• Title/Summary/Keyword: Dielectric test

Search Result 412, Processing Time 0.035 seconds

Analysis of Small Current Interruption Performance for $SF_6$ Gas Circuit Breaker ($SF_6$ 가스차단기의 소전류 차단성능 해석)

  • Kim, Hong-Kyu;Song, Ki-Dong;Chong, Jin-Kyo;Oh, Yeon-Ho;Park, Kyong-Yop
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.55 no.10
    • /
    • pp.528-533
    • /
    • 2006
  • To analyze the small current interruption performance for the gas circuit breakers, the gas density and electric field intensity should be calculated. In this paper, the FVFLIC method is used for the gas flow analysis and the FEM for the electric field analysis. Then, the dielectric withstanding voltage is evaluated by the empirical formulation or Streamer theory. By comparing the calculated dielectric strength with the test result, it is found that both methods show good prediction capability for the small current interruption performance. Especially, when both methods predict the same interrupting performance, the prediction is in accordance with the experimental result.

Thermal stabilities and dynamic mechanical properties of dielectric materials for thermal imprint lithography (임프린트 공법적용을 위한 절연재료의 열적, 기계적 성질)

  • Cho, Jae-Choon;Ra, Seung-Hyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.06a
    • /
    • pp.220-221
    • /
    • 2007
  • Recently, imprint lithography have received significant attention due to an alternative technology for photolithography on high performance microelectronic devices. In this work, we investigated thermal stabilities and dynamic mechanical properties of dielectric materials for thermal imprint lithography. Curing behaviours, thermal stabilities, and dynamic mechanical properties of the dielectric materials cured with various curing agent and spherical filler were studied using dynamic differential scanning calorimetry (DSC), thermogravimetric analysis (TGA), rheometer and universal test machine(UTM).

  • PDF

A study on the computer-controlled measuring device of complex dielectric constant (복소유전률 측정장치의 연구개발 - 컴퓨터제어 복소유전률 측정장치 -)

  • Nam, J.R.;Eum, S.O.;Kang, D.H.
    • Proceedings of the KIEE Conference
    • /
    • 1993.07b
    • /
    • pp.1206-1208
    • /
    • 1993
  • This paper is to study and realize a measuring device for complex dielectric constants. The device is consisted in order of interface unit, external RAM, programmable counter, D/A converter, measuring circuit, Sample & Hold circuit, A/D converter and related control circuits. Various excitation waves are digitalized and sent to the 4096 static RAM by personal computer. These data saved in the RAM are converted to analog excitation waves through D/A converter. The frequency of excitation wave is depend on the read-out speed of the RAM according to clock pulses. Such generated waves are applied to dielectrics under test and their responses are sampled and converted to digital data through A/D converter. The computer takes the digital data and calculates finally the complex dielectric constants. The frequencies for Measurement ranges from 0.04 Hz to 10 kHz.

  • PDF

A Study on the Dielectric Characteristics of Insulation Gases for a Sub-cooled Liquid Nitrogen System (이용률을 이용한 과냉질소 냉각시스템용 절연가스의 절연특성에 관한 연구)

  • Kang, Hyoung-Ku;Ko, Tae-Kuk
    • Progress in Superconductivity and Cryogenics
    • /
    • v.12 no.1
    • /
    • pp.52-55
    • /
    • 2010
  • A sub-cooled liquid nitrogen system is known as a promising method to develop high voltage superconducting apparatuses such as superconducting fault current limiters (SFCLs) and superconducting cables. To develop a high voltage superconducting machine adopting the sub-cooled liquid nitrogen system with a constant pressure. injecting a non-condensable gas is indispensable. In this study. the dielectric characteristics of insulation gases are investigated and analyzed by using electric utilization factors ($\xi$). It is found that the maximum electric field at sparkover that occurs with 50 % probability. $E_{MAX.50%}$ exponentially decreases as the S increases. This means that the $E_{MAX.50%}$ at sparkover can be estimated with the $E_{MAX.50%}$

A Study on Unsaturated Permeable Properties of the Soil-Bentonite Mixtures (Soil-Bentonite 혼합토의 불포화 투수특성 연구)

  • Kim Man-il
    • The Journal of Engineering Geology
    • /
    • v.15 no.2 s.42
    • /
    • pp.123-132
    • /
    • 2005
  • This study presents the results of a laboratory investigation performed to study physical properties of soil-bentonite mixtures through the vertical permeation test and dielectric measurement test using Frequency Domain Reflectometry system for the liner of waste landfill. For the laboratory experiments, geotechnical testing was conducted on pre-mixed soil-bentonite which is consisted of standard sand, weathered granite soil and bentonite for estimating physical parameters such as a volumetric water content, void ratio and dielectric constant. In experiment results, initial soil-bentonite mixing rate has an effect of change of volumetric water content. Also change of volumetric water content of a soil-bentonite mixture is clearly detected to measure a response of dielectric constant. In order to estimate an unsaturated permeable property of soil-bentonite mixtures, equations between volumetric water content and dielectric constant were derived from this study.

AC Breakdown Voltage Characteristics of SF6/CF4 in Uniform field (평등전계에서 SF6/CF4 혼합가스의 AC절연내력 특성)

  • Hwang, Chung-Ho;Park, Woo-Shin;Kim, Nam-Ryul;Huh, Chang-Su
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.20 no.4
    • /
    • pp.381-387
    • /
    • 2007
  • The excellent dielectric properties of $SF_6$(sulfur hexafluoride) have lead to its wide range of application in the field of high voltage insulation. Because there has been some recent concern regarding the environmental impacts of $SF_6$ binary gas mixtures, with $SF_6$ as the main component, have been the subject of active research. Scientists have long been interested in the possible use of gaseous fluorocarbons, including $CF_4$ (Carton Tetrafluoride), in high voltage applications due to their inert character and high dielectric strength. This paper presents experimental results concerning the AC breakdown characteristics lot various mixtures of $SF_6/CF_4$ in a test chamber and 25.8 kV GIS (Gas Insulation Switchgear) at practical pressures (0.1-04 MPa) and gap lengths (0.5 mm, 1 mm) in a test chamber. In the result, it was observed that an increase in the dielectric strength is attained through the addition of $SF_6$ to $CF_4$. It is possible to make an environment friendly gas insulation material while maintaining the dielectric strength by combing $SF_6$ and $CF_4$ which generates a lower level of the "global warming" effect.

Influence of Thermal Cycle Test of a 22.9 kV High Temperature Superconducting Cable System (22.9 kV 초전도케이블 시스템의 Thermal Cycle Test 영향)

  • Sohn, S.H.;Lim, J.H.;Yang, H.S.;Ryoo, H.S.;Choi, H.O.;Sung, T.H.;Kim, D.L.;Hwang, S.D.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.11a
    • /
    • pp.242-242
    • /
    • 2007
  • To verify the applicability of High Temperature Superconducting (HTS) cable system into the real grid, the HTS cable system with the specification of 22.9 kV, 1250 A, 100 m long was installed in the second quarter of 2006, and the long term field test has been in progress at the KEPCO's Gochang power testing yard. Apart from the conventional power cable, HTS cable system requires sufficient thermo-mechanical strength to endure a large temperature difference. To date, the KEPCO HTS cable system was cooled down and warmed to the room temperature several times to investigate the influence of thermal cycles experimentally. Dielectric properties, critical current dependance and heat losses were evaluated at each step of thermal cycle. The test results showed that thermal cycle did not induce the degradation of dielectric properties, and the critical current decreased to 5 % of the initial value.

  • PDF

gate stack구조를 이용한 LTPS TFT의 전기적 특성 분석

  • Jeon, Byeong-Gi;Jo, Jae-Hyeon;Lee, Jun-Sin
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.11a
    • /
    • pp.59-59
    • /
    • 2009
  • The efficiency of CMOS technology has been developed in uniform rate. However, there was a limitation of reducing the thickness of Gate-oxide since the thickness of Gate Dielectric is also reduced so an amount of leakage current is grow. In order to solve this problem, the semiconductor device which has a dual gate is used widely. This paper presents a method and a necessity for making the Gate Stack of TFT. Before Using test devices to measure values, stacking $SiN_x$ on a wafer test was conducted.

  • PDF

Development of High Voltage and High Energy Density Capacitor for Pulsed Power Application (펄스파워용 고전압 고에너지밀도 커패시터 개발)

  • 이병윤;정진교;이우영;박경엽;이수휘;김영광
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.52 no.5
    • /
    • pp.203-210
    • /
    • 2003
  • This paper describes high voltage and high energy density capacitor developed for pulsed power applications. The rated voltage of the developed capacitor is DC 22 [kV], the capacitance is 206 [$\mu$F] and the energy density is about 0.7 [kJ/kg]. Polypropylene film and kraft paper were used as the dielectrics. The ratio of the thickness of each dielectric material which consists of the composite dielectric structure, stacking factor and the termination method were determined by the charging and discharging tests on model capacitors. In terms of energy density, the developed capacitor has higher energy density compared with the products of foreign leading companies. In addition, it has been proved that the life expectancy can be more over 2000 shots through the charging and discharging test. The voltage reversal factor was 20%. This capacitor can be used as numerous discharge applications such as military, medical, industrial fields.

Breakdown characteristics with temperature variation on XLPE 6.9kV cable insulator at power plants (발전소 6.9kV급 XLPE 케이블 절연재의 온도에 따른 절연파괴 특성분석)

  • Park, Noh-Joon;Yang, Sang-Hyun;Lee, Ki-Joung;Kong, Tae-Sik;Kim, Hee-Dong;Park, Dae-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.79-79
    • /
    • 2010
  • In this paper, we present results of the dielectric breakdown test in various 6.9kV power cables used in power plants. The dielectric strength of the different conditioned cables was measured by placing the sliced cable sections in silicone oil bath with needle electrode. The results were analyzed by the Weibull distribution. The shape and scale parameters of the Weibull distribution for each cable sections under test were calculated and evaluated. Collected data base was applied to deterioration trend analysis and lifetime guide was also proposed.

  • PDF