• 제목/요약/키워드: HTS-FCL

검색결과 41건 처리시간 0.04초

초전도 케이블의 퀜치 특성에 대한 계통안전성 제어방식 (Power System Security Control Method for Quench Characteristic of High-Temperature Superconducting Cable)

  • 이근준;황시돌;이정필;김창현;박희철
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 학술대회 논문집
    • /
    • pp.375-380
    • /
    • 2004
  • This paper presents the basic quench protection idea for the HTS(High-Temperature Superconducting) cable. In Korea power system, the transfer capability of transmission line is limited by the voltage stability, and HTS cable could be one of the countermeasure to solve the transfer limit as its higher current capacity and lower impedance[1]. However, the quench characteristic of HTS cable makes HTS cable to loss its superconductivity, and therefore change the impedance of the line and power system operating condition dramatically. This pheonominum threats not only HTS cable safety but also power system security, therefore a proper protection scheme and security control counterplan have to be established before HTS cable implementation. In this paper, the quench characteristics of HTS cable for the fault current based on heat balance equation was established and a proper protection method by FCL(Fault Current Limiter) was suggested.

  • PDF

YBCO Coated Conductor의 과전류 특성해석 (Analysis of Over-current Characteristics in YBCO Coated Conductor)

  • 이찬주;남관우;강형구;고태국;석복렬
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 B
    • /
    • pp.693-694
    • /
    • 2006
  • In order to develop a high temperature superconducting(HTS) coil for the fault current limiter(FCL), the over-current characteristics in YBCO coated conductor(CC) with Ni-W alloy substrate are analyzed. The HTS wire is wound by bifilar winding method for resistive current limitation and it is operated in 65K sub-cooled nitrogen. In order to analyze the resistance and the temperature characteristics of the CC wire, an analysis program is developed considering all the composition materials except the buffer layer. Using this program, the temperature rise, the resistance development and the current limitation of CC are calculated depending on the applied voltage and the stabilizer materials. According to the analysis results, under the temperature restriction of 300K, the maximum voltage per meter is determined as 40V/m if the stabilizer is $25{\mu}m$ thick stainless steel at each side. Finally, the wire length needed for the distribution level HTS FCL is estimated.

  • PDF

대용량 초전도 신전력계통 보호방식 문제해결을 위한 기본연구 (A basic study on protection system of superconductivity power system)

  • 이승렬;김종율;윤재영;이병준
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제9권3호
    • /
    • pp.16-20
    • /
    • 2007
  • This paper describes protection system of new distribution power system with superconducting power devices such as HTS cable, HTS transformer, HTS-FCL. First of all, this paper investigates protection systems of Korean power system and then do a basic study on relaying systems in the power system with HTS power devices. For the more detailed results, we did the study using EMTDC relaying system modeling from the viewpoint of superconducting power devices application. Then we proposed some solution for a high resistance fault problem.

PSCAD/EMTDC를 이용한 SMES Component modeling에 관한 연구 (A study on the SMES component modeling using PSCAD/EMTDC)

  • 김진근;김재호;정희열;박민원;유인근
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.1998-1999
    • /
    • 2007
  • Before applying the HTS(High Temperature Superconductor) power devices to a real utility network, system analysis should be carried out by some simulation tools. PSCAD/EMTDC simulation tool is one of the most popularized useful analysis tools for electrical power system. Unfortunately the model component for HTS coil is not provided in PSCAD/EMTDC simulation tool. In this paper, EMTDC model component for HTS coil has been developed considering real characteristics of HTS coil like critical current, temperature and magnetic field. The developed model component of HTS coil could be used for power system application. Using the developed model component for HTS coil, we can easily do the simulation of HTS power devices application test in utility with the various inductance, quench current, inner magnetic field, and temperature values, for instances; SMES(Superconducting Magnetic Energy Storage) system, superconducting motor, transformer, and FCL(Fault Current Limiter)

  • PDF

초전도케이블/한류기 실계통 적용 변전소 및 설치위치 선정 기술검토 (Determination of a Substation and Installation Site for applying Superconducting Cable/FCL to Real Power Grid)

  • 양병모;원영진;김병헌;강지원;윤재영;이승렬;문영현
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제11권3호
    • /
    • pp.55-59
    • /
    • 2009
  • In attempts to closely study the effect of high efficiency, friendly environment HTS(High Temperature Superconducting) cable and SFCL(Superconducting Fault Current Limiters) on power system, several projects were carried out around the world. Promising results have been achieved in terms of cable capacity and reliability. commercial HTS cable and SFCL, however, must not only be only be feasible, but meet practical requirements as well. To facilitate the transition of HTS cable technology from the Lab. to the Real Grid, a New project for applying 22.9kV HTS cables and SFCL to the commercial Power Grid supported by Government has just started in KEPCO. Target of this project is to operate two 22.9kV, 50MVA, 150MVA HTS cables and two 22.9kV 630A, 3000A SFCL in a KEPCO Grid in order to demonstrate its reliability and stable operation. This paper will present the technology for selecting appropriate site and its plan for installation & operating of 22.9kV HTS cables & SFCL in KEPCO Grid.

Investigation on the inductive and resistive fault current limiting HTS power cable

  • Lee, Sangyoon;Choi, Jongho;Kim, Dongmin;Kwon, Yonghyun;Kim, Seokho;Sim, Kideok;Cho, Jeonwook
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제16권2호
    • /
    • pp.59-63
    • /
    • 2014
  • HTS power cable bypass the fault current through the former to protect superconducting tapes. On the other hand, the fault current limiting (FCL) power cable can be considered to mitigate the fault current using its increased inductance and resistance. Using the increased resistance of the cable is similar to the conventional resistive fault current limiter. In case of HTS power cable, the magnetic field of HTS power cable is mostly shielded by the induced current on the shield layer during normal operation. However, quench occurs at the shield layer and its current is kept below its critical current at the fault condition. Consequently, the magnetic field starts to spread out and it generates additional inductive impedance of the cable. The inductive impedance can be enhanced more by installing materials of high magnetic susceptibility around the HTS power cable. It is a concept of SFCL power cable. In this paper, a sample SFCL power cable is suggested and experimental results are presented to investigate the effect of iron cover on the impedance generation. The tests results are analyzed to verify the generation of the inductive and resistive impedance. The analysis results suggest the possible applications of the SFCL power cable to reduce the fault current in a real grid.

22.9kV 초전도케이블/한류기의 국내 배전계통 적용을 위한 설계사양 고찰 (Specifications for Korean Power system application of 22.9kV HTS cable and FCL)

  • 이승렬;박종영;윤재영;양병모;이승엽;원영진;이병준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.266_267
    • /
    • 2009
  • 22.9kV HTS(High Temperature Superconducting) cable and SFCL(Superconducting Fault Current Limiter) will be installed to Icheon 154kV substation for real distribution power system operation in 2010. This paper proposes CLR (Current Limiting Resistance) specification of the SFCL and fault current condition fo the HTS cable for applying to Korean power system.

  • PDF

타입에 따른 무유도 권선형 코일의 한류 특성연구 및 자장해석 (A study on the current limiting characteristics and magnetic analysis of the non-inductively wound coil)

  • 장재영;박동근;장기성;나진배;김원철;정윤도;고태국
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제11권1호
    • /
    • pp.25-29
    • /
    • 2009
  • To reduce the power loss in normal state, non-inductively wound high temperature superconducting (HTS) coils are used for fault current limiter (FCL) application. Non-inductively wound coils can be classified into two types: solenoid type and pancake type. These two types have different electrical and thermal and mechanical characteristics due to their winding structure difference. This paper deals with the current limiting characteristics, magnetic field analysis of the two coils. Simulation using finite element method (FEM) was used to analyze the magnetic field distribution and inductance of the coils. Short circuit test using stabilizer-free coated conductor (CC) was also carried out. We can compare the characteristics of the two types of coil by using the data obtained from simulation and short circuit test. We confirmed the feasibility of FCL application by the analysis about the characteristics of non-inductively wound coil using CC.

DC Superconducting fault current limiter characteristic test with a DC circuit breaker

  • So, Jooyeong;Choi, Kyeongdal;Lee, Ji-kwang;Kim, Woo-Seok
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제23권2호
    • /
    • pp.19-23
    • /
    • 2021
  • We have studied the breaking system that combines a resistive superconducting fault current limiter (SFCL) and a DC circuit breaker for DC fault current. To verify the design of the 15 kV DC SFCL, which was driven from the previous work, a 500 V DC system was built and a scale-down SFCL were manufactured. The manufactured SFCL module was designed as a bifilar coil which is a structure that minimizes inductive reactance. The manufactured SFCL module has been experiment to verify characteristics of the current-limiting performance in the DC 500 V system. Also, the manufactured FCL module was combined with the DC circuit breaker to be experimented to analyze the breaking performance. As a result of the experiment, when SFCL was combined to the DC circuit breaker, the energy dissipation received by the DC circuit breaker was reduced by up to 84% compared to when the DC circuit breaker operates alone. We are preparing methods and experiments for the optimal method for much higher performance as a future work.

적층판으로 제작된 고온초전도 한류기에 발생한 국부적 열폭주 점에 대한 열응력 해석 (Thermal Stress Due to a Hot - Spot on the Laminated Plate in High Temperature Superconducting Fault Current Limiter)

  • 양경진;강기주
    • 대한기계학회논문집A
    • /
    • 제27권5호
    • /
    • pp.705-712
    • /
    • 2003
  • Analysis for the thermal stress distribution in the laminated plates containing a hot-spot(local heating region) is performed. It is assumed that the local heating region induces only mechanical stress by the thermal expansion but effect of the thermal conduction is neglected. The region is regarded equivalent to a homogeneous inclusion expanding in a laminated medium. As an example, Au/YBCO/Al$_2$O$_3$laminate which is often employed for High Temperature Superconducting Fault Current Limiter(HTS FCL) has been analyzed. Effects of heat input, thickness of each layer and the got spot size upon the stress distribution in the hot-spot have been investigated. For a constant heat generation into the hot-spot, as the thickness of the Al$_2$O$_3$substrate increases, the stress in the YBCO layer is peculiarly oscillated, and the curvature of laminate has a maximum at a certain thickness of the Al$_2$O$_3$.