• Title/Summary/Keyword: Fire Safety Design

Search Result 676, Processing Time 0.026 seconds

A Study on the Critical Safety Management Buildings and factors by Analyzing the Actual State of Building Safety Management (건축물 안전관리 실태분석을 통한 중점안전관리 대상 및 요소 설정에 관한 연구)

  • Kim, Eun-Hee
    • Journal of the Architectural Institute of Korea Planning & Design
    • /
    • v.35 no.4
    • /
    • pp.37-44
    • /
    • 2019
  • According to the statistical surveys and studies, insufficient maintenance in the use of existing buildings caused fire and collapse accidents. In this respect, I analyzed the data managed by the current building maintenance and inspection system to find out the actual state of safety management and proposed two significant results. First, regarding the state of the buildings, the safety management status of the small-sized ones, where 20 years or more passed after construction, is the worst and a priority improvement plan is required. Second, there are eight deeply concerning factors for the fire incidents and collapse accidents of buildings. In the order of high risk, these factors are structural strength (seismic design), exterior wall finishing material, basement floor, interior finishing materials, other evacuation facilities, corridors stairs entrances, rooftop, fire partition. We need to have more special designs and management plans regarding high-risk factors as a system to prevent accidents in the building.

Cable Functional Failure Temperature Evaluation of Cable Exposed to the Fire of Nuclear Power Plant (원자력발전소 케이블 노출 화재 시 기능상실온도 분석)

  • Lim, Hyuk-Soon;Bae, Yeon-Kyoung;Chi, Moon-Goo
    • Fire Science and Engineering
    • /
    • v.26 no.1
    • /
    • pp.10-15
    • /
    • 2012
  • The fire event occurred in fire proof zone often causes serious electrical problems such as shorts, ground faults, or open circuits in nuclear power plants. These would be directed to the loss of safe shutdown capabilities performed by safety related systems and equipments. The fire event can treat the basic design principle that safety systems should keep their functions with redundancy and independency. In case of a cable fire, operators can not perform their mission properly and can misjudge the situation because of spurious operation, wrong indication or instrument. These would deteriorate the plant capabilities of safety shutdown and make disastrous conditions. In this paper, investigation and cause analysis of cable fire in Nuclear Power Plant, we described the cable fire temperature and functional failure criteria and the cable functional failure temperature evaluation by exposed fire is studied.

The Leakage Crack Calculation of the Fire Door and the Stack Effect Analysis (방화문의 누설틈새 계산 및 연돌효과 분석)

  • Kim, Il-Young;Kwon, Chang-Hee
    • Fire Science and Engineering
    • /
    • v.27 no.2
    • /
    • pp.46-53
    • /
    • 2013
  • The architecture environment has changed. The corresponding design criteria should be changed. From July 27th, 2005 the Korea Standard of the fire door changed concerning the smoke resistance test which made the door gap structure more elaborate. However the National Fire Safety Codes are applied by the old data's of England. Which in case differs in the actual construction to the blue print, making the safety standard too excessive. Analyze the results and the phenomenon that occurs due to the difference between design and reality. The National Fire Safety Codes should be revised to leakage crack calculation is presented. Difference of the air flow for the smoke protection due to the stack effect analyzed. Living patterns and evacuation patterns of the apartment reflect and reasonable air flow measurement method are presented.

Optimum Design on Fire Resistance of Gas Cylinder Cabinets using Thermal Analysis (열해석을 이용한 가스 실린더 캐비닛의 내화성능 최적설계)

  • Nam, Minseo;Kim, Jiyu;Kim, Euisoo
    • Journal of the Korean Institute of Gas
    • /
    • v.26 no.1
    • /
    • pp.34-40
    • /
    • 2022
  • Gas cylinder cabinets have risks such as cylinder explosion and scattering of debris when a fire occurs. These risks are likely to cause gas spills and cause secondary damage. In order to reduce damage, it is very important to secure the fire resistance performance of the gas cylinder cabinet. In foreign countries, NFPA codes in the United States and EN-14470-2 in Europe stipulate fire resistance test standards for gas cylinder cabinets to protect internal cylinders for a certain period of time in a situation where gas cylinder cabinets are exposed to flames. However, in Korea, only internal pressure performance and airtight performance standards are specified, and the target is limited to piping, and research and regulations for the fire resistance performance of gas cylinder cabinets are insufficient compared to overseas. Therefore, in this study, finite element analysis was used to establish fire resistance standards for domestic gas cylinder cabinets. In the event of a fire, optimal conditions are derived in terms of structure and material.

A Study on the Development of Evaluation Methods for Fire Risk Analysis of High-rise Building ((초)고층 건축물의 화재위험성 평가기법 개발에 관한 연구(I))

  • Kwon, Young-Jin;Shin, Yi-Chul
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.11a
    • /
    • pp.223-228
    • /
    • 2008
  • Fire is recognized as a significant hazard in a service life of a structure. Therefore there is a clear need to provide an improved understanding of the performance of material and structures in fire and to provide clear design guidance in order to progress safety design especially high rise building. It is the aim of this study to investigates and analyze the study on the development of evaluation methods for fire risk analysis of high-rise building.

  • PDF

A Study on the Analysis of Evacuation Risk by Building Application for Fire Safety (화재안전을 위한 건축물 용도별 피난리스크 분석에 관한 연구)

  • Jin, Seung-hyeon;Koo, In-Hyuk;Seo, Dong-Goo;Kwon, Young-Jin
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2021.05a
    • /
    • pp.164-165
    • /
    • 2021
  • In Korea, in the case of fire scenarios in performance design, it is assumed that the sprinkler is not working. In addition, it does not applicate various fire conditions. Therefore it is not enough that the accuracy about fire scenario. In foreign countries, reseach is being conducted to predict the casualities that can occur due to fire in the building space through statistical risk analysis. Also, research is consistently conducting for design that consider the sprinker probability of operation. Therefore, to analyze the fire risk of each building in Korea, the risk was analyzed using statistical data. As a result, the risk of casualties that can occur for each building use was analyzed as 0.6(persons/cases) for residential buildings, 0.25(persons/cases) for sales facilities, and 0.12(persons/cases) for buisiness facilities.

  • PDF

Analysis of Prediction Results and Grid Size Dependence According to Changes in Fire Area (화원면적 변화에 따른 격자 크기 의존도 및 예측결과 분석)

  • Yun, Hong-Seok;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.33 no.6
    • /
    • pp.9-19
    • /
    • 2019
  • In fire simulations for building fire safety evaluation, changes in the fire area and grid size can significantly influence the prediction results. Therefore, the effects of area changes of the fire source with identical maximum heat release rates on the prediction results of a compartment fire were investigated. The dependence of the prediction results on the grid size using the identical fire area was also examined. No significant changes were observed in the thermal and chemical characteristics of the fires with variable grid sizes, even though the fire area was changed when six or more grids were set based on the fire diameter. In addition, changes in the fire area caused significant differences in the prediction of major physical quantities associated with available safety egress time (ASET) within a compartment. However, the fire area changes did not considerably influence the overall fire characteristics outside the compartment after reaching a certain distance from the opening.

An Improvement of Fire Safety Code for Rack-Type Warehouse in Korea (국내 랙크식 창고의 방화관련 규정 개선에 관한 연구)

  • Kim, Woon-Hyung;Lee, Young-Jae
    • Fire Science and Engineering
    • /
    • v.28 no.6
    • /
    • pp.69-75
    • /
    • 2014
  • Recently Amore pacific rack-type warehouse fire broke out and argue an urgent improvement of fire protection design code including automatic sprinkler and detection design. Various type of commodities have their unique fire characteristics from fire spread rate and heat lease rate and fire hazard depends on storage height, rack arrangement, aisle width, fire load etc. With increasing ceiling height for more storage space prevent effective water spray of sprinkler head, also delays detection time causes failure of early suppression. To achieve fire protection code performance of this occupancy, Major code articles relating to a classification of commodity, sprinkler system installation, detection and fire fighting are reviewed and suggested based on fire case analysis, code review between country and field survey.

DB Construction of Activation Temperature and Response Time Index for Domestic Fixed-temperature Heat Detectors in Ceiling Jet Flow (천장제트기류에 대한 국내 정온식 열감지기의 작동온도 및 반응시간지수(RTI)에 관한 DB 구축)

  • Yoon, Ga-Yeong;Han, Ho-Sik;Mun, Sun-Yeo;Park, Chung-Hwa;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.34 no.3
    • /
    • pp.35-42
    • /
    • 2020
  • The accurate prediction of fire detector activation time is required to ensure the reliability of fire modeling during the safety assessment of performance-based fire safety design. The main objective of this study is to determine the activation temperature and the response time index (RTI) of a fixed heat detector, which are the main input factors of a fixed-temperature heat detector applied to the fire dynamics simulator (FDS), a typical fire model. Therefore, a fire detector evaluator, which is a fire detector experimental apparatus, was applied, and 10 types of domestic fixed-temperature heat detectors were selected through a product recognition survey. It was found that there were significant differences in the activation temperature and RTI among the detectors. Additionally, the detector activation time of the FDS with the measured DB can be predicted more accurately. Finally, the DB of the activation temperature and RTI of the fixed-temperature heat detectors with reliability was provided.

A Study on Assesment of Aalidity of Introducing of Design·Construction·Supervision Register Criteria Measures for Hazardous Materials Facilities (위험물시설의 설계·시공·감리업 등록제 도입에 대한 타당성 검토에 관한 연구)

  • Cha, Jung-Min;Lee, Yong-Jae;Kim, In-Beom;Hyun, Seong-Ho
    • Fire Science and Engineering
    • /
    • v.29 no.1
    • /
    • pp.27-37
    • /
    • 2015
  • This study is to analyze current inadequate status of installing hazardous materials facilities, and to propose rational standards by researching validity for implementing registration for design, construction, supervision for installing fire safety facilities. By studying installation of registering designing, constructing, supervising industry on hazardous material facilities, professional and higher level of stability measures for national hazardous material facility was provided. For above reasons, necessity of institutionalizing of registering standards for construction and supervising industry became clear. Much more gradual institutionalization is needed for construction industry. Moreover, new national qualification should be reconsidered, in order to rebuttal the above and also to cultivate and acquire technical power.