• 제목/요약/키워드: Faulty Insulator

검색결과 14건 처리시간 0.024초

송전선로 노화애자의 안전 감지를 위한 상관전파신경망 (Correlation Propagation Neural Networks for Safe sensing of Faulty Insulator in Power Transmission Line)

  • 김종만
    • 전기학회논문지P
    • /
    • 제58권4호
    • /
    • pp.511-515
    • /
    • 2009
  • For detecting of the faulty insulator, Correlation Propagation Neural Networks(CPNN) has been proposed. Faulty insulator is reduced the rate of insulation extremely, and taken the results dirty and injured. It is necessary to detect the faulty insulator and exchange the new one. And thus, we have designed the CPNN to be detected that insulators by the real time computation method through the inter-node diffusion. In the network, a node corresponds to a state in the quantized input space. Each node is composed of a processing unit and fixed weights from its neighbor nodes as well as its input terminal. Information propagates among neighbor nodes laterally and inter-node interpolation is achieved. 1-D CPNN hardware has been implemented with general purpose. Experiments with static and dynamic signals have been done upon the CPNN hardware. Through the results of simulation experiments, we define the ability of real-time detecting the faulty insulators.

전자파 잡음을 이용한 전기설비 불량 검출장치 개발 (Development of the equipment for detecting the poor power facilities by receiving electric noises)

  • 이복규;강성철
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 1997년도 한국자동제어학술회의논문집; 한국전력공사 서울연수원; 17-18 Oct. 1997
    • /
    • pp.1356-1359
    • /
    • 1997
  • There are various methods to detect the faulty electric facilities(esp, insulator) indirectly on power distribution lines at a certain distance apart. This paper describes the proto type equipment to detect a faulty insulator by receiving a electric discharge noises, which are generated with a periodicity of 120Hz.

  • PDF

불량애자 검출을 위한 비젼 기반 전파 신경망 (Propagation Neural Networks based on vision techniques for detecting of Faulty Insulator)

  • 김종만;김영민;황종선;박현철;임성호
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 하계학술대회 논문집 Vol.3 No.2
    • /
    • pp.1097-1102
    • /
    • 2002
  • For detecting of Faulty Insulator, a new Lateral Information Propagation Networks (LIPN) has been proposed. Energized insulator is reduced the rate of insulation extremely, and taken the results dirty and injured. It is necessary to be actions that detect the faulty insulator and exchange the new one. And thus, we have designed the LIPN to be detected that insulators by the real time computation method through the inter-node diffusion. In the network, a node corresponds to a state in the quantized input space. Each node is composed of a processing unit and fixed weights from its neighbor nodes as well as its input terminal. Information propagates among neighbor nodes laterally and inter-node interpolation is achieved. Through several simulation experiments,real time reconstruction of the nonlinear image information is processed.

  • PDF

절연노화 애자의 실시간 감지를 위한 신경회로망의 개발 (Neural Networks for Real-time detecting of Energized Insulator)

  • 김종만;김원섭;김형석;신동용
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 D
    • /
    • pp.2276-2279
    • /
    • 2002
  • For detecting of Energized Insulator, a new Lateral Information Propagation Networks(LIPN) has been proposed. Faulty insulator is reduced the rate of insolation extremely, and taken the results dirty and injured. It is necessary to be actions that detect the faulty insulator and exchange the new one. And thus, we have designed the LIPN to be detected that insulators by the real time computation method through the inter-node diffusion. In the network, a node corresponds to a state in the quantized input space. Each node is composed of a processing unit and fixed weights from its neighbor nodes as well as its input terminal. Information propagates among neighbor nodes laterally and inter-node interpolation is achieved. Through the results of simulation experiments, we define the ability of real-time detecting the faulty insulators.

  • PDF

오손 애자자의 실시간 검출을 위한 계측기반 신경망 (Instrumentation based Neural Networks for Real-time detecting of Energized Insulator)

  • 김종만;김영민
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 춘계학술대회 논문집
    • /
    • pp.25-29
    • /
    • 2004
  • For detecting of Energized Insulator, a new Lateral Information Propagation Networks(LIPN) has been proposed. Faulty insulator is reduced the rate of insulation extremely, and taken the results dirty and injured. It is necessary to be actions that detect the faulty insulator and exchange the new one. And thus, we have designed the LIPN to be detected that insulators by the real time computation method through the inter-node diffusion. 1n the network, a node corresponds to a state in the quantized input space. Each node is composed of a processing unit and fixed weights from its neighbor nodes as well as its input terminal. Information propagates among neighbor nodes laterally and inter-node interpolation is achieved. Through the results of simulation experiments, we difine the ability of real-time detecting the faulty insulators.

  • PDF

활선애자점검기의 개발 및 154kV 선로에의 적용 - 제2부 : 진단 알고리즘 개발 (Development of Live-line Insulator Tester and Its Application to 154kV Power Lines - Part 2 : Inspection Algorithm Development)

  • 박준영;이재경;조병학;오기용
    • 전기학회논문지P
    • /
    • 제59권1호
    • /
    • pp.89-95
    • /
    • 2010
  • A new live-line insulator tester was developed to detect faulty insulators in 154kV power transmission lines. This paper is the second part of the two-part paper and deals with its inspection algorithm development. Unlike normal condition with low pollution and low humidity, the inspection data measured in the field under high pollution or high humidity showed that the voltage distribution of an insulator string has offsets in comparison with those of others and its insulation resistances are greatly decreased, which leads to wrong results of the existing inspection algorithms under such conditions. To solve this problem, we propose new diagnosis algorithms that can exactly detect faulty insulators from measured data regardless of environmental conditions. Its effectiveness was validated by live-line field tests in actual power lines.

Microphone Array와 열화상 카메라를 이용한 고압설비 고장검출 (Malfunction Detection of High Voltage Equipment Using Microphone Array and Infrared Thermal Imaging Camera)

  • 한순신;최재영;이장명
    • 제어로봇시스템학회논문지
    • /
    • 제16권1호
    • /
    • pp.25-32
    • /
    • 2010
  • The paper proposes a hierarchical fault detection method for the high voltage equipment using a microphone array which detects the location of fault and the thermal imaging and CCD cameras which verifies the fault and stores the image, respectively. There are partial arc discharges on the faulty insulators, which generates a specific pattern of sound. Detecting the signal using the microphone array, the location of the faulty insulator can be estimated. The 6th band-pass filter was applied to remove noise signal from wind or external influence. When the mobile robot carries the thermal and CCD cameras to the possible place of the fault insulator, the fault insulators or power transmission wires can be detected by the thermal images, which are caused by the aging or natural erosion. Finally, the CCD camera captures the image of the fault insulator for the record. The detection scheme of fault location using the microphone array and the thermal images have been proved to be effective through the real experiments. As a result of this research, it becomes possible to use a mobile robot with the integrated sensors to detect the fault insulators instead of a human being.

불량소자의 검지를 위한 실시간 전송 뉴로 모률라 (A Neural Network Modulars for Real-time Detection of Bad Materials)

  • 김종만;김원섭
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2008년도 춘계학술대회 논문집 센서 박막재료연구회 및 광주 전남지부
    • /
    • pp.54-57
    • /
    • 2008
  • A new modular Lateral Information Propagation Networks can be implemented in a IC chip with the circuit VLSI technology for detection of bad materials. The proposed modular architecture is propagated the neural network through inter module connections. For such inter module connections, the host(computer or logic) mediates the exchange of information among modules. Also border nodes in each module have capacitors for temporarily retaining the information from outer modules. For detecting of Faulty Insulator, $4\;{\times}\;4$ neural network modules has been designed and simulation of interpolation with the designed networks has been done.

  • PDF

활선애자점검기의 개발 및 154kV 선로에의 적용 - 제1부 : 점검기 개발 (Development of Live-line Insulator Tester and Its Application to 154kV Power Lines - Part 1 : Tester Development)

  • 이재경;박준영;조병학;오기용
    • 전기학회논문지P
    • /
    • 제59권1호
    • /
    • pp.83-88
    • /
    • 2010
  • A new live-line insulator tester was developed to detect faulty insulators in 154kV power transmission lines. This paper is the first part of the two-part paper and deals with its tester development. The developed tester has the following characteristics. First, it automates parts of the insulator inspection process by using a sensor and an actuator, and secondly, it sustains its weight by itself, not by a lineman. Finally, it measures the insulation resistance of an insulator together with its distribution voltage to provide more information for its analysis and diagnosis. These leads to the improvement of its operation efficiency, measurement reliability and usability. Its effectiveness was validated by live-line field tests in actual power lines.

가공송전선로 애자 적용실태와 향후 전망 (Insulator application and prospect)

  • 김우겸;민병욱;김태영;위화복;최진성;이북창
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.327_328
    • /
    • 2009
  • The insulator being used for transmission line is to mount the charged conductor on the tower or other supports. The insulators are classified according to its material: porcelain, glass and polymer. Polymer insulators are also called as composite insulator or non ceramic insulator (NCI). Insulators are a major element of a power transmission system. Since a faulty insulator can lead to a wide spreading blackout, it must have sufficient mechanical and electrical strength. It must be durable, have high electrical insulation and be able to withstand a leakage current. It must also be able to withstand the toughest weather conditions. In Korea, porcelain insulators have been used widely. However, to make compact equipment and keep up with global trends, we have enhanced domestic production of polymer insulator and are encouraging its applications. Accordingly, this thesis will look at types of insulators, use and trends, and prospects of insulators application in the field.

  • PDF