Breakdown characteristics with temperature variation on XLPE 6.9kV cable insulator at power plants

발전소 6.9kV급 XLPE 케이블 절연재의 온도에 따른 절연파괴 특성분석

  • Published : 2010.06.16

Abstract

In this paper, we present results of the dielectric breakdown test in various 6.9kV power cables used in power plants. The dielectric strength of the different conditioned cables was measured by placing the sliced cable sections in silicone oil bath with needle electrode. The results were analyzed by the Weibull distribution. The shape and scale parameters of the Weibull distribution for each cable sections under test were calculated and evaluated. Collected data base was applied to deterioration trend analysis and lifetime guide was also proposed.

Keywords