• 제목/요약/키워드: Electric Facilities

검색결과 838건 처리시간 0.027초

Preventing Method against the Occurrence of a Corona between a Dead End clamp and a Porcelain Insulator Used in 154kV Substation

  • Han, Woon-Ki;Choi, Jong-Soo;Lee, Jun;Kim, Jae-Chul
    • International Journal of Safety
    • /
    • 제6권2호
    • /
    • pp.22-26
    • /
    • 2007
  • An episode of corona is a heterogeneity-caused electric discharge that occurs when electric fields are formed layer on layer and concentrated on an electrode. Electric wires built at the tip of 154kV private facilities use dead end clamp spawns corona from homogeneity caused by field concentration. Corona induces power loss, noise, insulator failure and more. In this research, we've studied the characteristics of coronas that take place in porcelain insulators and terminal electric wires of supporting hard wares (dead end clamp) that are set up as spares in the 154kV private facilities use hydroelectricity installations to support electric wires. Corona, which cannot be identified by regular methods, was measured utilizing UV image camera. As the result of measuring corona via UV image camera, we've confirmed that the depletion of insulators was accelerated following the wire end treatment method and validated the stress intensity of insulators at various lengths of bare wires caused by electric fields via FEMLAB. We have also proposed a new model for relieving homogeneity-caused field concentration, and after analyzing the proposed model via FEMLAB, we've confirmed that the concentration of field distribution was indeed reduced. Such results are exploited in installation of private facilities use equipments, maintenance of insulators and hard wares as well as safety enhancement, and are anticipated to be effectively utilized in corona prevention measures.

산업전기 설비의 상태 감시를 위한 자가 발전 센서 시스템의 설계 (Design of Self-Powered Sensor System for Condition Monitoring of Industrial Electric Facilities)

  • 이기창;강동식;전정우;황돈하;이주훈;홍정표
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 학술대회 논문집 정보 및 제어부문
    • /
    • pp.264-266
    • /
    • 2005
  • Recently, on-line diagnosis methods through wired and wireless networks are widely adopted in the diagnosis of industrial Electric Facilities, such as generators, transformers and motors. Also smart sensors which includes sensors, signal conditioning circuits and micro-controller in one board are widely studied in the field of condition monitoring. This paper suggests an self-powered system suitable for condition-monitoring smart sensors, which uses parasitic vibrations of the facilities as energy source. First, vibration-driven noise patterns of the electric facilities are presented. And then, an electromagnetic generator which uses mechanical mass-spring vibration resonance are suggested and designed. Finally energy consumption of the presented smart sensor, which consists of MEMS vibration sensors, signal conditioning circuits, a low-power consumption micro-controller, and a ZIGBEE wireless tranceiver, are presented. The usefulness and limits of the presented electromagnetic generators in the field of electric facility monitoring are also suggested.

  • PDF

생산설비에서 에너지효율 산정 (Energy Efficiency Calculations of the Production Facilities)

  • 박형준;정찬수
    • 조명전기설비학회논문지
    • /
    • 제21권6호
    • /
    • pp.102-108
    • /
    • 2007
  • 원유가의 급등과 더불어 에너지자원에 대한 관심이 크게 증가 되었는데, 다양한 에너지관련 분야 중에서 먼저 선행되어야 하는 것은 기존의 설비에서 사용하고 있는 에너지가 효과적으로 사용되고 있는가를 판단하는 것이며, 이를 에너지 효율의 산정이라고 한다. 따라서 본 논문에서는 에너지의 주요 수요처중 하나인 제지 생산 플랜트의 한 공정에서 전력에너지와 열에너지에 대한 에너지효율을 계산하였다. 이때 전력에너지는 운전 중인 전동기의 부하에 따른 효율을 중심으로, 열에너지는 공정에서 입출력되는 열량을 중심으로 계산하였다. 즉 운전 중인 생산설비의 한 공정의 전력과 열에너지에 대해 각각 에너지효율을 산정하였으며 일부 에너지절감에 대한 방안도 제시하였다.

전력사용 시설물의 Pattern Search 법을 이용한 최적 접지 설계에 관한 연구 (A Study on the Optimal Grounding Design using Pattern Search Method for Electric Power Facilities)

  • 최홍규;김경철;최병숙
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2001년도 학술대회논문집
    • /
    • pp.173-180
    • /
    • 2001
  • Electric power facilities must have effective grounding to provide means to carry electric current into the earth under fault conditions and to prevent damage of equipment, Ignition, and electrocution of presonnel. nuts paper present an algorithm called the Pattern Search method for the optimal parameters selection of the grounding system. Computer simulation results used the CDEGS grounding analysis program verifying the effects of the grounding system design parameters obtained from this method show that the grounding systems are adequately designed.

  • PDF

전기사업법상 기술기준 개편 (Restructuring of Technical Regulation in Korea Electricity Business Act)

  • 김한수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.223-226
    • /
    • 2004
  • The Technical Regulation in Korea Electricity Business Act, shall be obeyed for design, installation and maintenance of electric facilities to ensure public safety and reliable supply of electricity. The Technical Regulation will be a basis for securing electrical safety, and also will be a governmental criterion for judging acceptance of the electric facilities from a safety viewpoint.

  • PDF

변전설비 간 상호작용을 고려한 지진응답해석 (Seismic Analysis of Substation Facilities Considering Interaction Effect)

  • 장정범;황경민;서용표;이근직
    • 한국지진공학회:학술대회논문집
    • /
    • 한국지진공학회 2006년도 학술발표회 논문집
    • /
    • pp.605-612
    • /
    • 2006
  • 765kV substation facilities are most important as electric power supply network in the 21 century. So, in order to prevent interruption of electric power supply under earthquake, 765kV substation facilities have to secure the safety against the earthquake. However, even though each substation facility is interconnected mutually, seismic interaction effect doesn't be considered in the initial design. Therefore, seismic capacity evaluation of 765kV substation facilities is carried out considering the seismic interaction effect on a basis of seismic design criteria for Korean transmission and substation facilities.

  • PDF

전력계통에서의 다목적댐 수력발전계획 (hydraulic-power generation of electricity plan of multi-Purpose dam in electric Power system)

  • 김승효;고영환;황인광
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 C
    • /
    • pp.1248-1252
    • /
    • 1999
  • To provide electricity power of good quality, it is essential to establish generation of electricity plan in electric power system based on accurate power-demand prediction and cope with changes of power-need fluctuating constantly. The role of hydraulic-power generation of electricity in electric power system is of importance because responding to electric power-demand counts or reservoir-type hydraulic-power generation of electricity which is designed for additional load in electric power system. So hydraulic-power generation of electricity must have fast start reserve. But the amount of water, resources of reservoir-type hydraulic-power generation of electricity is restricted and multi-used, so the scheduling of management by exact forecasting the amount of water is critical. That is why efficient hydraulic-power generation of electricity makes a main role on pumping up the utility of energy and water resource. This thesis introduced the example of optimal generation of electricity plan establishment which is used in managing reservoir-type hydraulic-power generation of electricity.

  • PDF

전기철도 전력시설 진단용 원격진단시스템 구축을 위한 네트워크 설계 (Network Design for Construction of Remote Diagnosis System for Power Facilities of Electric Railway)

  • 김재문;김양수
    • 전기학회논문지P
    • /
    • 제58권4호
    • /
    • pp.432-436
    • /
    • 2009
  • This paper is described that advanced study on network design of remote diagnosis system for power facilities of electric railway. In the field, it is very difficult for worker to diagnosis power facilities including catenary because workers should be maintenance on AC power supply. Therefore, to properly design on remote diagnosis system, we have searched the inside and outside of the country-related technology trends. Also we confirmed that required technologies to design interface technology required for the development of sensor devices and the USN network was designed in accordance with required skills. Throughout variety of requirements, we have development iRFS based ZA sensors and iRFM to receive data of sensor. Also CC2420 is applied as single-chip which used 2.4GHz IEEE802.15.4 compliant RF tranciver designed for low-power and low-voltage wireless applications for ZigBee communication.

345/154KV 전력소 구내의 자계 분포 특성 (Characteristic of Magnetic Fields Distribution in 345/154KV outdoor Substation)

  • 사재원;김성명;홍정표;전형태;한성진;주수원
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 A
    • /
    • pp.97-99
    • /
    • 1997
  • For two decades and more, a lot of research work on the biological effects of EMF (Electromagnetic Field) on human health have been reported. Electric facilities in a typical substation are the main source of magnetic field. This paper presents the measurement and analysis of magnetic field in 345/154KV outdoor substation. The magnetic field depends on the currents which distributed by electric facilities. The result of this paper will be able to be used as basic informations to reduce the level of EMF from the electric utility facilities.

  • PDF