• Title/Summary/Keyword: Frost thickness

Search Result 76, Processing Time 0.026 seconds

Growth of frost formed on heat exchanger fins (열교환기 휜에서의 서리 성장)

  • An, Won-Jun;Kim, Jung-Soo;Lee, Kwan-Soo
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.256-261
    • /
    • 2008
  • In this study, frost behavior on two dimensional fins of a heat exchanger was experimentally investigated. Temperature distribution on a 2-D fin surface and frost properties were measured in the directions perpendicular to and parallel to airflow. The results indicated that the temperature gradient in the direction perpendicular to airflow was large because of fin heat conduction, while that in the direction parallel to airflow was very small. Frost thickness in the airflow direction decreased from the leading edge towards the trailing edge of the fin due to leading edge effect. The reduction rate of frost thickness in the airflow direction, however, was very small compared with that in the direction perpendicular to the airflow, as affected by the temperature distribution.

  • PDF

A Computer Simulation for Performance Prediction of Fin-Tube Heat Exchanger under Frosting Conditions (착상조건 하에서 핀-관 열교환기의 성능예측을 위한 컴퓨터 시뮬레이션)

  • Lee, K.S.;Pak, H.Y.;Lee, W.Y.;Lee, T.H.;Lee, S.Y.;Lee, M.R.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.7 no.1
    • /
    • pp.161-170
    • /
    • 1995
  • This study is concerned with the numerical analysis of performance on fin-tube heat exchanger under frosting condition. In this work, tube-by-tube method using LMED is employed. The present results are compared with O'Neal's experimental and numerical results. A standard evaporator model with 2rows-2columns is selected to investigate the effects of the various parameters such as fin pitch, air flow velocity, and humidity. The results show that frost thickness and the amount of frost per unit area decrease as fin-pitch becomes narrower. In the meantime, frost thickness and accumulation rate increase with higher inlet air humidity. It is shown that heat transfer rate increases during 30minutes and then it decreases. Heat transfer rate and the amount of frost increase with air velocity, however frost thickness does not increase over a certain velocity.

  • PDF

The Effect of Environmental Parameters on Frost Formation on a Horizontal Cylinder (수평 실린더에서의 서리 생성에 대한 환경 변수들의 영향)

  • Lee, Yun-Bin;Ryu, In-Sang;No, Seung-Tak
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.26 no.2
    • /
    • pp.253-260
    • /
    • 2002
  • It is known that frost formation on surfaces of the heat exchanger seriously affects the performance of the refrigeration system. Accordingly, defrosting should follow, and effective defrosting is possible only when both analytic tools and comprehensive experimental data on frost formation are assailable. An experimental investigation was undertaken to characterize the effect of environmental parameters on frost formation on a horizontal cylinder in cross uniform flow. Several experiments were carried out with various environmental parameters such as inlet air temperature, inlet air humidity, air velocity and cooling surface temperature. Frost thickness, mass, surface temperature and cylinder inner and outer temperature were measured at front and rear positions of the cylinder. Thickness, mass, density, and effective thermal conductivity of the frost layer were obtained from measured data and effects of environmental parameters on the frost formation were analyzed. Data from experiments were correlated using dimensionless variables.

A Characteristics Study on the Visualization and Heat Transfer of the Frost Formation Structure Variation by Control Plate Surface Temperature (표면온도 제어에 의한 착상층 구조변화의 가시화 및 열전달 특성 연구)

  • Kim Kyung-Chun;Ko Choon-Sik;Jeong Jae-Hong;Ko Young-Hwan;Shin Jong-min
    • 한국가시화정보학회:학술대회논문집
    • /
    • 2002.11a
    • /
    • pp.55-58
    • /
    • 2002
  • To control the frost formation, a temperature variation of the cooling plate and characteristics on hydrophilic and hydrophobic surfaces was attempted. As a temperature variation of the cooling plate, being closely related to the frost layer density of frost layer is found to be affected by the melting process inside the frost layer during the heating period. At characteristics on surface, completely different structures of frost are appeared in the initial stage of frost formation due to the difference in surface conditions, while those effects are vanished with time. It is found that the frost thickness, density and heat flux characteristics are closely associated with the frost structure.

  • PDF

Frost Behavior on a One-Dimensional Fin Considering Heat Conduction of Heat Exchanger Fins (열교환기 휜의 열전도를 고려한 1차원 휜에서의 착상 거동)

  • Kim, Jung-Soo;Kang, Soo-Jin;Lee, Kwan-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.11
    • /
    • pp.727-732
    • /
    • 2008
  • This paper presents a mathematical model to predict the behavior of frost formed on an one-dimensional fin of heat exchanger, considering fin heat conduction under frosting conditions. The computational domain consists of air-side, the frost layer, and fin region, and they are coupled to the frost layer. The frost behavior is more accurately predicted with fin heat conduction considered (Case A) than with constant fin surface temperature assumed (Case B). The results indicate that for Case B, the frost thickness and heat transfer are overpredicted in most regions of the fin, as compared with those for Case A. In addition, for Case A, the maximum frost thickness varies little with the fin length variations, and the extension of the fin length after 30mm contributes insignificantly to heat transfer.

Evaluation of Ground Water Level Effect on Frost Heaving in Road Pavements (도로 포장체에서 동상에 대한 지하수위 영향 평가)

  • Kweon, Gichul;Lee, Jaehoan
    • International Journal of Highway Engineering
    • /
    • v.15 no.1
    • /
    • pp.47-56
    • /
    • 2013
  • PURPOSES: This study is to evaluate a ground water level effect on frost heaving in road pavements. METHODS: The effects of water table on frost heaving in pavement systems were evaluated from the mechanical analysis using FROST program. The input parameters and boundary conditions were determined by considering climates, pavement sections, and material properties specially subgrade soil types in Korea. RESULTS: When the water table located above the freezing depth, amount of frost heaving caused by freezing the water in pavement itself was big enough to damage in pavement system, although pavement system consists of fully non-frost-susceptible materials with sufficient thickness of anti-freezing layer. The amount of frost heaving was decreased rapidly with increasing the distance between the water table and freezing depth. CONCLUSIONS: It was concluded that there is no engineering problems related with frost heaving in practical sense when the distance between freezing depth and water table is over 1.5m for having subgrade soils less than 50% of #200 sieve passing to meet specification on quality control in Korea.

Effects of Humidity and Velocity on Frost Distribution Characteristics of Humid Air Flow on Cold Surfaces (차가운 표면위에서의 습공기 유동의 습도 및 속도가 착상분포 특성에 미치는 영향)

  • Kwon Jeong-Tae;Rew Keun-Ho;Lim Hyo-Jae;Han Ji-Won;Kwon Young Chul
    • Journal of Energy Engineering
    • /
    • v.14 no.4 s.44
    • /
    • pp.213-218
    • /
    • 2005
  • In order to understand the heat and mass transfer characteristics of humid airflow in frosting conditions, a flat plate of aluminum with cooling modules located in the central part of the plate was used. A microscope system (resolution of 0.05 mm) was used for the measurement of local thickness of frost at seven points along the plate in the flow direction. For the total mass of frost at each test operation, an electronic balance (resolution of 1 mg) was used. The local frost thickness distributions far various test conditions were presented along with the frost mass data measured at the given operating times. The effect of humidity and velocity of humid air on frosting were analyzed.

Numerical Study of Performance Variation Under Frost and Non-frost Condition of Refrigerating System in the Refrigerator Truck (냉동탑차용 냉장시스템의 착상 및 무착상 상태에서의 성능변화에 관한 해석적 연구)

  • Kim, Sang-Hun;Myung, Chi-Wook;Cho, Hong-Hyun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.11
    • /
    • pp.733-740
    • /
    • 2011
  • To analyze the cooling performance in the refrigerator truck according to frost growth, the analytical model of refrigeration system was developed under frost and non-frost condition using EES. The system performance was analyzed with outdoor temperature, storage temperature, outdoor front air velocity and compressor speed in order to investigate the system performance characteristics with operating conditions. Besides, the system performance under frost condition was compared with that under non-frost condition. As a result, the frost thickness was 0.9 mm when the refrigerating capacity of frost condition was decreased by 30%. The maximum of the system COP was shown at compressor speed of 1500 rpm for non-frost and frost condition, simultaneously. The performance under frost condition was more sensitive to the operating condition compared to that under non-frost condition.

Early Frost Damage and Diagnose of Damage Depth Due to Early Frost Damage of the Concrete According to the Thickness of Members (부재 두께 변화에 따른 콘크리트의 초기동해 특성 분석 및 깊이진단)

  • Kim, Tae-Woo;Han, Min-Cheol
    • Journal of the Korea Institute of Building Construction
    • /
    • v.19 no.2
    • /
    • pp.131-138
    • /
    • 2019
  • Recently, there are many structures exposed to severe outdoor environments, which results in rapid degradation of durability of the concrete structures. there can be rapid deterioration of the concrete structures from early frost damage due to the insufficient curing in low outdoor temperature condition. The objective of this study is to investigate the effect of thickness change conditions and binding material on early frost damage depth of the concrete exposed to cold weather in winter, and is to clearly assess damage depth of the concrete structure due to early frost damage. Specimens with 300x300x(150, 200, 250, 300mm) were prepared. OPC and OPC+FA+BS were adopted for binders. Test results indicate that the depth of the early frost damage was deeper with the decrease of thickness of members. The brightness of specimens were reduced when the member thickness was thinner. When determining the depth of early frost damage, it can be distinguished into dark color and relatively bright color when dried for approximately 30 minutes in the indoors of $20^{\circ}C$ in temperature and 60% in relative humidity after submerging in water for 24 hours. The dark colored part can be determined easily when measured with vernier calipers.

An Analysis for Predicting the Thermal Performance of Fin-Tube Heat Exchanger under Frosting Condition (착상시 핀-관 열교환기의 열적 성능 예측을 위한 해석)

  • Lee, T.H.;Lee, K.S.;Kim, W.S.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.8 no.2
    • /
    • pp.299-306
    • /
    • 1996
  • This work presents an analytical model, so called modified LMTD method, to predict the thermal performance of finned-tube heat exchanger under frosting conditions. In this model, the total heat transfer coefficient and effective thermal conductivity of the frost layer were defined as a function of frost surface temperature. The surface temperature of the frost layer formed on the heat exchanger was calculated through the analysis of the heat and mass transfer process in the air and frost layer. To examine the validity of this analytical model, the computed results from the present model, such as heat transfer rate, frost mass and thickness of frost, were compared with the ones of the expermental work and LMED method.

  • PDF