakdown voltage and various electrical characteristics in diagnostic tests including Pi2.

Breakdown Characteristics of Dry Air under 170[kV] GIB (170[kV] GIB 내에서 건조공기(Dry Air)의 절연파괴 특성)

  • Han, Ki-Son;Yoon, Jin-Yul;Ju, Hyung-Jun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.10
    • /
    • pp.136-142
    • /
    • 2010
  • In this paper, we changed $SF_6$ insulation gases used already in the GIB(Gas Insulated Bus, gas insulated busbar) of switching appliances of power grid 170[kV] GIS(Gas Insulated Switchgear, Gas Insulated Switchgear) with green insulation dry air gases and studied dielectric breakdown voltage characteristics by the AC voltage withstand test. Withstand test AC voltage applied to the standard KEPCO's 170[kV] GIB with dry air insulation and and the equivalent of dry air and $SF_6$ gas were examined. Breakdown voltage of dry air, using an expression of the experiments were calculated and AC Withstand criterion of dry air insulation for the AC voltage test was derived. Using the criterion, dry air gases can be used instead of the $SF_6$ gas was confirmed in the factory acceptance test at 170[kV] GIB.

A Study on Characteristics of Insulation Breakdown by the Mixing Ratio of enhanced Dry Air and SF6 (개선된 Dry Air와 SF6의 혼합비에 따른 절연파괴 특성 연구)

  • Seok, Jeong-Hoo;Beak, Jong-Hyun;Lim, Dong-Young;Bae, Sungwoo;Kim, Ki-Chai;Park, Won-Zoo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.30 no.3
    • /
    • pp.86-93
    • /
    • 2016
  • It is very desirable that a mixture gas possessing excellent insulation performance is suggested for insulation on increasing high voltage. This paper proposes a $SF_6$ mixture gas based on the factors including dielectric strength, environmental impact and economic feasibility of manufacture for the insulation in eco-friendly power equipment. A suitable-$SF_6$ content was determined to improve the dielectric strength in $N_2$ and Dry Air. The examination results of the factors revealed that a $SF_6$/Dry Air mixture gas possessing the $SF_6$ content was more appropriate than a $SF_6/N_2$ mixture gas to the eco-friendly power equipment. In addition to the selection of the suitable $SF_6$ mixture gas, insulation characteristics as a function of $SF_6$ content were described from electron-detachment mechanism.

Insulation Characteristics of High Temperature Superconducting Cable (고온 초전도 레이블의 절연 특성)

  • Kim, H.J.;Kim, J.H.;Sim, K.D.;Kim, H.J.;Cho, J.W.;Seong, K.C.;Kwag, D.S.;Kim, S.H.
    • Proceedings of the KIEE Conference
    • /
    • 2004.11a
    • /
    • pp.244-247
    • /
    • 2004
  • The electrical insulating design is important to realize a HTS power cable because the cable is operated under the high voltage environment. For the insulation design of a HTS power cable, it is necessary to investigate the AC, impulse breakdown and partial discharge(PD) inception stress of liquid nitrogen/LPP composite insulation system. Based on these results, the electrical insulation of a HTS power cable is designed and Mini-model cables are manufactured. The manufactured Mini-model cables are evaluated that AC, impulse withstand voltage, breakdown and partial discharge inception stress and analyzed characteristics insulation of HTS cable bending condition according to this paper. From these tests, the AC, impulse withstand voltage test and partial discharge inception stress is satisfied "standard technical specification of KEPCO" in Korea and the breakdown voltage was 120kV.

  • PDF

Insulation Design for a 13.2kV/630A High-Tc Superconducting Fault Current Limiter (13.2kV/630A급 고온초전도 한류기의 절연설계)

  • Kang, Hyoung-Ku;Lee, Chan-Joo;Ko, Tae-Kuk;Seok, Bok-Yeol
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.941-942
    • /
    • 2007
  • The superconducting fault current limiter (SFCL) consists of superconducting coil for limiting the fault current and cryogenic cooling system for keeping the coil in superconducting condition. The study on the insulation design for superconducting coil and cryogenic cooling system should be elaborately performed to develop a high voltage SFCL. In this paper, insulation design of solenoid coil for 13.2kV/630A SFCL is performed through the AC dielectric breakdown test and lightning impulse dielectric strength test. The dependence of dielectric characteristics on the magnitude of liquid nitrogen pressure is also investigated. Through the investigation, it is verified that dielectric characteristics of sub-cooled nitrogen are strongly enhanced by the pressurization. The electrical insulation design of 13.2kV/630A SFCL is performed by applying the experimental results. The successful insulation design for development of 13.2kV/630A SFCL is confirmed by AC dielectric breakdown tests.

  • PDF

An Experimental Study on Water Absorbtion Characteristics of Generator Stator Bar Insulation by Cooling Water Temperature in 500MW Capacity Power Plant (500MW급 화력 발전기 냉각수 온도에 따른 고정자 권선 절연재의 흡습 특성에 관한 실험적 연구)

  • Bae, Yong-Chae;Kim, Hee-Soo;Lee, Doo-Young;Lee, Wook-Ryun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.8
    • /
    • pp.1392-1397
    • /
    • 2008
  • The mechanical integrity of generator stator windings is one of the critical point because the electric power is generated and conducted to power system through these windings. De-mineralized water is used to cool stator bars during the normal operation of generator in large power plants because the water cooled method has highest cooling efficient. Water absorption of bar insulation is progressed by several causes such as generation of water leak path by corrosion, delamination of insulation by vibration, and inadequate water treatment, etc.. Reliable water absorption diagnostics of generator stator bar is important to ensure the availability of power plant and to reduce maintenance cost by generator accident. It is described that the water absorption characteristics for generator stator bar insulation used in 500MW capacity standard fossil power plant by cooling water temperature. It is verified that the management of stator cooling water temperature is one of the important factors to decrease water absorption rate of generator stator bars.

Surface Flashover Characteristics on Poor Contact in N2/O2 Mixture Gas under Non-Uniform Field (불평등 전계 중 불량 접촉갭에 관한 N2/O2 혼합가스의 연면플래쉬오버특성)

  • Lim, Dong-Young;Choi, Eun-Hyeok;Choi, Sang-Tae;Choi, Byoung-Ju;Lee, Kwang-Sik;Bae, Sungwoo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.8
    • /
    • pp.63-69
    • /
    • 2015
  • This paper presents the surface flashover characteristics to simulate the poor contact between an anode and a solid dielectric in a $N_2/O_2$ mixture gas (8/2) under a non-uniform field. The surface flashover voltage of the $N_2/O_2$ mixture gas revealed the irregular tendency that was not in accordance with the Paschen's law with an increasing gap of the poor contact. In addition, the insulation performance of the $N_2/O_2$ mixture gas at 0.6MPa was comparable to that of $SF_6$ gas of 0.1MPa based on the insulation performance on the poor contact. These results are able to apply the insulation design of eco-friendly gas insulation switchgear considering the internal faults.