Analysis of Insulation Aging in High Voltage Motor Stator Windings (고압전동기 고정자 권선의 절연열화 분석)

  • Kim, Hee-Dong;Kong, Tae-Sik;Lee, Young-Jun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.06a
    • /
    • pp.200-203
    • /
    • 2006
  • Prior to destructive testing, diagnostic tests were performed in eight high voltage motors. Diagnostic tests included polarization index, ac current, dissipation factor($tan{\delta}$) and partial discharge magnitude. The rewind of motor stator insulation at rated voltage is assessed by the results of these tests. After completing the diagnostic tests, the stator windings of motors were subjected to gradually increasing ac voltage, until the insulation punctured. No. 1 motor failed near rated voltage of 12.96 kV. The breakdown voltage of No. 4 motor was 6.99 kV which is lower that expected for good quality coils in 6.6 kV class motors. The failure was located in a line-end coil at the exit from the core slot. These two motors began operation in 1994. While testing No. 7 motor, flashover occurred between the stator winding and the stator frame at 15 kV. The relationship between the diagnostic test and the drop in insulation breakdown voltage was analyzed.

  • PDF

Breakdown Characteristics of Dry Air under 362 kV GIB (362 kV GIB 내에서 건조공기의 절연파괴 특성)

  • Han, Ki-Son;Ju, Hyung-Jun;Yoon, Jin-Yul;You, Hong-Geun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.23 no.10
    • /
    • pp.804-808
    • /
    • 2010
  • In this paper, we studied the dielectric breakdown voltage characteristics by the AC withstand voltage test on using green insulation dry air instead of $SF_6$ insulation gas used in the GIB (gas insulated bus) of 362 kV GIS (gas insulated switchgear). The AC withstand voltage test applied to the standard KEPCO's 362 kV GIB with dry air insulation, and the equivalence of dielectric breakdown voltage for dry air and $SF_6$ gas were examined, and the empirical formulas of dielectric breakdown voltage for dry air were calculated, and the criterion of AC withstand voltage test for dry air insulation was derived. Using the criterion, dry air can be used instead of $SF_6$ gas for 362 kV GIB in the factory acceptance test was confirmed.

A Study on Transmission Tower by Applying Polymer Insulation Arms (암절연물을 적용한 송전철탑 연구)

  • Park, Hoy-Yul;Ahn, Myeong-Sang;Lee, Tae-Joo;Lee, Dong-II;Choi, In-Hyuk;Kim, Joung-Ho
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.05b
    • /
    • pp.1-4
    • /
    • 2005
  • The electric power demand is steadily high. It becomes difficult to secure the land for overhead transmission lines year after year. Downsizing of overhead transmission lines can be most effectively achieved by applying polymer insulation arm. This paper describes the outline of compact overhead transmission lines and the result of mechanical evaluation of FRP for the compact transmission towers. Bending strength of FRP was evaluated according to the fiber orientation because the fiber orientation in FRP has a great effect on the strength of FRP.

  • PDF

A Study on the Complex Accelerating Degradation and Condition Diagnosis of Traction Motor for Electric Railway (전기철도용 견인전동기의 복합가속열화 상태진단에 관한 연구)

  • 왕종배
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.15 no.1
    • /
    • pp.93-101
    • /
    • 2002
  • In this study, the stator form-winding sample coils based on silicone resin and polyimide were made for fault prediction and reliability estimation on the C-Class(200$\^{C}$ ) insulation system of traction motors. The complex accelerative degradation was periodically performed during 10 cycles, which was composed of thermal stress, fast rising surge voltage, vibration, water immersion and overvoltage applying. After aging of 10 cycles, the condition diagnosis test such as insulation resistance '||'&'||' polarization index, capacitance '||'&'||' dielectric loss and partial discharge properties were investigated in the temperature range of 20 ∼ 160$\^{C}$. Relationship among condition diagnosis tests was analyzed to find a dominative degradation factor and an insulation state at end-life point.

AC Breakdown Analysis by Epoxy Thickness in Composite-Insulation (복합절연물내의 에폭시 두께에 따른 AC 절연파괴 분석)

  • Jung, Hae-Eun;Yun, Jae-Hun;Kim, Byoung-Chul;Kang, Seong-Hwa;Lim, Kee-Joe
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.11a
    • /
    • pp.468-469
    • /
    • 2007
  • $SF_6$ gas used widely as insulating component in electric power industry has excellent in insulation and arc extinguishing performance in gas-insulated switchgear. However, the concern about eco-friendly alternative gas is currently rising, because $SF_6$ gas is one of the main greenhouse gases. As one of the study for $SF_6$ free technology, composite-insulation technology is focused in this paper. To analyze the influence by epoxy thickness change, the composite-insulation composed of dry-air and epoxy was used in this paper. To analyze AC breakdown by the epoxy thickness, needle-plane electrode was used and needle was molded by epoxy. Under the gas pressure ranged from 0.1 to 0.6MPa, the breakdown voltage of dry-air were measured in AC electric field. The data of composite-insulation were acquired by changing the thickness of epoxy used in each composite-insulation under the same condition.

  • PDF

A Study on Thermal Properties for Epoxy Micro-and-Nano Mixture Composites(EMNC) (에폭시 마이크로-나노 입자가 혼합된 콤포지트의 열적특성에 관한연구)

  • Lee, Chang-Hoon;Kim, Kuk-Jin;Kim, Suk-Man;Kang, Do-Hoon;Yeon, Da-Som;Park, Jae-Jun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.83-83
    • /
    • 2010
  • This study investigates the thermal and mechanical properties of insulation elements through mixing epoxy based micro- and nano particles. Regarding thermal properties, DSC and DMA were used to calculate crosslinking densities for various types of insulation elements. In a mechanical property of bending strength, shape and scale parameters were obtained using the Weibull plot. This study obtained the most excellent results of scale parameters, such as Vol 3.2%, in the bending strength of EMNCs.

  • PDF

Application Technologies of Polymer Suspended Insulators for the Electric Track Line (전차 선로용 폴리머 현수애자의 적용 기술)

  • Han, Se-Won;Cho, Han-Goo;Song, Hong-Jun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.05c
    • /
    • pp.59-61
    • /
    • 2001
  • Polymeric suspended insulators for the electric track line have been developed. The main elements to design polymeric insulators are the insulation ability related with materials of FRP core and housing, and the optimal structure related with fitting parts and interface characteristics. To confirm the design fitness of insulator samples the electric field distribution by FEM and mechanical stress distribution by NASTRAN program was analysed with housing shed shapes and fitting structure. The leakage distance and breakage voltage properties which are core parameters to determine electric insulation ability are selected according to the requirement values of user specification, then the power frequency wet withstand voltage was specified above 22kV and the leakage distance was required above 290mm. The contamination condition of the electric track line was the heavy class according to IEC 815 in order to retain the enough safety margin against overvoltages.

  • PDF

Development of Optimum Shape Forming Technology of Angle Ring and Cap for 154kV transformer Insulation (154kV급 변압기절연물 앵글링과 캡의 최적성형 기술 개발)

  • Suh, Wang-Byuck;Kim, Jong-Won;Jang, Sung-Ju;Ryu, Jung-Soo;Bae, Dong-Ho
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.30-30
    • /
    • 2010
  • The Angle Ring and Cap which is called pressboard are settled at primary and secondary coil winding of 154 kV transformer that can reduce effectively distance of insulation. As it has not manufactured pressboard of Angle Ring and Cap for high voltage grade, insulation components industry especially high voltage transformer has not participate in a competition with worldwide yet. That's why is difficult to make an specialized shape of insulation components of high voltage grade. At first, it is very important to make an utility of deformation manufacturing for high voltage transformer insulation components by itself. Therefore it has finally completed to make an deformation manufacturing utility using an special analysis tools. In this paper, developed insulation components was investigates in tensile strength is introduced.

  • PDF

Analysis of Insulation Condition in High Voltage Motor Stator Windings Following Cleaning and Insulation Reinforcement (세척과 절연보강에 따른 고압전동기 고정자 권선의 절연상태 분석)

  • Kim, Hee-Dong
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.25 no.6
    • /
    • pp.474-480
    • /
    • 2012
  • Diagnostic tests were performed on two high voltage(HV) motor stator windings. These tests included the measurement of insulation resistance, polarization index, AC current, dissipation factor($tan{\delta}$) and partial discharge(PD) magnitude. Surface contamination of HV motor stator windings has an effect on the AC current and $tan{\delta}$. When the stator windings were finished cleaning and insulation reinforcement, the increase rate of AC current(${\Delta}I$) and dissipation factor(${\Delta}tan{\delta}$) were very small compared to those before cleaning. However, the PD magnitude remained the same. These tests show that cleaning and insulation reinforcement of HV motor stator windings can reduce the insulation failure.

A Study on the Development of Traction Motor for Electric Railway: Insulation System Design & Performance Test

  • Wang, Jong-Bae
    • Transactions on Electrical and Electronic Materials
    • /
    • v.2 no.4
    • /
    • pp.19-23
    • /
    • 2001
  • In this paper, design considerations and manufacturing procedure of 200 class insulation system with polyimide(Kapton) main insulation and silicone resin VPI process on the traction motor thor EMU will be reviewed. The performance test and the long life evaluation test that prove stability and reliability of Insulation system for traction motor will also be introduced.

  • PDF