• Title/Summary/Keyword: Hot Smoke Test

Search Result 14, Processing Time 0.021 seconds

Flame control method for hot smoke test (Hot smoke test 를 위한 화염 제어 방법)

  • 김진국
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1996.11a
    • /
    • pp.30-33
    • /
    • 1996
  • This paper presents the technical basis for hot smoke test intended to investigate the effectiveness of smoke ventilation system in both high-rise building and those containing atria and/or galleria. Smoke is particularly serious hazard in these building in which considerable time is required for complete evacuation. It is widely recognised that the effectiveness of large smoke ventilation system can be difficult to confirm by a critical analysis of the system design calculation. Thus a hot smoke test is recently introduced through the experiences of many attempts. Diffusion flames used for hot smoke test have a higher flame length, so that those can not be applied to small compartment. Therefore the objective of this paper is introducing the method of flame control which can be applied to any size of compartment

  • PDF

Full-Scale Test of Smoke-Control Performance of a Subway Tunnel (지하철 본선터널 제연성능 실물 실험)

  • Park, Won-Hee;Lee, Duck-Hee;Jung, Woo-Sung
    • Fire Science and Engineering
    • /
    • v.25 no.4
    • /
    • pp.94-102
    • /
    • 2011
  • Hot smoke test is done in a subway tunnel. Alcohol trays of 1.0 MW and smoke generators are used for generating hot smoke. The fans equipped with the tunnel are successively run 9 min after smoke generation. It is verified how hot smoke is controlled by fans. Velocity and direction of flow, temperature and smoke density are measured and analyzed for smoke control performance of the tunnel with fans and analyzed from the fire-safety-point of view. Velocity of smoke flow is obtained by using measured velocity and temperature at the ceiling of the tunnel. The time when smoke-control flow is builded up is different for the different positions. Velocity distributions at various positions will be used for the boundaries and the comparison data in numerical simulations for evaluation on smoke-control facilities of subway tunnel.

Evaluation of Smoke Control Performance of Ventilation System Using by Hot Smoke Test (Hot Smoke Test를 이용한 주차장 환기설비의 제연 성능평가)

  • Joung, Suckhwan
    • Journal of Korean Society of Disaster and Security
    • /
    • v.12 no.2
    • /
    • pp.47-56
    • /
    • 2019
  • Recently, in order to overcome the difficulty of entering a fire source due to the occurrence of a large amount of smoke in the event of a fire in a parking lot, it has used that a method of discharge smoke using air supply, exhaust fans and jet fans installed for ventilation of parking lots. In this study, the variation of flow in the smoke layer was observed using CCTV under two conditions, in which only the air supply fan operates and the manned fan operates together, and the temperature around the plume was compared to Albert eq. to assess its suitability as a parking lot ventilation performance evaluation method. As a result, it was found that the smoke layer could be disturbed if the Jet Fan was operated at the same time, which could lead to the possibility of an initial evacuation disturbance. However, the additional operation of the Jet Fan has been confirmed by the observation CCTV that the emission performance is improved, which is believed to help conduct the suppression operation. The temperature around the plume was measured and compared to Alpert eq, and was analyzed to be about $2^{\circ}C$ lower at the center axis of the plume and $9.0^{\circ}C$ higher at 8 m in the direction of the discharge of smoke. The results of temperature measurements around the plume were lower than the maximum temperature expected in AS 4391 and did not exceed the expected temperature risk caused by the experiment. As with these results, the temperature risk from the progression of hot smoke tests is foreseeable, so it will be available as one of the general evaluation methods for assessing smoke control performance in a parking lot without relevant criteria.

A Study of the Opacity Correlation Factor between the Filtration Type and Light Extinction Type Diesel Smoke Meters (여지반사식과 광투과식 매연측정기의 매연도 상관계수에 관한 연구)

  • Kim, Young-Ju;Park, Kyoung-Seok
    • Transactions of the Korean Society of Automotive Engineers
    • /
    • v.15 no.5
    • /
    • pp.146-152
    • /
    • 2007
  • Recently, The air pollution problems become hot issues as the production of the diesel automotive increases. The ministry of environment has enforced a precise inspection law to decrease the vehicle emission. In this circumstances, the smoke measurement is somewhat complicated by the use of the different type smoke meters. Although the paper filtration type opacimeter has been used for measuring smoke widely but currently the light extinction type is being used for precise inspection law. These two type opacimeters are different in their measuring principles on each other. So, for the time being the regulation standards can be confused by these two type opacimeters. In this article, The correlation factor between these two type opacimeters is studied by using engine dynamometer and vehicle test. The result of the dynamometer test shows the light extinction type is more sensitive than the filtration type by 1.47 times. But the relation factor by the vehicle test achieved 1.37 value, which is lower than that of the dynamometer test. In the future study the more precise research is needed to estimate the relation factor on vehicle test.

Standardization of the Performance Test Procedure for Smoke Control System (제연설비 성능시험방법의 표준화)

  • Kwark, Ji-Hyun
    • Fire Science and Engineering
    • /
    • v.20 no.3 s.63
    • /
    • pp.21-28
    • /
    • 2006
  • Since hot toxic gas included in the fire is the most principal reason of the death and has the fluid mechanical characteristics unlike air, smoke control method appropriate for the figure and structure of a fire room is needed and each unit of the smoke control system requests high performance according to this characteristics, for which performance test procedures and evaluation criteria must be established. Domestic criteria involved with the smoke control consist of the pre-investigation by documents and the part inspection, which has lots of problems because they are far from the performance based evaluation method compared with the references of developed countries. Consequently, domestic and international references were compared and analyzed, problems being emerged and standardization scheme of the test procedure was presented.

A Study on the Improvement of Domestic Smoke Control Standards through Analysis the Standards about Air Leakage Rate of Domestic and Abroad (국내·외 누설률에 관한 기준 분석을 통한 국내 연기제어 기준 개선에 관한 연구)

  • Kim, Hye-Won;Han, Ji-Woo;Lee, Byeong-Heun;Jin, Seung-Hyeon;Kwon, Young-Jin
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2018.11a
    • /
    • pp.61-62
    • /
    • 2018
  • On this Study, it conducts the Standards investigation about air leakage of Buildings for performance improvement of Smoke control in Fire. In domestic standards, it is incomplete the Criteria standards of air leakage. Therefore it is considered that won't limit the smoke spread due to stack effect. But in the case of the United States, it conducts the Hot smoke air-Leakage test and it consider that can prevent the Smoke Spread in Compartment.

  • PDF

An Experimental Study on Flow Angle with Swirl in a Horizontal Circular Tube (수평 원통 관에서 선회를 동반한 유동각에 대한 실험적 연구)

  • Chang, Tae-Hyun
    • Journal of the Korean Society of Manufacturing Process Engineers
    • /
    • v.2 no.4
    • /
    • pp.82-87
    • /
    • 2003
  • Flow angle with Swirl in a horizontal circular tube and a cylindrical annuli were experimentally studied for its visualization. This present investigation deals with flow angle, flow visualization studies and vortex core by using oil smoke and a hot wire anemometer for Re = 40,000 and 50000 at X/D = 41, 59 and 71 in a horizontal circular tube. In the swirl air flow, a vortex core was formed at high swirl intensity along the test tube. The flow angle and the vortex core depended on the swirl intensity along the test tube. The results of flow angles with swirl measured by flow visualization and hot wire reasonably agree with those of Sparrow One of the primary objectives of this research was to measure the flow angle with swirl in a cylindrical annuli along the test tube for different Reynolds numbers. The Reynolds number for these measurements ranged from 60,000 to 100,000 with L/D = a to 4.

  • PDF

An Experimental Study on Exhaust Gas Change of a Heavy-Duty Diesel Engine by EGR (대형디젤기관의 EGR에 의한 배기가스변화에 관한 실험적 연구)

  • 오용석;문병철;한영출
    • Transactions of the Korean Society of Automotive Engineers
    • /
    • v.10 no.6
    • /
    • pp.59-64
    • /
    • 2002
  • The effects of EGR on emissions were investigated by using a six-cylinder, 8 litre, turbo-charged, heavy-duty diesel engine with a low pressure route EGR system. The experiments were performed at various engine loads while the EGR rates were set from 0% to 30%. Hot and cooled EGR are achieved without cooling and with cooling respectively. To verify the possibility of EGR technology for the applications, test were performed with steady state test cycle. It was found that the exhaust emissions with the EGR system resulted in a very large reduction in oxides of nitrogen at the expense of higher smoke and PM emissions. Increasing the EGR rate leads to deteriorating specific fuel consumption and power at lower speed and higher load. Also, the reduction rates of NOx emissions for hot and cooled EGR are similar.

An Experimental Investigation of Swirl Angle in a Horizontal Round Tube by Flow Visualization Method

  • Tae-Hyun Chang
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.27 no.7
    • /
    • pp.879-888
    • /
    • 2003
  • Swirling air flow in a horizontal round tube was experimentally studied for its visualization. The present investigation deals with swirl angle, flow visualization studies and accompanying vortex core behavior by using oil smoke and a hot wire anemometer for Re = 40,000 and 50000 at X/D = 41, 59 and 71. In the swirl air flow, a vortex core was formed at high swirl intensity along the test tube. The swirl angle and the vortex core depended on the swirl intensity along the test tube. The results of swirl angles measured by flow visualization and hot wire reasonably agree with those of previous studies.

Investigation of Performent Standards for the Fire Damper (방화Damper의 성능기준 고찰)

  • Jo, Jung-Dal
    • Fire Protection Technology
    • /
    • s.12
    • /
    • pp.10-17
    • /
    • 1992
  • Dampers which being installad in air duct are Valume damper, fire damper, leakage rated damper, but among them fire damper and leakage rated damper are used for preventing the spread of flame, hot gas and smoke through the duct. this report is aimed to intorduce the test example of the multiple fire damper which was conducted F.I.L.K, simuetaneously to investigate the performent standards and Structure of the fire damper which settled in several countries.

  • PDF