• 제목/요약/키워드: HRV(Heat recovery ventilator)

검색결과 13건 처리시간 0.02초

공동주택용 폐열회수형 환기장치의 성능에 관한 측정 연구 (A Study on the Performance of Heat Recovery Ventilators for Apartment Houses)

  • 장현재;홍석진
    • 설비공학논문집
    • /
    • 제20권1호
    • /
    • pp.26-34
    • /
    • 2008
  • Heat recovery ventilator(HRV) is recommended to improve indoor air quarlity (IAQ) and energy conservation in apartment houses. Recently, in Korea, HRV is produced from many manufacturers. However, there have been not so many experiences to apply HRV in apartment houses and verification on the performance such as heat exchange efficiency, carry-over rate, internal leakage, etc. have not been carried out sufficiently. So in this study, fan performance, heat exchange efficiency, air leakage, internal exhaust leakage, external leakage and sound level of HRV were examined for selected HRV models under domestic and international standard. Results of performance test, there were need to improve latent heat exchange efficiency and sound level of HRV.

환기관점에서 본 열교환 환기유니트 (Consideration of Heat Recovery Ventilator from Ventilating Standpoint)

  • 송준원;강일경;김태희;신용섭;박재성;최원영
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.417-422
    • /
    • 2006
  • On trends of 'well-being', heat recovery ventilators(HRV) are recently installed in high rise buildings. HRV is not energy saving instrument but ventilating one. But many people have not been aware of the accurate fact. In this study, performances of HRV are tested under foreign and domestic standards. Especially air-tightness is measured three times by using gas concentration method and pressing equipment. Wet effective ventilating air volume is acquired by solving gas concentration equations. After research air-tightness and effective ventilating air volume must be more focused on than heat transfer efficiency to select the optimal HRV. Heat transfer efficiency must be adjusted by air-tightness results.

  • PDF

사무용 건물에서 전열교환 환기시스템과 일반공조기의 냉방에너지 비교분석에 관한 연구 (A Comparative Analysis on Cooling Energy of Heat Recovery Ventilator and Air Handling Unit in the Office Building)

  • 장지훈;김현수;어진선;이승복;김병선
    • KIEAE Journal
    • /
    • 제16권6호
    • /
    • pp.123-128
    • /
    • 2016
  • Purpose: In order to save the energy consumption of buildings, buildings have been constructed with high performance insulation or airtightness. However, high performance insulation or air tightness has led to a poor indoor air quality. Therefore, HRV(Heat Recovery Ventilator) has received attention to save the energy consumption and insure a good air quality. Because existing research is almost about the performance of HRV in residential buildings, This study analyzed the effect of HRV on cooling energy consumption in commercial office building. Method: This study was proceeded at commercial office building in In-cheon. In order to evaluate the energy consumption of HRV, this study proposed two methods: estimating energy consumption of the room installed AHU(Air Handling Unit) system; estimating energy consumption of the room installed HRV system. Therefore, comparison of two methods was proceeded to evaluate energy performance of each method. Result: As the result of comparison between rooms installed AHU and HRV, the experiment showed that energy consumption of the room installed HRV system is about 22% less than the room of AHU system. This conclusion is considered because the room installed HRV system have maintained temperature well at set point temperature $26^{\circ}C$.

학교 교실의 태양광발전 환기시스템 적용성 연구 (A Study on Application of a Heat Recovery Ventilator using Photovoltaic System in School)

  • 장용성;서승직;홍성희;유권종;박효순
    • 한국태양에너지학회 논문집
    • /
    • 제25권1호
    • /
    • pp.27-34
    • /
    • 2005
  • This study aims to evaluate application of a heat recovery ventilator(HRV) using photovoltaic(PV) system. To this end, we analyzed performance of a PV system, which it was evaluated by monthly power wattage and conversion efficiency according to design capacity of a HRV. The results of this study can be summarized as follows. (1) A conversion efficiency of the PCS was evaluated about 86% in rated power. (2) A maximum, minimum and average output power were respectively analyzed 49.2W, 47.3W, and 48.8W. (3) Total power wattage of 200W PV system was 211kW and it was 316kW in case of 300W PV system. (4) Insufficient electrical power of a duct and window type ventilation system was respectively calculated 133.5kW and 147.7kW.

KS, JIS 열교환 환기장치 실험규격의 민감도 분석 (Sensitivity Analysis on KS and JIS Standard for Heat Recovery Ventilator)

  • 이정재;임병찬;김환용
    • 설비공학논문집
    • /
    • 제17권11호
    • /
    • pp.998-1004
    • /
    • 2005
  • Recently natural ventilation rate is decreased due to the airtightness of apartment building. Therefore the use of heat recovery ventilator (HRV) has been greatly increased as an alternative method to supply fresh air and save energy in the building. In this research the experiment standard of HRV is compared between KS and JIS and the sensitivity analyses are experimented by both standards. Under cooling experiment condition indoor and outdoor wet-bulb temperature difference of JIS is 2 to 3 times higher than that of KS. It shows that the efficiency measurement of HRV by KS is expected to have greater sensitivity than by JIS and thus accurate measurement of web-bulb temperature is required. The experimental results provide that the efficiency of thermal exchange is resemblance to each others between KS and JIS. Under cooling experiment condition the efficiency of humidity exchange by KS presents higher than by JIS, however, under heating experiment condition the efficiency by KS shows lower than by JIS, reversely.

열회수형 환기장치의 운전조건에 따른 경제성 평가에 관한 연구 (A Cost Analysis of the Heat Recovery Ventilator under Various Condition)

  • 강태욱;고재윤
    • 한국태양에너지학회 논문집
    • /
    • 제26권1호
    • /
    • pp.21-28
    • /
    • 2006
  • Changes in building construction methods and repairing of older buildings have reduced infiltration rate. Synthetic materials, release airborne particles and uneven healthy odor are increased. For preventing pollutants introduce fresh outdoor air into the building, simply letting fresh outdoor air into building, however, Is not a cost-effective way to ventilation. When additional ventilation is added to an existing HVAC system, the heating and cooling equipment, often cannot handle the increased load. A HRV provides a way to minimize in energy costs while introducing fresh air to a building. In this study, the economical research of HRV, made of three types of materials, are conducted. Heat recovering characteristics are studied at seasonal outdoor air conditions based on the outdoor air property condition at, Seoul in 2002. As a results, the average sensible effectiveness is 0.75 in the sensible heat exchanger and average total effectiveness is 0.65 in the total heat exchanger. The pay back period of the sensible heat exchangers are $3.2{\sim}3.5$ year and it of total heat exchanger is 2.2 years.

공동주택 열교환기의 성능 및 에너지소비 특성 평가 (Evaluation of the Performance and the Energy Consumption Characteristics of Heat Recovery Ventilators in Apartments)

  • 김상민;박병윤;손장열
    • 설비공학논문집
    • /
    • 제17권5호
    • /
    • pp.496-504
    • /
    • 2005
  • Heat recovery ventilators (HRV) are developed in order to satisfy both energy conservation and the improvement of indoor air quality as an alternative for current natural ventilation systems and local mechanical ventilation systems in kitchens and bathrooms. However, the performance of HRV system and the consequent effect on heating and cooling energy saving have not been sufficiently validated quantitatively in case of the application of HRVs in real residences. In this study, field measurement and computer simulation were conducted in both summer and winter period to assess the performance and validate energy conservation effect of HRVs. Under the Korea weather condition, average total heat recovery efficiency was $27\%$ in summer and $46\%$ in winter. According to the field measurement, HRV system can save the energy by $10\%$ in summer and 15$\%$ in winter. Furthermore, according to the simulation assessment, HRV system can save the energy by $17\%$ in summer and $17\%$ in winter.

폐열회수환기를 위한 열교환장치의 경제성 평가 (An economic evaluation of heat exchanger for heat recovery ventilation)

  • 박용효;이상범
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2008년도 추계 학술논문 발표대회
    • /
    • pp.241-244
    • /
    • 2008
  • Recently, The high Air-Tightness and high heat insulation for building construction cause a ventilation air volume deficiency. Also, Worldwide high energy price is strongly urging to economize the air conditioning energy. Therefore Heat Recovery Ventilation is used for the satisfaction of ventilation air volume and building energy saving. Accordingly, this study dose the heat exchanger performance evaluation and economic efficiency evaluation of Heat Recovery Ventilation. And, we wish to make a basic study about HRV System application of HVAC System and Multi System Air-conditioning.

  • PDF

CFD를 이용한 열회수형 환기장치 운전에 따른 혹한기 공동주택의 실내 열환경 검토 (A Study of the Indoor Thermal Environment in Apartment Buildings in Freezing Weather Operation of Heat Recovery Ventilator by CFD Simulation)

  • 김창연;박종일;김동규;신병환;금종수
    • 설비공학논문집
    • /
    • 제27권6호
    • /
    • pp.293-299
    • /
    • 2015
  • In Korea, it is the law that an apartment building which consists of over 100 households must have a ventilation system installed, either natural or mechanical. The heat recovery ventilator (HRV) is great way to reduce energy consumption. In this research we confirmed that based on site's construction plan and existing diffuser form, performed purpose CFD which simulates operation in temperatures below $-5^{\circ}C$ to circumstances of installation of an HRV in an apartment. As a result of this research we found that when the diffuser's aperture area was adjusted, the distribution of air temperature and residence time of air was more equally distributed and air temperature was higher, compared to when the diffuser has an identical aperture area. We also found that we are able to increase even more air temperature and air distribution of air temperature and residence time of air was even more equally distributed when run in parallel with a splitter damper.

폐열회수 환기유닛의 인증시험 방법에 대한 오차분석 (Uncertainty Analysis of Test Method for Heat Recovery Ventilators)

  • 한화택;추연복
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.423-428
    • /
    • 2006
  • Twenty nine HRV models have been tested for last two years since the attestation system has been started by KARSE. It is the objective of the present study to analyze the performance test results. Uncertainty analysis has been conducted to find the effects of measured variables on the uncertainties of test results. The uncertainty of enthalpy is found to be affected by the uncertainty of wet bulb temperature significantly, but not by that of dry bulb temperature for the present range of parameters. The uncertainty of effective enthalpy efficiency is calculated to be 6%P for the cooling condition, and 3%P for the heating condition approximately. In order to reduce the uncertainty of the test results, the uncertainty of wet bulb temperature should be minimized and the indoor/outdoor test conditions should be modified so as to increase the enthalpy difference.

  • PDF