• Title/Summary/Keyword: Illuminance fluctuation

Search Result 5, Processing Time 0.022 seconds

Analyses on Daylight Variations for Optimum Controls of Daylight Dimming Systems in a Small Office (소규모 사무실에 적용된 조광제어 시스템의 최적제어를 위한 주광변화 분석)

  • Yoon, Youn-Ju;Baik, Yong-Kyu;Kim, Soo-Young
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.24 no.5
    • /
    • pp.433-442
    • /
    • 2012
  • The influence of outdoor sky conditions on photosensor signals were examined to determine an appropriate index that is effectively used for optimum illuminance fluctuation when a daylight dimming system is used for a small office. Field measurements were conducted under various sky conditions. Results indicate that the outdoor global and vertical illuminance fluctuated within narrow ranges under clear and overcast sky conditions. The fluctuation of sky ratio under partly-cloudy sky caused wide ranges of illumnance fluctuation. A partially-shielded photosensor at backwall produced 56% of light output from fixtures controlled by a photosensor at ceiling. This implies that the photosensor at backwall does not always guarantee target illuminance due to the less output. The fluctuation of light output from fixtures were insignificant under clear and overcast sky. The fluctuation range of photosensor illuminance under partly-cloudy sky caused wide fluctuation ranges of light output. Regression result implies that the outdoor vertical illuminance was recommended for an effective index that is used for control of light output.

Analyses on Photosensor Illuminance for Prediction of Fluctuating Illuminance by Daylight Dimming Control Systems (조광제어 시스템 적용시 실내조도의 변동예측을 위한 포토센서의 주광조도 분석)

  • Kim, Soo-Young
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.22 no.11
    • /
    • pp.788-797
    • /
    • 2010
  • This study examines the influence of fluctuating daylight illuminance on daylight dimming control systems. Field measurements were performed for a full-scale mocked-up model under various daylight conditions in winter. Fluctuating ranges for a partially-shielded photosensor were great when the variation of sky ratio was great. When solar altitude was lower the illuminance and fluctuating range of illuminance were great due to the influence of direct components of daylight and the interrefelction between surfaces in rear area of space. It implies that daylight dimming system would not function effectively, unless the desktop illuminance by daylight is enough. Fluctuation ranges of photosensor illuminance were lower than 50 lx under clear sky conditions, but they were greater than 100 lx under partly-cloudy sky conditions. It means that the fluctuation range of electric light output of lighting fixture would greater under the partly-cloudy conditions and cause potential visual annoyance to occupants. Outdoor vertical illuminance reaching the windows would be an effective factor that can be used to predict the fluctuation of photosensor signals for effective controls of daylight dimming system.

The Influence of Illuminance Variation by a Daylight Dimming Control System on Visual Comfort Under Clear Sky Conditions (청천공 조건에서 조광제어 시스템 적용시 조도변화에 대한 시각적 만족도 분석)

  • Kim, Soo-Young
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.22 no.8
    • /
    • pp.553-561
    • /
    • 2010
  • This study examines the influence of light variation on visual responses in a small office space where a daylight dimming control system is applied. Field measurements and survey were performed in a full-scale mocked-up small office space under clear sky day conditions. Maximum fluctuation range for desktop was 133.5 lx and it just happened once for entire monitoring period. For the majority of time, the fluctuation range did not exceed 50 lx, which did not cause visual discomfort to subjects. The daylight dimming control system successfully kept required illuminance levels for an office environment when desktop illuminance by daylight ranged up to 300 lx. The most serious contributor to the sensation of glare was direct daylight through window. The dimming of electric light was not a significant contributor to visual discomfort for the subjects under clear sky day conditions. Visual comfort was significantly influenced by the sensation of glare, feeling for visual stimulation and distraction, and required illuminance level.

The Effect of The Index of Indoor Environment on The Productivity (실내환경지수가 생산성에 미치는 영향)

  • Kim, Myung-Ho;Lee, Ye-Jin
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.19 no.1
    • /
    • pp.615-621
    • /
    • 2018
  • To enhance the energy saving and comfort of indoors, this study performed a stimulation of sound fluctuation, color temperature, and aroma. The experiment with EEG, HRV, and Vibra images was conducted in an environmental test room with a temperature of $25[^{\circ}C]$, relative humidity of 50[RH%], air current speed of 0.002[m/s], and illuminance of 1000[lux]. The stimulation experiment set up different sensory stimulation conditions, such as before exposure, single-sensory stimulation of fluctuation a=1.106 jazz music, single-sensory stimulation of RED color lighting, single-sensory stimulation of scent aroma, and multi-sensory stimulation of fluctuation a=1.106 jazz music, RED color lighting, and scent aroma. After the multi-sensory stimulation of fluctuation a=1.106 jazz music, RED color lighting and scent aroma, the capacity for work and attention were increased, and the stress index and fatigue degree were decreased. In addition, multi-sensory stimulation of fluctuation a=1.106 jazz music, RED color lighting, and scent aroma were effective in maintaining a stable heart and health. In addition, the Vibra image appeared to decrease tension/anxiety and stress. The multi-sensory stimulation of fluctuation a=1.106 jazz music, RED color lighting, and scent aroma help increase the Neuro-energy more than that by no exposure and single-sensory stimulation.

A Study on the 'a' index of Sound source for Productivity improvement (생산성향상을 위한 음원의 a지수에 관한 연구)

  • Yoo, Young-Jo;Kim, Myung-Ho
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.15 no.1
    • /
    • pp.547-554
    • /
    • 2014
  • In this study, have researched 'a' index from three sound sources, effects on subject and finding optimal 'a' index, which can improve subject's stability, concentration and productivity. Check the health status of subjects who were selected 5 male and 5 female university students, and the period of this experiment was about two months. It were measured each subject's EEG, HRV and vibra image to analyze transition of stability, concentration, stress and heart beat. The results was measured in an environmental test room of temperature $25[^{\circ}C]$, the relative humidity 50 [%], illuminance 1,000 [lux] and air current speed 0.02[m/sec] with 'a' index of three sound sources which are a=1.106, a=1.749 and a=2.227. Results in a=1.106 compared to before exposure, relative $S{\alpha}$ wave, relative $L{\beta}$ wave and relative $M{\beta}$ wave have been revitalized, asymmetry index, stress and HRV have been decreased. Thus, to increase stability, concentration and productivity, also to decrease stress, changes in sound source of a=1.106 was found to be the most effective.