• 제목/요약/키워드: Fault insulator

검색결과 37건 처리시간 0.026초

Microphone Array와 열화상 카메라를 이용한 고압설비 고장검출 (Malfunction Detection of High Voltage Equipment Using Microphone Array and Infrared Thermal Imaging Camera)

  • 한순신;최재영;이장명
    • 제어로봇시스템학회논문지
    • /
    • 제16권1호
    • /
    • pp.25-32
    • /
    • 2010
  • The paper proposes a hierarchical fault detection method for the high voltage equipment using a microphone array which detects the location of fault and the thermal imaging and CCD cameras which verifies the fault and stores the image, respectively. There are partial arc discharges on the faulty insulators, which generates a specific pattern of sound. Detecting the signal using the microphone array, the location of the faulty insulator can be estimated. The 6th band-pass filter was applied to remove noise signal from wind or external influence. When the mobile robot carries the thermal and CCD cameras to the possible place of the fault insulator, the fault insulators or power transmission wires can be detected by the thermal images, which are caused by the aging or natural erosion. Finally, the CCD camera captures the image of the fault insulator for the record. The detection scheme of fault location using the microphone array and the thermal images have been proved to be effective through the real experiments. As a result of this research, it becomes possible to use a mobile robot with the integrated sensors to detect the fault insulators instead of a human being.

고속철도 유리애자 파손원인을 위한 현장 진동 연구 (A Study on Field Vibration for Fault Cause Analysis of Glass Insulator on High-speed Railway)

  • 김영석;송길목;방선배;김선구;류영태
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 Techno-Fair 및 합동춘계학술대회 논문집 전기물성,응용부문
    • /
    • pp.189-190
    • /
    • 2008
  • This study was investigated a possibility of fault of glass insulator due to vibration on high-speed railway. The proper vibration of 1-glass insulator have many frequency band and high amplitude showed in high frequency than low frequency. The proper vibration of strut tube insulator was lowest 170Hz, highest 1.5kHz. The field signal amplitude of viaduct and open route were biggest moment pantograph of high-speed rail. The surface vibration(V3) amplitude of strut tube insulator was biggest. From the FFT analysis of viaduct and open route, the strut tube insulator effect by vertical vibration was big, the frequency was 82.5Hz and 105Hz, respectively. However, in comparison with the proper vibration of strut tube insulator, the resonance was not observed. Although the amplitude of insulator is high, the possibility of fault is low because the glass insulator deterioration by the accumulation of vibration do not happen.

  • PDF

A Study on the Acoustic Fault Detection System of Insulators from Their Radiation Noises

  • Park, Kyu-Chil;Yoon, Jong-Rak
    • Journal of information and communication convergence engineering
    • /
    • 제9권5호
    • /
    • pp.510-514
    • /
    • 2011
  • To detect the insulator in the fault state on the electric poles, we first measured radiation sounds from normal state insulators and error state insulators in the anechoic chamber. We processed the signals in frequency domain to find the features with filter bank, narrow band and wide band analysis. So we could found two apparent results from their frequency spectrums - one was 120Hz harmonic components, the other was high average noise level than normal state ones. Then we also introduced a technique for the direction detection of the fault state insulator using the cross correlation from the three dimensional array microphones. To eliminate the noise signal from unexpected directions, we suggested the zero padding technique in cross correlation function. From these, we could conclude that acoustic fault detection techniques are useful of the detection of insulators' faults and the estimation of the direction of the fault state insulators.

배전선로 고장예지를 위한 애자의 고장징후 특성에 관한 연구 (A Feasibility Study on the Characterization of Incipient Insulator Failure for Distribution Fault Prediction)

  • 신정훈;김태원;박성택;김창종
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 추계학술대회 논문집 학회본부
    • /
    • pp.245-249
    • /
    • 1997
  • A feasibility study on the characterization of incipient insulator failure for distribution fault prediction is presented. In this study, real distribution data was collected and analyzed to isolate incipient failure signatures or parameters which were expected to show distinct behaviors before and after failure incident. Several signal analysis methods were applied to isolate the parameters and a new strategy of analysis, the event-date concept, was also applied to find a relationship between non-harmonic and high frequency signal activities and imminent insulator failures.

  • PDF

고속철도용 유리애자의 진동 및 파손가능성 분석 (Analysis of Fault Possibility and Vibration of Glass Insulator on High-speed Railway)

  • 김영석;송길목;정진수;김선구;전용주;류영태
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.2044-2045
    • /
    • 2008
  • This paper was studied fault possibility of glass insulator through the proper vibration and field vibration comparison. The proper vibration of 1 cell glass insulator have many frequency band and high amplitude showed in high frequency than low frequency. The field signal amplitude of viaduct and open route were biggest moment pantograph of high-speed rail. From the FFT analysis of viaduct and open route, in the case of positive direction, the strut tube insulator effect by vertical vibration was big, the frequency was 82.5Hz and 105Hz, respectively. However, in the case of negative direction, the vibration did not cause big effect. In comparison with the proper vibration of glass insulator, the resonance was not observed.

  • PDF

배전용 애자장치의 열화특성 및 선로사고와의 상관관계에 관한 연구 (A Study on the Relation of Fault in Distribution Line by Insulator deterioration)

  • 김태원;신정훈;박성택
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 E
    • /
    • pp.1666-1669
    • /
    • 1998
  • In General, Distribution Line is largely effected by temperature, humidity and natural system's condition. The power system network, particularly fault of power distribution system connected to comsumer would cause a magnificent effect to the society. And then Improvement in living conditions and increase in the industrial production brought by the development in economy and new technology, in due course, ask more and reliable electric energy. In this paper, we will describes that the effection of deterioration in Insulator and its relation of fault in power system.

  • PDF

Arcing Horn의 아크섬락특성과 애자보호와의 관계 연구 (A Study on the Relation Between Arc Characteristics and Insulator Protection of the Arcing Horn)

  • 조성배
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 E
    • /
    • pp.1734-1736
    • /
    • 1997
  • Insulator strings can be frequently damaged by fault currents occured by lightning strokes, overvoltages and contamination of the insulators. So the Insulator damages may lead to extensive damages to transmission lines as well as power outages that have caused dangerous situations to occur. This paper suggests the characteristics of arcing horn in relation to the protection of insulators and basic design concepts of the arcing horn for transmission lines.

  • PDF

154kV 활선 애자련의 불량애자를 검출하는 활선애자 점검기 개발 (Development of Inspection Tool for 154kV Live-line Insulator string)

  • 이재경;박준영;오기용;조병학
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 학술대회 논문집 정보 및 제어부문
    • /
    • pp.373-374
    • /
    • 2008
  • To prevent an insulator failure, a new inspection system is presented for 154kV insulator strings. The inspection system detects fault insulators by measuring resistance and voltage of each insulators in the 154kV insulator string. The inspection instrument obtains autonomously insulation resistance and assigned voltage along the insulator string. The insulator inspection instrument is manipulated by two operators. In addition, a set of mechanism is applied to prevent the system from being reset under live-line condition. We confirmed its effectiveness through experiments.

  • PDF

고장 발생에 따른 HVDC 시스템용 TP 케이블의 절연체 수명 손실 분석 (Analysis of Insulation Life Loss due to Fault Occurrence of TP Cable for HVDC Systems)

  • 정우희;이재인;이석주;딘민차우
    • 한국산업정보학회논문지
    • /
    • 제29권4호
    • /
    • pp.55-66
    • /
    • 2024
  • HVDC (high-voltage direct current) 시스템에 TP (thermoplastic) 케이블을 안전하게 사용하기 위해서는 다양한 연구와 테스트를 통해 운전 중 발생할 수 있는 시스템 고장으로 인한 케이블의 수명 손실률 분석이 필요하다. 본 논문에서는 HVDC 시스템 운영 중에 발생할 수 있는 고장 유형에 따른 TP 케이블의 절연체 수명 손실률을 분석하였다. TP 케이블 모델에 고장으로 인한 전력을 인가하고, 2D 유한요소법을 통한 분석 결과를 바탕으로 Arrhenius-IPM (Inverse Power Model)을 적용하여 절연체의 수명 손실률을 분석하였다. 분석결과 절연체 수명 손실률은 전기장 세기의 영향이 높았으며, 고장 발생 시 절연체 내부 측에서 손실률이 가장 높았다. 이러한 결과는 TP 케이블 상용화를 위한 초기 설계 단계에서 중요한 특성으로 사용될 수 있다.

배전용 불량애자에서의 전자파 부분방전 검출장치 개발 (Development of the partial discharge detecting equipment using electromagnetic wave in deteriorated insulator)

  • 강창원;송일근;김주용;이병성;강대수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 C
    • /
    • pp.1667-1669
    • /
    • 2001
  • The clack of Insulator, which results from internal or external surges such as electrical, mechanical, and thermal stress, might cause ground fault and a power failure without proper repairs. In order to minimize losses caused by a short-term or long-term power failure, it is necessary to detect the deteriorated insulator as early as possible. To do so, we will develop a new device, which can detect and trace an deteriorated insulator by monitoring its physical change the variation of frequency spectrum. This device will do so by finding a Periodic wave sharp (120 Hz), a peculiar wave generated by defused electricity.

  • PDF