• 제목/요약/키워드: Impulse Current Generator

검색결과 50건 처리시간 0.026초

복합차체의 낙뢰에 대한 인체 안전성 분석 (Safety Analysis for Passengers of Composite Car-body against Lightning Strikes)

  • 길경석;박대원;김성욱;박찬용;조영진
    • 한국전기전자재료학회논문지
    • /
    • 제22권6호
    • /
    • pp.526-531
    • /
    • 2009
  • In this paper, the safety for passengers of composite car-body against lightning strikes was analyzed by the application of an impulse generator which can produce impulse current up to 50 kA with 8/$20{\mu}s$ waveform. Potential difference on inside surface of the car-body was measured as a safety parameter for the passengers against lightning strikes. The potential difference between 20 em distant was 175 V at 37.67 kA, and it corresponds to 875 V between 1 m distant. The amount of charge flowing a passenger at 100 kA impulse current can be estimated to $0.31\;mA{\cdot}s$. This is much less than the limit amount of charge for human body, $30\;mA{\cdot}s$ which is presented by Koeppen and Osypka.

$10/350{\mu}s$ 서지전류를 이용한 I 등급 SPD의 성능평가 (Performance Evaluation of Class I SPD Using $10/350{\mu}s$ Surge Current)

  • 조성철;엄주홍;이태형
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.1466-1467
    • /
    • 2007
  • A new parameter W/R for the class I test have been introduced in the IEC 61643-1 published in 2005. One of the possible test impulses which meets the parameters for class I test is the 10/350 [${\mu}s$] waveshape proposed in IEC61312-1. 10/350 [${\mu}s$] waveshape meets parameters for class I test in the IEC 61643-1. The impulse generator for making the 10/350 [${\mu}s$] waveshape is consist of IVG, ICG, crowbar coil and crowbar switch. The electric change Q and the specific energy W/R were measured and calculated using the exclusive use measuring software according to the formula of IEC 611643-1. We verified the correspondence between measured results using impulse generator and recommended parameters by IEC 61643-1.

  • PDF

산화아연 피뢰기 소자의 다중 뇌 임펄스 특성 (Effect of Multiple Lightning Impulse Currents on Zinc Oxide Arrester Blocks)

  • 이복희;강성만;박건영;최휘성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.22-24
    • /
    • 2003
  • In this work, in order to investigate the effect of multiple lightning impulse currents on zinc oxide arrester blocks. We have been designed and fabricated a multi-impulse generator which can produce quintuple voltages with $1.2/50{\mu}s$ to 100kV and quintuple currents with $8/20{\mu}s$ to 12kA and we have evaluated the characteristics of zinc oxide arrester block using several electrical and physical methods after the multi-impulse test. It was found that the multi-impulse failures of ZnO arrester blocks were mainly caused by surface flashover and the multi-impulse currents test would be more suitable than single impulse current test in evaluation of the characteristics of zinc oxide arrester blocks corresponding to actual situations.

  • PDF

조명기기의 임펄스내전압 성능의 분석 (Analysis of Impulse Withstand Voltage Performance of Lighting Equipment)

  • 이복희;방평호
    • 조명전기설비학회논문지
    • /
    • 제28권3호
    • /
    • pp.91-96
    • /
    • 2014
  • Modern electronic circuits are becoming more vulnerable to damage by surges, and it is required to improve the impulse withstand voltage performance of electrical and electronic equipment. This paper presents the impulse withstand voltage performance of lighting equipment connected to power lines, and the impulse withstand voltage tests for fluorescent lamp, LED lamp and halogen lamp were carried out according to the reference standards under normal service conditions. To conduct performance tests against lightning surge, a combination wave ($1.2/50{\mu}s$ voltage - $8/20{\mu}s$ current) was employed. The test surge was applied between lines or between line and ground of the specimen to be measured. The test surge was applied synchronized at the peak value of the positive and negative AC voltage waves. As a consequence, some specimens satisfied the impulse withstand voltage test criteria, but lighting equipment such as 36W fluorescent lamps, 5W and 5.5W LED lamps and 50W halogen lamp were damaged at the test voltage levels between power lines. It is needed to improve the qualities of lighting equipment to satisfy EMC immunity requirements of equipment for general lighting purposes.

고전압 COS 퓨즈로부터 방사된 충격성 소음의 전파특성과 저감에 관한 실험적 연구 (An Experimental Study on the Propagation Characteristics and Reduction of Impulse Noises from a High Voltage COS Fuse)

  • 송화영;주경민;이동훈;강내국;정낙헌
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2005년도 추계학술대회논문집
    • /
    • pp.71-74
    • /
    • 2005
  • This experimental study describes the propagation characteristics and reduction of impulse noises emitted from a high voltage COS(Cut Out Switch) fuse of a transformer. When a high voltage COS fuse becomes a short circuit by the over current. The peak sound Pressure above 150dB(A) is generated. In this study, an impulse noise generator is designed for generating the impulse noises similar to the noise level of COS fuse, which is utilized to test the noise reduction of a reactive silencer. The reactive silencers have been tested for 10 different types with each different porosity, hole diameter and length. From the experimental results, it is found that the reactive silencer has an excellent performance to greatly suppress the impulse noise and that its performance is closely connected with the porosity and hole diameter.

  • PDF

동결 토양에서 지중방전을 고려한 소규모 전극의 과도접지임피던스 특성 (Transient Ground Impedance of Small-sized Ground Electrode considering Underground Discharge in Frozen Soil)

  • 이태형;조성철;엄주홍;이복희
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2009년도 춘계학술대회 논문집
    • /
    • pp.324-327
    • /
    • 2009
  • This paper presents the transient impedance in a discharge region when high voltage lightning impulse is applied to small-sized ground electrodes in frozen soil. For a realistic analysis of ionization characteristics near the ground electrode in the soil, ground rod installed outdoors and high voltage impulse voltage generator were used. From the analysis of response voltage and current flowing ground electrode to earth, it was verified that the ionization near the ground electrode contributes to reduction of ground impedance and limits the ground potential rise effectively under high impulse voltage.

  • PDF

대지구조에 따른 매설지선의 과도접지임피던스 특성 (Transient impedance characteristics of counterpoise according to the soil structures)

  • 이복희;이봉;정동철;김기복;조성철
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2009년도 추계학술대회 논문집
    • /
    • pp.311-314
    • /
    • 2009
  • This paper presents the characteristics of grounding impedance of counterpoises buried at various soil structures. Grounding impedance measurements were made by the Fall-of-Potential method. The experiments were carried out in 50 m counterpoise of 25 $mm^2$ buried at a depth of 0.5 m. The test current was injected by the impulse generator having the front time of $1{\sim}60{\mu}s$. As a result, the soil structures greatly influences on the grounding impedance characteristics of counterpoise. The transient grounding impedances strongly depend on the injection mint and the front time of impulse current.

  • PDF

Parameters Optimization of Impulse Generator Circuit for Generating First Short Stroke Lightning Current Waveform

  • Eom, Ju-Hong;Cho, Sung-Chul;Lee, Tae-Hyung
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권1호
    • /
    • pp.286-292
    • /
    • 2014
  • This paper presents the parameters optimization technology for generating the first short stroke lightning current waveform($10/350{\mu}s$) which is necessary for the performance tests of components of lightning protection systems, as required under IEC 62305 and the newly amended IEC 62561. The circuit using the crowbar device specified in IEC 62305 was applied to generate the lightning current waveform. To find the proper parameters of the circuit is not easy because the circuit consists of two parts; circuit I, which relates to the front of current waveform, and circuit II, which relates to the tail. A simulation in PSpise was carried out to find main factors related to the front and tail of $10/350{\mu}s$. The lightning current generator was developed by utilizing the circuit parameters found in the simulation. In the result of experiments, new parameters of the circuits need to be changed because of the difference between the simulation and the experiment results. Using the iterative method, the optimized parameters of the circuits was determined. Also a multistage-type external coil and a damping resistor were proposed to make the efficiency of generation to enhance. According to the result in this paper, an optimized first short stroke lightning current waveform was obtained.

RCD와 SPD의 접속 위치에 따른 보호협조 (Protection Coordination Associated with Connection Location of Residual Current Devices and Surge Protective Devices)

  • 이복희;박희열;신건진;배관영;류춘형;이강희
    • 조명전기설비학회논문지
    • /
    • 제27권3호
    • /
    • pp.100-106
    • /
    • 2013
  • In this paper, in order to analyze lightning impulse response characteristics in combined installations of SPDs and RCDs, surge protection coordination between SPDs and RCDs are experimentally investigated by using the combination wave generator. Six different types of single-phase residual current operated circuit-breakers with integral overcurrent protection for household and similar uses(RCBOs) being present on the domestic market are tested according to KS C IEC 61009-1 standard. As a result, when a class I SPD is located on the source side of an RCBO, all kinds of specimens are able to provide the proper coordination between the SPD and RCBOs without nuisance tripping, unintended operation or damage due to test impulse currents. However, in the case that the class II SPD is located on the load side of RCBOs, a lot of L-N mode injected currents is split into the RCBO, and a few RCBOs are damaged. Coordination between SPDs and RCDs is not valid and a role of SPDs is of no use. When combining SPDs with RCDs, it is necessary to select SPDs and RCDs in consideration of the protection voltage level of metal oxide varistor embedded in RCDs.

전기광학변환소자로서의 결정과 그 응용 - 학술강연회초록

  • Naomi Furuya
    • 전기의세계
    • /
    • 제22권3호
    • /
    • pp.79-80
    • /
    • 1973
  • This is the abstract of lecture on Electro-optic characteristics of D-KDP crystal and its application for high speed shutter made by Dr. Naomi Furuya; The professor of Yamanashi University in Kofu Japan on March 31, 1973 for KEEI in the auditorium of Korea Electric Company. His lecture is listened by KEEI members that KDP Z-cut crystal can be utilized as a high speed shutter of 10$^{-6}$ second, combining special camera and 2-3KV electrical impulse generator and also recording slide photographs on tungoten lamp crystal voltage and melting fuse phenomena due to over-current taken by this special equipment had been demonstrated.

  • PDF