Recently, distributed generation using renewable energy resources have increased due to the limitation of conventional energy. To utilize these energy source effectively, a method of applying the energy storage system(ESS) in distribution system has been considered. In this paper, we simulated the one line-to-ground fault in power system with ESS. Based on these simulations, we analyzed the effect on Over Current Relay(OCR) operation. As a result, ESS operation modes result fault current fluctuation. Thus, OCR need to reset the pick up current. This paper analyze effect of ESS in distribution system according to OCR setting by using ElectroMagnetic Transient Program(EMTP).