A Recursive Distance Relaying Algorithm Immune to Fault Resistance (고장저항의 영향을 최소화한 순환형 거리계전 알고리즘)

  • Ahn, Yong-Jin;Kang, Sang-Hee;Lee, Seung-Jae
    • Proceedings of the KIEE Conference
    • /
    • 2001.05a
    • /
    • pp.259-261
    • /
    • 2001
  • An accurate digital distance relaying algorithm which is immune to the combined reactance effect of the fault resistance and the load current is proposed. The algorithm can estimate adaptively the impedance to a fault point independent of the fault resistance. To compensate the apparent impedance, this algorithm uses iteratively the angle of an impedance deviation vector improved step by step. The impedance correction algorithm for ground faults uses a current distribution factor to compensate mutual coupling effect.

  • PDF

An Improved Algorithm of Fault Indicator Generation of FRTU in Distribution Automation System (배전자동화시스템에서 전류방향성을 이용한 단말장치의 고장표시 오류 개선 방법)

  • Seo, Jung-Soo;Kim, Hyung-Seung;Lim, Seong-Il;Choi, Myeon-Song;Lee, Seung-Jae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.10
    • /
    • pp.1354-1363
    • /
    • 2014
  • In this paper, an improved method of fault indicator generation algorithm in FRTUs is proposed for the present Distribution Automation System. In order to find fault area, correct FI information should be generated. But when a single line-to-ground fault occurs, FI information is generated in downside of the fault in some circumstance because existing FI algorithm considers only magnitude. It is found that the upside fault current direction if different from the downside fault current direction. Therefore, in order to prevent to generate the wrong fault indication information for FRTU at the downside of the fault, an improved fault indication generation method is developed. Not only the basic conditions are taken into account, but also the directions from the angle difference between zero and positive sequence currents are considered to generated the fault indication information. In case study, the proposed method has been testified and shown the reasonability in generating correct the fault indication information, for many kinds of faults according to conditions.

New Fault Location Algorithms by Direct Analysis of Three-Phase Circuit Using Matrix Inverse Lemma for Unbalanced Distribution Power Systems

  • Park, Myeon-Song;Lee, Seung-Jae
    • KIEE International Transactions on Power Engineering
    • /
    • v.3A no.2
    • /
    • pp.79-84
    • /
    • 2003
  • Unbalanced systems, such as distribution systems, have difficulties in fault locations due to single-phase laterals and loads. This paper proposes new fault locations developed by the direct three-phase circuit analysis algorithms using matrix inverse lemma for the line-to-ground fault case and the line-to-line fault case in unbalanced systems. The fault location for balanced systems has been studied using the current distribution factor, by a conventional symmetrical transformation, but that for unbalanced systems has not been investigated due to their high complexity. The proposed algorithms overcome the limit of the conventional algorithm using the conventional symmetrical transformation, which requires the balanced system and are applicable to any power system but are particularly useful for unbalanced distribution systems. Their effectiveness has been proven through many EMTP simulations.

An Improved Method of Fault Indication Information Using Filtering Algorithm (배전자동화 중앙장치에서 필터링 알고리즘을 통한 고장표시 오류 개선방법)

  • Seo, Jung-Soo;Kim, Hyung-Seung;Lim, Sung-Il;Choi, Myeon-Song;Lee, Seung-Jae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.64 no.10
    • /
    • pp.1418-1425
    • /
    • 2015
  • In this paper, an filtering method of FI(Fault Indication) information generated by FRTU(Feeder Remote Terminal Unit)s is proposed for the present DAS(Distribution Automation System). In order to find fault area, correct FI information should be generated. But when a single line-to-ground fault occurs, FI information is generated in downside of the fault in some circumstance because existing FI algorithm considers only magnitude. These wrong FI information can be removed by changing existing algorithm. An improved algorithm considers both the direction of zero-sequence current and the phase of three-phase current&voltage. But many FRTUs are distributed in DAS and Changing the algorithm all of FRTU will spend a lot of time and cost. On the other hand, an filtering algorithm proposed in this paper can substitute for it. The filtering algorithm also considers both the direction of zero-sequence current and the phase of three-phase current&voltage. In case study, the proposed method has been shown the reasonability in filtering the fault indication information.

Surface Potential Distribution according to Grounding Electrode Shapes (접지전극 형상에 따른 대지표면전위분포)

  • Baek, Young-Hwan;Lee, Bok-Hee;Li, Feng;Yang, Soon-Man;Lee, Kyu-Sun
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.1360-1361
    • /
    • 2008
  • This paper presents the surface potential rise distribution near grounding electrodes produced by ground fault currents. The small-scale model with the foundation pedestal in hemispherical tank was used to simulate the ground fault condition of the electrical installations for street lamps. When entering the fault current through the test ground electrode, surface potential rise, potential gradient, touch and step voltages for different grounding electrode shapes were measured, and the results obtained were discussed.

  • PDF

A Study on the Improvement of Fault Detection Capability for Fault Indicator using Fuzzy Clustering and Neural Network (퍼지클러스터링 기법과 신경회로망을 이용한 고장표시기의 고장검출 능력 개선에 관한 연구)

  • Hong, Dae-Seung;Yim, Hwa-Young
    • Journal of the Korean Institute of Intelligent Systems
    • /
    • v.17 no.3
    • /
    • pp.374-379
    • /
    • 2007
  • This paper focuses on the improvement of fault detection algorithm in FRTU(feeder remote terminal unit) on the feeder of distribution power system. FRTU is applied to fault detection schemes for phase fault and ground fault. Especially, cold load pickup and inrush restraint functions distinguish the fault current from the normal load current. FRTU shows FI(Fault Indicator) when the fault current is over pickup value or inrush current. STFT(Short Time Fourier Transform) analysis provides the frequency and time Information. FCM(Fuzzy C-Mean clustering) algorithm extracts characteristics of harmonics. The neural network system as a fault detector was trained to distinguish the inruih current from the fault status by a gradient descent method. In this paper, fault detection is improved by using FCM and neural network. The result data were measured in actual 22.9kV distribution power system.

High Impedance Fault Detection on 22.9kV Multigrounded Distribution System (22.9kV 이중접지 배전선로 고저항 지락 검출)

  • Park, Young-Moon;Lee, Ki-Won;Lim, Ju-Il;Yoon, Man-Chul;Yoo, Myeong-Ho
    • Proceedings of the KIEE Conference
    • /
    • 1987.11a
    • /
    • pp.463-468
    • /
    • 1987
  • In this paper, a high impedance fault detection on 22.9kV multigrounded distribution system that has been very difficult by any existing conventional protective relaying systems is studied. Because the fault current is very low, it cannot be distinguished from neutral current caused by load unvalanced on multigrounded distribution system. We developed the new and best algorithms of high impedance ground fault detection. This algorithms are 'the even order power method, even order ratio method', 'and even order ratio varience method'. Using this algorithms, a detection device for high impedance faults is constructed and tested in the laboratory. And continually, it is installed and has been tested in KEPCO substations.

  • PDF

Analysis of effects of OCR in operation mode during fault ocuurs in Distribution System (배전계통 내 고장발생시 운전모드가 과전류계전기에 미치는 영향 분석)

  • Kim, Yong-Hwan;Rhee, Sang-Bong;Kim, Chul-Hwan
    • Proceedings of the KIEE Conference
    • /
    • 2015.07a
    • /
    • pp.563-564
    • /
    • 2015
  • Recently, distributed generation using renewable energy resources have increased due to the limitation of conventional energy. To utilize these energy source effectively, a method of applying the energy storage system(ESS) in distribution system has been considered. In this paper, we simulated the one line-to-ground fault in power system with ESS. Based on these simulations, we analyzed the effect on Over Current Relay(OCR) operation. As a result, ESS operation modes result fault current fluctuation. Thus, OCR need to reset the pick up current. This paper analyze effect of ESS in distribution system according to OCR setting by using ElectroMagnetic Transient Program(EMTP).

  • PDF

Restudy of Fault Current Distribution Ratio with Grounding Type of Normal Joint Box in Underground Transmission Systems (지중송전계통에서 보통접속함의 접지방식에 따른 고장전류분류율 재검토)

  • Hong, D.S.;Kang, J.W.;Jang, T.I.;Kim, H.H.;Yoon, H.H.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.500-502
    • /
    • 2002
  • Receltly, Underground transmission system is getting increased. Therefore the design of grounding system becomes very important to discharge overcurrent of lightning and fault through earth and reduce sheath induced voltage and sheath circulation current. This paper describes fault current distribution ratio for grounding line with grounding types of normal joint box and sheath grounding resistor at line-to-ground fault of cable.

  • PDF

Ungrounded System Fault Section Detection Method by Comparison of Phase Angle of Zero-Sequence Current

  • Yang, Xia;Choi, Myeon-Song;Lee, Seung-Jae;Lim, Il-Hyung;Lim, Seong-Il
    • Journal of Electrical Engineering and Technology
    • /
    • v.3 no.4
    • /
    • pp.484-490
    • /
    • 2008
  • In this paper, an integrated fault section detection and isolation strategy is proposed based on the application of the Distribution Automation System(DAS) utilizing advanced IT and communication technologies. The Feeder Remote Terminal Unit(FRTU) has been widely used to collect data in the Korean distribution system. The achieved data is adopted in this method for detecting multiple fault types. Especially in the case of single phase-to-ground fault, the fault section is detected by comparison of the zero-sequence current phase angle. The test results have verified the effectiveness of the proposed method in a radial distribution system through extensive simulations in Matlab/Simulink. Furthermore, a communication-based demo system identical to the simulation model has been developed, and it can be applied as an online monitoring and control program for fault section detection and isolation.