상용2회선 수전방식을 적용한 무정전 수변전설비 구축방안 검토·제안연구 (Construction of Uninterruptible Power System by Reliable Incoming Dual-Power Line)

  • 최진성;이상중
    • 조명전기설비학회논문지
    • /
    • 제24권12호
    • /
    • pp.64-70
    • /
    • 2010
  • High capacity UPS and emergency generators are commonly employed at facilities where power interruption is not allowed. Nowadays, combinations of existing commercial incoming power and an emergency generator or combination of multiple generators and CTTS(Closed Transition Transfer Switch) is adopted sometimes for more reliable power supply. In this paper, application of CTTS and STS(Static Transfer Switch) to dual-power line is suggested for highly reliable uninterruptible power. By realizing such a system, construction of incoming power facilities, installation of emergency generator and large capacity UPS can be omitted, through which saving of the installation space and corresponding capital investment can be expected.

선박 비상조명용 전원장치의 성능개선 (A Study on the Improvement of Performance of Power Supply for Ship's Emergency Lighting System)

  • 양현숙;이수헌;정태선;이성근;김윤식
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2004년도 전력전자학술대회 논문집(2)
    • /
    • pp.822-825
    • /
    • 2004
  • This paper describes the improvement of performance of power supply for ship's emergency lighting system(SELS). Proposed system is composed of power factor correction (PFC) circuit, emergency power supply system (EPSS), half bridge(HB) inverter, fluorescent lamp(FL) starting circuit and microprocessor control system. Experimental works using proposed system confirm that speedy and stable power to be supplied when main power source cut-off, compared with conventional relay type, and control power factor up to $97.5[\%]$ and input power up to $35.0[\%]$ by adjusting of pulse frequency of the HB inverter.

  • PDF

비상발전기 통합제어 및 감시시스템 개발 (Development of an Integrated Control and Monitoring System for Emergency Power Generators)

  • 진강규;류길수;윤지근;유성호;김재환
    • 한국마린엔지니어링학회:학술대회논문집
    • /
    • 한국마린엔지니어링학회 2001년도 춘계학술대회 논문집
    • /
    • pp.192-196
    • /
    • 2001
  • These days, most of electric power facilities need high stability. Therefore integrated system has been required to monitor and control electronic power distribution system in fields at all times when the interruption of electric power has occurred. To construct this system, unit that convert and process the input signal from fields needed. And for control and monitoring from remote place MMI software is required. Lastly network equipments are required for real-time communications. So, in this paper, units for control and monitoring of emergency power generator and for electric power monitoring in normal electric power and interruption of electric power are developed. Also integrated remote system for monitoring in remote is developed.

  • PDF

Conceptual design of autonomous emergency operation system for nuclear power plants and its prototype

  • Kim, Jonghyun;Lee, Deail;Yang, Jaemin;Lee, Subong
    • Nuclear Engineering and Technology
    • /
    • 제52권2호
    • /
    • pp.308-322
    • /
    • 2020
  • This paper presents a conceptual design for a plant-wide autonomous operation system that uses artificial intelligence techniques. The autonomous operation system has the power and ability to perform the control functions needed for the emergency operation of a nuclear power plant (NPP) with reduced operator intervention. This paper discusses the emergency operation and level of automation in an NPP and presents the design requirements for an autonomous emergency operation system (A-EOS). Then, an architecture that consists of several modules is proposed, with descriptions of the functions. Finally, this paper introduces a prototype of the suggested autonomous system that integrates the authors' previous works.

Use of gaze entropy to evaluate situation awareness in emergency accident situations of nuclear power plant

  • Lee, Yejin;Jung, Kwang-Tae;Lee, Hyun-Chul
    • Nuclear Engineering and Technology
    • /
    • 제54권4호
    • /
    • pp.1261-1270
    • /
    • 2022
  • This study was conducted to investigate the possibility of using gaze entropy to evaluate an operator's situation awareness in an emergency accident situation of a nuclear power plant. Gaze entropy can be an effective measure for evaluating an operator's situation awareness at a nuclear power plant because it can express gaze movement as a single comprehensive number. In order to determine the relationship between situation awareness and gaze entropy for an emergency accident situation of a nuclear power plant, an experiment was conducted to measure situation awareness and gaze entropy using simulators created for emergency accident situations LOCA, SGTR, SLB, and LOV. The experiment was to judge the accident situation of nuclear power plants presented in the simulator. The results showed that situation awareness and Shannon, dwell time, and Markov entropy had a significant negative correlation, while visual attention entropy (VAE) did not show any significant correlation with situation awareness. The results determined that Shannon entropy, dwell time entropy, and Markov entropy could be used as measures to evaluate situation awareness.

비상전원 기능을 갖는 하이브리드 ESS를 위한 PCS 제어전략 (A PCS Control Strategy for Hybrid ESS with Function of Emergency Power Supply)

  • 김상진;권민호;최세완;백석민;김미성
    • 전력전자학회논문지
    • /
    • 제21권4호
    • /
    • pp.302-311
    • /
    • 2016
  • This paper proposes a hybrid ESS that integrates an energy storage system (ESS) with an uninterruptible power supply (UPS). The hybrid ESS has a demand management and emergency power supply function while increasing the battery utilization of the UPS, which has just been used in a power failure. In addition to the critical load, the proposed system augments the capacity of emergency generation using an additional load, which has voltage and frequency-dependent characteristics to the grid side. The control algorithm of the AC-DC converter and bidirectional DC-DC converter is proposed for demand management and emergency power supply. Furthermore, seamless and autonomous transfer methods to alleviate the transient during mode transfer are proposed. To validate the proposed control scheme, experimental results from a 5 kW prototype are provided.

소방용 비상발전기의 현장부하시험을 위한 20 kW급 ESS 부하시험장치 모델링과 구현에 관한 연구 (A Study on the Implementation and Modeling of 20kW Scale ESS Load Test Device for Emergency Generator)

  • 최승규;이후동;최성식;페레이라 마리토;노대석
    • 한국산학기술학회논문지
    • /
    • 제20권9호
    • /
    • pp.541-550
    • /
    • 2019
  • 소방용 비상발전기는 화재 시 인명과 재산을 보호하는 소방 시설에 전원을 공급하는 중요한 설비이다. 이러한 중요성에 따라 관련 법규에서는 의무적으로 비상발전기에 비상용 부하를 연결하여 시험하도록 규정하고 있다. 그러나 실 계통에서는 비상전원계통의 부하운전 시험을 위해 상용 전원을 차단하는 경우 저압기기의 파손, 병원과 같은 중요시설의 응급부하 정지 등 심각한 문제점이 발생할 수 있어, 무부하로 비상발전기를 형식적으로 시험하고 있는 실정이다. 따라서, 본 논문에서는 상기의 문제점을 개선하기 위하여, 상용 전원의 차단 없이 비상발전기에 전기저장장치를 연계하여, 비상용부하의 동작특성과 동일하게 ESS가 충전동작을 수행함으로서 비상발전기의 성능 및 상태를 시험할 수 있는 방안을 제시한다. 또한, 배전계통 상용 해석 프로그램인 PSCAD/EMTDC를 이용하여, 비상발전기, 비상용부하, ESS 부하시험장치로 구성된 비상전원계통의 모델링을 제시하고, 20kW급 ESS 부하시험장치를 구현하여, 이를 바탕으로 다양한 시나리오에 따른 시뮬레이션과 시험을 수행하여 본 논문에서 제안한 ESS 부하시험 장치와 모델링의 유용성을 확인한다.

Effects of child pick-up behavior on emergency evacuations

  • Jang, Sang Hoon;Hwang, Ha;Chung, Ji-Bum
    • Nuclear Engineering and Technology
    • /
    • 제54권7호
    • /
    • pp.2519-2528
    • /
    • 2022
  • The child pick-up behavior of parents during an emergency can cause heavy traffic congestion and failing to evacuate an affected area successfully. In this study, we analyzed the effect of child pick-up behavior using, as an example, a nuclear power plant accident caused by an earthquake, which is a typical no-notice emergency. A quake was assumed to occur near the Shin-Kori nuclear power plant in Ulsan, Korea, resulting in a nuclear power plant accident. An agent-based dynamic simulation model using VISSIM was employed to conduct sensitivity analyses with different child pick-up rates. The results confirmed that parents are a major cause of congestion and a vulnerable class in an emergency evacuation. The child pick-up behavior caused significant traffic congestion, and parents who pick up their children showed a higher evacuation failure rate.

선박 비상조명 원격 모니터링 제어 (A Study on the Remote Monitoring and Control of Ship's Emergency Lighting System)

  • 양현숙;김건우;임현정;문정필;이성근;김윤식
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2005년도 전력전자학술대회 논문집
    • /
    • pp.207-210
    • /
    • 2005
  • This paper describes a design of several ship's emergency lighting system(SELS) that power factor is improved and power is controlled extensively, and techniques to control and monitor this system in remote distance by PC serial communication. The remote monitoring control system is composed of emergency power supply system (EPSS), half bridge(HB)inverter, fluorescent lamp(FL), microprocessor, multi communication interface. EPSS checks the voltage of the emergency backup battery in real time. In case that the voltage of 13[V] or less has been detected for 5[msec] or longer for 3 times in a row, charger circuit is connected for battery charging. Experimental works using proposed system confirm that speedy and stable power to be supplied when main power source cut-off, compared with conventional analog type, and input power up to 35.0[%] by adjusting of pulse frequency of the HB inverter.

  • PDF

Research on Line Overload Emergency Control Strategy Based on the Source-Load Synergy Coefficient

  • Ma, Jing;Kang, Wenbo;Thorp, James S.
    • Journal of Electrical Engineering and Technology
    • /
    • 제13권3호
    • /
    • pp.1079-1088
    • /
    • 2018
  • A line overload emergency control strategy based on the source-load synergy coefficient is proposed in this paper. First, the definition of the source-load synergy coefficient is introduced. When line overload is detected, the source-load branch synergy coefficient and source-load distribution synergy coefficient are calculated according to the real-time operation mode of the system. Second, the generator tripping and load shedding control node set is determined according to the source-load branch synergy coefficient. And then, according to the line overload condition, the control quantity of each control node is determined using the Double Fitness Particle Swarm Optimization (DFPSO), with minimum system economic loss as the objective function. Thus load shedding for the overloaded line could be realized. On this basis, in order to guarantee continuous and reliable power supply, on the condition that no new line overload is caused, some of the untripped generators are selected according to the source-load distribution synergy coefficient to increase power output. Thus power supply could be restored to some of the shedded loads, and the economic loss caused by emergency control could be minimized. Simulation tests on the IEEE 10-machine 39-bus system verify the effectiveness and feasibility of the proposed strategy.