• Title/Summary/Keyword: Impulse Current

Search Result 369, Processing Time 0.031 seconds

The transient grounding impedance measurment of large grid grounding electrodes (대규모 그리드 접지전극의 과도접지임피던스의 측정)

  • Jeon, Byung-Wook;Lee, Su-Bong;Li, Feng;Lee, Seung-Ju;Jung, Dong-Cheol;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.10a
    • /
    • pp.69-72
    • /
    • 2008
  • This paper presents the transient and conventional grounding impedance behaviors of large grid grounding system associated with the injection point of impulse current The measurement methods consider two possible errors in the grounding-system impedances: (1) ground mutual resistance due to current flow through ground from the ground electrode to be measured to the current auxiliary, (2) ac mutual coupling between the current test lead and the potential test lead The test circuit was set to reduce the error factors. The transient grounding impedance depends on the rise time and injection point of impulse current It is effective that grounding conductor is connected to the center of the large grid grounding system.

  • PDF

Property of Long vertical rod according to the different injection point with impulse current (대형 봉상 접지전극의 임펄스 인가위치에 따른 특성)

  • 이복희;장근철;엄주홍;김병근;오성균;길형준
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2003.11a
    • /
    • pp.369-372
    • /
    • 2003
  • To obtain a low ground resistance in high resistivity soil or in insufficient place such as downtown, long vertical ground rods are often used. However, if the lightning current or fault current with high frequency flows into the grounding system, the ground impedance is remarkedly increased. This paper presents how the impulse and fault current works on the long. vertical ground rods associated with incoming points. When the test current was injected at the bottom of ground rod, the potential waveform of ground rod includes the oscillation with high frequency.

  • PDF

Ground ing Impedance Characteristics of Ground Rods in frequency Domain (주파수 영역에서 봉상전극의 접지임피던스 특성)

  • Lee, Hyung-Soo;Shim, Keon-Bo;Kim, Kyung-Chul;Choi, Jong-Kee;Park, Sang-Man
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.248-253
    • /
    • 2005
  • Although DC ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute index due to its dependence on impulse current shape. In this paper, ground impedance of various rod-type ground electrodes has been measured in frequency domain ranging from 1 Hz to hundreds of kHz. Equivalent circuit models of the ground rod have been identified from the measured values of ground impedance in frequency domain.

  • PDF

Modeling of Impedance Characteristics of Grounding Electrode for Distribution Line Pole (배전전주의 봉상 접지전극 형태별 임피던스 특성의 모델링)

  • Shim, Keon-Bo;Kim, Kyung-Chul;Lee, Hyung-Soo;Park, Jae-Duck;Choi, Jong-Kee;Park, Sang-Man
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.694-696
    • /
    • 2005
  • Although DC ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute index due to its dependence on impulse current shape. In this paper, ground impedance characteristics of ground electrodes has been measured in frequency domain ranging from 1 Hz to hundreds of kHz. Equivalent circuit models and transfer function models of the ground rod have been identified from the measured values of ground impedance in frequency domain.

  • PDF

Electrochemical Impulse Oscillations at the Platinum Group Electrode Interfaces (백금족 전력 계면에서 전기화학적 Impulse 발진)

  • 전장호;손광철;라극환
    • Journal of the Korean Institute of Telematics and Electronics A
    • /
    • v.32A no.3
    • /
    • pp.143-151
    • /
    • 1995
  • The electrochemical impulse oscillations of the cathodic currents at the platinum group (Pt, Pd) electrode/(0.05M KHC$_{8}H_{4}O_{4}$) buffer solution interfaces have been studied using voltammetric, chronoamperometric, and electrochemical impedance methods. The periodic impulses of the cathodic currents are the activation controlled currents due to the hydrogen evolution reaction, and depend on the fractional surface coverage of the adsorbed hydrogen intermediate and potential. The oscillatory mechanism of the cathodic current impulses is connected with the unstable steady state of negative differential resistance. The widths and periods of the cathodic current impulses are 4ms or 5ms and 152.5ms or 305ms, respectively. The H$^{+}$ discharge reaction step is 38 or 61 times faster thatn the recombination reaction steps and the H$^{+}$ mass transport processes. The atom-atom recombination reaction step is twice faster thatn the atom-ion recombination reaction step. The two kinds of active sites corresponding to the atom-atom and atom-ion recombination reaction steps exist on the platinum group electrode surfaces.

  • PDF

Transient Impedance Characteristics of Mesh Grounding System under Impulse Current (임펄스 전류에 대한 메쉬접지계의 과도임피던스 특성)

  • Lee, Bok-Hee;Park, Jhong-Soon
    • Proceedings of the KIEE Conference
    • /
    • 1997.11a
    • /
    • pp.361-363
    • /
    • 1997
  • Electronic devices are very weak against lightning surges injected from grounding systems and can be damaged. The malfunction and damage of electronic circuits bring about several disadvantages such as low operation performances, a lot of economical losses, and etc. In order to obtain the effective protection measure of electronic devices from overvoltages and lightning surges, the analysis of the transient grounding impedances is very important. The aim of this work is to evaluate the behaviors of transient grounding impedances under impulse currents and to investigate the effect of grounding lead wire. Z-t, Z-i and V-i curves of transient grounding impedance under impulse current waveforms have been measured and analyzed.

  • PDF

Ionization characteristics in soil Subjected to Impulse Voltage (임펄스전압에 의한 토양의 이온화 특성)

  • Kim, Hoe-Gu;Park, Geon-Hun;Choi, Jong-Hyuk;Cho, Jung-Hyun;Lee, Gang-Su;Lee, Bok-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.1362-1363
    • /
    • 2008
  • It has been known that the values of soil resistance drops when a high impulse current is injected into a grounding electrode. In this study, the electrical characteristics of medium grain size sand to different water contents are investigated. The results were discussed based on its voltage and current traces, impulse resistances and I-V curve.

  • PDF

Analysis of soil discharge characteristics in sand with water content (수분 함유량에 따른 모래의 지중방전 특성 분석)

  • Lee, Bok-Hee;kim, Hoe-Gu;Park, Geon-Hun;Lee, Kyu-Sun;Ahn, Chang-Hwan
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.436-439
    • /
    • 2008
  • It has been known that the value of soil resistance drops when a high impulse curennt is injected into a grounding electrode. In this paper, impulse generator is used to investigate the dry soil and wet soil characteristics in cylinderical test cell. The impulse resistances and breakdown characteristics were discussed based on its voltage and current traces. As a result, sand resistances are decreased with increasing the applied currents. It was thought that a decrease in resistance of dry sand with increasing current is due to both thermal and ionization processes. On the other hand, in case there is no water presence in the soil, the reduction in resistance as the currents are of dry sand increased is mainly due to the ionization process.

  • PDF

The Effects of Soil Model in the Grounding System Design (침상 접지전극봉의 접지효과 분석)

  • Lee, Hyung-Soo;Shim, Keon-Bo;Ahn, Chung-Hoon;Kim, Kyu-Sam
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.451-455
    • /
    • 2004
  • Although DC ground resistance is a good index of performance for a grounding system, it does not reflect the grounding performance during the transient states. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute performance index due to its dependence on impulse current shape. In this paper, a grounding performance of needle-typed ground rod has been compared with simple ground rod.

  • PDF

Safety Analysis for Passengers of Composite Car-body against Lightning Strikes (복합차체의 낙뢰에 대한 인체 안전성 분석)

  • Kim, Sung-Wook;Choi, Su-Yeon;Park, Dae-Won;Kil, Gyung-Suk
    • Proceedings of the KSR Conference
    • /
    • 2008.11b
    • /
    • pp.144-150
    • /
    • 2008
  • In this paper, the safety for passengers of composite car-body against lightning strikes was analyzed by the application of an impulse generator which can produce impulse current up to 50 [kA] with 8/20 [us] waveform. Potential difference on inside surface of the car-body was measured as a safety parameter for the passengers against lightning strikes. The potential difference between 20 [cm] distant was 175 [V] at 37.67 [kA], and it corresponded to 875 [V] between 1 [m] distant. The amount of charge flowing a passenger at 100 [kA] impulse current can be estimated to 0.31 [mA s]. This is much less than the limit amount of charge for human body, 30 [mA s] which is presented by Koeppen and Osypka.

  • PDF