가스절연개폐기에서 용량성 전압프로브를 이용한 부분방전의 측정 (Partial Discharge Measurement by a Capacitive Voltage Probe in a Gas Insulated Switch)

  • 길경석;박대원;최수연;김일권;박찬용
    • 한국전기전자재료학회논문지
    • /
    • 제21권1호
    • /
    • pp.85-89
    • /
    • 2008
  • An objective of this paper is to develop a partial discharge (PD) measurement device for monitoring gas insulated switches installed in power distribution system. A capacitive voltage probe was studied and designed to detect PD pulse without an electrical connection. The PD measurement device consists of the capacitive voltage probe attached outside of a bushing, a coupling network which attenuates AC voltage by 270 dB, and a low noise amplifier with the gain of 40 dB in ranges of 500 kHz${\sim}$20 MHz. The sensitivity of the prototype device calculated by a calibrator was 1.98 m V /pc. An application experiment was carried out in a 25.8 kV gas insulated switch and the peak pulse of 76.7 pC was detected. From the experimental results, it is expected that the PD measurement device can be applied to online monitoring system of gas insulated switches.

친환경 가스개폐기 개폐성능 향상을 위한 유동해석 및 실험 (Fluid Dynamics Analysis and Experimental Trial to Improve the Switching Performance of Eco-friendly Gas Insulated Switch)

  • 유련;안길영;김영근;조해용
    • 한국기계가공학회지
    • /
    • 제21권9호
    • /
    • pp.42-49
    • /
    • 2022
  • An underground electric switch is a high-voltage switch used in distribution network systems for a reliable power supply. Many studies are being conducted to expand the switch to use an eco-friendly gas using dry air instead of SF6 gas to reduce greenhouse gas emissions. In this study, a flow analysis model was established to improve the performance of an eco-friendly gas switch. The results were compared and reviewed through experiments. For the optimal arc grid design applied to the switch, the flow characteristics based on the flow path configuration and the changes in arcing time for each configuration were compared. Flow analysis can predict the switch flow distribution, and a comparative review of the flow path configurations of various methods is possible.

특고압 가스 절연 부하 개폐기의 통합형 대전력 시험 방법 및 회로 구성에 관한 연구 (A Study on the Construction of Test circuit and Unification of Experiment Method for High Voltage Gas-insulated Load Switch using High Power Testing System)

  • 정흥수;김민영;김준석
    • 조명전기설비학회논문지
    • /
    • 제22권12호
    • /
    • pp.36-46
    • /
    • 2008
  • 본 논문은 대전력시험설비를 이용한 특고압 가스 절연 부하 개폐기의 대전력 시험회로의 구성과 통합형 시험 방법에 관하여 연구하였다. 대전력시험설비는 전기기기의 전기적 및 기계적인 성능을 검증하는 설비로서 단락발전기, 보호차단기, 투입스위치, 임피던스, 고압변압기, 저압변압기, 측정 및 보호시스템 등으로 구성되며, 이 시스템을 이용하여 단시간전류시험, 전류개폐용량시험, 단락투입 및 차단시험 등을 실시한다. 특고압 가스 절연 부하 개폐기의 규격으로는 국내 배전계통에 적용되는 ES(한국전력공사 표준규격) 5925-0002가 있으며, 국제 규격으로는 IEC 60265-1, 62271-1 및 IEEE C 37.74 등이 있다. 본 논문에서는 여러 규격에 각각 규정되어 있는 시험 절차, 시험회로 구성 및 시험 방법 등을 통합하여 600[MVA]급 대전력 시험설비에 적용하였다.

가스절연개폐기에서 용량성 전압프로브를 이용한 부분방전 측정 (Partial Discharge Measurement by a Capacitive Voltage Probe in a Gas Insulated Switch)

  • 최수연;박찬용;박대원;김일권;길경석
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 추계학술대회 논문집
    • /
    • pp.476-477
    • /
    • 2007
  • This paper described the partial discharge (PD) measurement techniques for diagnosing gas-insulated switches in overhead power distribution system. A capacitive voltage probe to detect PD pulse was designed and fixed on the surface of a bushing. We also designed a coupling network to attenuate AC voltage by 270 dB, and a low-noise amplifier having the gain of 40 dB and 500 kHz~20 MHz 3 dB. From the calibration, it was calculated that the sensitivity of the measurement system was 0.94mV/pC. In the application experiment, we could measure a PD pulse of 45 pC.

  • PDF

단거리송전선에서 투입저항이 없는 차단기적용에 관한 연구 (The Study on Application of Circuit Breaker without Closing Resistor in Short Transmission Line)

  • 김정배;정영환;송원표
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제53권1호
    • /
    • pp.31-37
    • /
    • 2004
  • In this paper, the analysis result of the switching surge in substation including GIS(Gas Insulated Switchgear) has been described using the EMTP(Electro Magnetic Transient Program) program. After performing the modeling of the input data, we have reviewed the energization overvoltages of GCB(Gas Circuit Breaker) without closing resistor in 345kV network, according to the conditions of simultaneously operating switch and statistically operating switch. Firstly, it can be known that the energization overvoltage of single line is higher than that of parallel energized line. Secondly, the maximum energization overvoltage obtained in statistics switch is higher than one in simultaneous switch. From these results, it can be known that the phase-to-earth energization overvoltages of $\alpha$-$\beta$ section are less than 2.2 p.u when closing resistor is eliminated. Therefore, it is possible to consider the circuit breaker eliminated the closing resistor in $\alpha$-$\beta$ section.

배전용 가스개폐기의 내 오손 성능향상 대책 (Anti-Contamination Capability of Gas Insulated Switch for Distribution Line)

  • 김주용;송일근;김찬영;한재홍
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 추계학술대회 논문집 학회본부 C
    • /
    • pp.758-760
    • /
    • 1998
  • This paper provides the results of performance investigation of gas insulated switches(G/S) for distribution power system. In order to investigate anti-contamination capability of G/S we carried out electrical tests and material analysis on the body of G/S and it's accessories. Through this experiment we found out the lead cable of G/S had not anti-contamination capability and G/S had insufficient interval between each phase. In order to improve the performance of G/S for heavy contamination area it is indispensable to replace the lead cable to the new cable which has anti-contamination ability.

  • PDF

APG 주형방식을 이용한 가스절연개폐기용 절연 스페이서 제작에 관한 연구 (A Study on the Manufacture of Gas Insulated Switchgear Spacer Using APG Molding Process)

  • 이찬용;배재성;조한구;이상묵;이재형
    • 한국전기전자재료학회논문지
    • /
    • 제35권4호
    • /
    • pp.386-391
    • /
    • 2022
  • The gas insulation switchgear, which is a device for protecting a power system, cannot be supported by the insulation gas itself in a charge unit stored in a metal container. Therefore, molding technology is required to manufacture a gas insulation switch spacer. The APG method injection molding simulation was performed by applying the variables obtained through the physical properties of an epoxy composite used for manufacturing an insulating spacer to a moldflow software. After varying the temperature conditions of heater in the simulation, the thermal characteristics and the degree of hardening of the spacer were analyzed, based on which the optimum process conditions are presented.

국산 배전자동화시스템 구성설비의 보유기능 및 특성 (The Functions and Characteristics of Distribution Automation System Components)

  • 하복남;박상만;장정태;최태일;김호용;오상기
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 B
    • /
    • pp.899-901
    • /
    • 1996
  • KODAS is made up of the Central Control System(CCS) as four Vax workstations linked up with LAN networks, six Substation Communication Control Units(SCCU) installed in substation to transfer data, 125 Feeder Remote Units(FRU) located at the lower position of automated switch to provide the information of Fault Indicator(FI) and three kinds of automated switches to have remote control functions such as SF6 gas feeder automation switch, recloser and gas insulated pad mountes switchgear for under ground line. This paper explains the functions and characteristics in detail about each devices mentioned above.

  • PDF

송변전계통 전력개폐설비의 고장 실태조사 연구 (Analysis on Fault for Switching Devices in Transmission & Substation System)

  • 이봉희;이희성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 A
    • /
    • pp.415-417
    • /
    • 1999
  • Recently, Reliability of switching devices for transmission & substation system is very important. Therefore, We have investigated fault trend of switching devices from 1982 to 1998 This paper presents fault analysis on Circuit Breakers, Disconnecting Switch, Gas Insulated Switchgear, etc. Thus, this paper will help improve design, manufacture, construction technology and maintenance method.

  • PDF