DOI QR코드

DOI QR Code

Analysis of Insulation Condition in High Voltage Motor Stator Windings Following Cleaning and Insulation Reinforcement

세척과 절연보강에 따른 고압전동기 고정자 권선의 절연상태 분석

  • Kim, Hee-Dong (Korea Electric Power Corporation (KEPCO) Research Institute)
  • 김희동 (한국전력공사 전력연구원 기술전문센터)
  • Received : 2012.05.13
  • Accepted : 2012.05.25
  • Published : 2012.06.01

Abstract

Diagnostic tests were performed on two high voltage(HV) motor stator windings. These tests included the measurement of insulation resistance, polarization index, AC current, dissipation factor($tan{\delta}$) and partial discharge(PD) magnitude. Surface contamination of HV motor stator windings has an effect on the AC current and $tan{\delta}$. When the stator windings were finished cleaning and insulation reinforcement, the increase rate of AC current(${\Delta}I$) and dissipation factor(${\Delta}tan{\delta}$) were very small compared to those before cleaning. However, the PD magnitude remained the same. These tests show that cleaning and insulation reinforcement of HV motor stator windings can reduce the insulation failure.

Keywords

References

  1. J. H. Dymond, N. Stranges, K. Younsi and J. E. Hayward, IEEE Trans. Ind. Appl., 38, 577 (2002). https://doi.org/10.1109/28.993182
  2. H. D. Kim and B. H. Kim, J. KIEEME, 19, 1067 (2006).
  3. H. D. Kim and T. S. Kong, J. KIEEME, 25, 309 (2012).
  4. H. Yoshida and K. Umemoto, IEEE Trans. Electri. Insul., 21, 1021 (1986). https://doi.org/10.1109/TEI.1986.349018
  5. G. Stone, IEEE Trans. Ind. Appl., 41, 91 (2005). https://doi.org/10.1109/TIA.2004.840977
  6. H. D. Kim, J. KIEE, 58, 788 (2009).
  7. H. Zhu, C. Morton, and S. Cherukupalli, Conf. IEEE Int. Sympos. Electri. Insul., 384 (2006).