A Computer Simulation for Performance Prediction of Fin-Tube Heat Exchanger under Frosting Conditions

착상조건 하에서 핀-관 열교환기의 성능예측을 위한 컴퓨터 시뮬레이션

  • Published : 1995.02.01

Abstract

This study is concerned with the numerical analysis of performance on fin-tube heat exchanger under frosting condition. In this work, tube-by-tube method using LMED is employed. The present results are compared with O'Neal's experimental and numerical results. A standard evaporator model with 2rows-2columns is selected to investigate the effects of the various parameters such as fin pitch, air flow velocity, and humidity. The results show that frost thickness and the amount of frost per unit area decrease as fin-pitch becomes narrower. In the meantime, frost thickness and accumulation rate increase with higher inlet air humidity. It is shown that heat transfer rate increases during 30minutes and then it decreases. Heat transfer rate and the amount of frost increase with air velocity, however frost thickness does not increase over a certain velocity.

Keywords