• 제목/요약/키워드: 2-Stage compression heat pump

검색결과 23건 처리시간 0.026초

지역난방용 2단 압축 히트펌프 시스템 성능평가 (Performance Evaluation of a Two-Stage Compression Heat Pump System for District Heating)

  • 박차식;차동안;권오경
    • 설비공학논문집
    • /
    • 제24권7호
    • /
    • pp.585-590
    • /
    • 2012
  • The objective of this study is to investigate the performance of a two-stage compression heat pump system for district heating. The experimental setup of heat pump consists of compressor, condenser, evaporator, expansion device, intercooler, flash tank, oil separator and accumulator. The experimental evaluations on the two-stage compression cycle were carried out under various operating conditions which were heat source temperature, the degree of compressor inlet superheat, and intermediate pressure. The temperature ranges of unutilized energy as the heat source were used in the test conditions. As the heat source temperature increased from $10^{\circ}C$ to $30^{\circ}C$, the COP and heating capacity of the heat pump system increased by 22.6% and 45.8%, respectively. The performance of the two-stage heat pump system increased by 5.2% with the variation of the intermediate pressure in the same heat source temperature conditions.

하천수 열원 이용 2단압축 열펌프의 최적성능 및 효용 운전범위에 관한 시뮬레이션 연구 (Simulation on the Optimal Performance and Effective Operating Range of a 2-Stage Compression Heat Pump Using River Water)

  • 정태훈;박차식;김용찬
    • 설비공학논문집
    • /
    • 제20권5호
    • /
    • pp.295-303
    • /
    • 2008
  • The objectives of this study are to predict actual system performance and effective operating range of the 2-stage compression heat pump system using river water. An electronic expansion valve was applied to the simulation to analyze the effects of operating conditions on the system performance. The developed program was verified by comparing the predictions with the measured data. The results from the present model showed a good agreement with the measured data. In addition, the heat pump simulation was conducted by increasing condenser reservoir inlet temperature to investigate the benefits of the 2-stage compression over the 1-stage compression in the heating mode. The performance of the 2-stage compression cycle was better than that of the 1-stage compression when the inlet temperature of the condenser reservoir was higher than $40^{\circ}C$.

단단 및 2단 압축/흡수 히트펌스시스템의 성능 및 중요인자비교 분석 (Performance and Parameter Comparison between single stage and Two-Stage Compression/Absorption Heat Pump System)

  • ;박성룡
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.451-456
    • /
    • 2005
  • The mathematical model for the heat exchangers of absorber and desorber is made in the elementary control volume method and the thermodynamic properties of working fluid. water/ammonia mixture. are calculated by some fundamental subroutines in RefProp 7.0 and flash subroutines made by authors The simulation results show that two-stage cycle has higher COP than single stage if temperature lift is high: the performance of single stage compression cycle can be improved by increase of absorber pressure. but the performance of two-stage compression cycle can not be improved in this way : the compressor discharging temperature of two-stage compression is much lower than that of single stage cycle. which is very important to the safety operation of CA heat pump. Major parameter comparison between the cycles at their optimal configurations is also given.

  • PDF

하천수열원을 이용한 2단압축 열펌프의 난방성능 시뮬레이션 (Simulation on the Heating Performance of a 2-Stage Compression Heat Pump System Using River Water)

  • 박차식;김보현;김용찬;이영수;방기영
    • 설비공학논문집
    • /
    • 제17권11호
    • /
    • pp.1005-1013
    • /
    • 2005
  • The use of river water as a heat source of a heat pump has the advantage in the performance compared to the use of atmospheric air because the temperature variation of river water over the year is relatively small. In this study, the performance of the heat pump system using river water as a heat source was numerically investigated. A simulation model for the 2-stage compression heat pump system was developed with each component model composed of compressors, heat exchangers, a flash tank and electronic expansion devices. The peformance of the heat pump system using river water was improved by $50\%$ compared to that using atmospheric air in winter conditions.

하천수 열원 2단 압축 열펌프시스템의 부분부하 운전특성에 관한 실험적 연구 (An Experimental Study on the Part-Load Performance of a River Water Source 2-Stage Heat Pump)

  • 김지영;백영진;이영수;나호상
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2007년도 춘계학술대회B
    • /
    • pp.1964-1968
    • /
    • 2007
  • The river water heat source heat pump has the advantage in the performance compared to air source heat pump. Although its better performance, the large temperature difference between load and source makes system performance worse by nature. In this study, 2-stage compression is considered as the solution of this problem. Generally, heat pump is designed for maximum capacity rate, but it actually operates at part load condition in many cases. Therefore, an information on the part-load character is very important in view of the system overall performance. In this study, part-load performance tests of a R134a 2-stage compression heat pump were carried out over the river water and supply heating water temperature changes. The experimental results show that the system performance is influenced by the part load rates, river water temperature, load temperature, etc.

  • PDF

하수처리수를 이용한 2단 압축 열펌프 시스템의 운전특성에 관한 연구 (A Study on The Operation Characteristics of 2-Stage Compression Heat Pump using Treated sewage)

  • 김지영;백영진;이영수;장기창;나호상
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.299-303
    • /
    • 2008
  • The treated sewage temperature is about $5^{\circ}C$ lower in summer and $5{\sim}10^{\circ}C$ higher in winter than ambient air. It can be used heat pump heat source and is good heat source on high performance of heat pump. In this study, to develop 100RT 2-stage compression heat pump use treated sewage water heat source and system applies to sewage disposal plant. Although heat pump is better performance, the large temperature difference between load and source makes the performance degradation of a heat pump. To solve this problem screw 2-stage compression is considered. The experiment was focused on the system operating performance variations over supply water and treated sewage water a temperature in the field. The results show that system of heating performance is higher then general heat pump and is enough to supply a hot water of $70^{\circ}C$.

  • PDF

하천수 열원 2단압축 열펌프의 최적 중간압에 관한 실험적 연구 (An Experimental Study on the Optimal Intermediate Pressure of a 2-Stage Compression Heat Pump Using River Water)

  • 박차식;정태훈;주영주;김용찬
    • 설비공학논문집
    • /
    • 제21권6호
    • /
    • pp.333-339
    • /
    • 2009
  • The objective of this study is to predict optimal intermediate pressure of a 2-stage compression heat pump system using river water. To determine the maximum performance of the 2-stage compression heat pump system, the experimental evaluations on the 2-stage compression cycle were carried out under various operating conditions. Electronic expansion valves were applied to control intermediate pressure and superheat. Based on the experimental data, an empirical correlation for predicting optimal intermediate pressure which considering cycle operating parameters was developed. The present correlation was verified by comparing the predicted data with the measured data. The predictions showed a good agreement with the measured data within a relative deviation of ${\pm}4%$ at various operating conditions.

2단 압축 수열원 열펌프 시스템의 부분부하 운전특성에 관한 연구 (A study on the part-load performance of 2-stage water source heat pump)

  • 이영수;백영진
    • 한국지열·수열에너지학회논문집
    • /
    • 제5권1호
    • /
    • pp.13-17
    • /
    • 2009
  • The river water heat source heat pump has the advantage in the performance compared to air source heat pump. In this study, an experimental study on a 2-stage heat pump, which is designed to utilize a river water heat source, were carried out. Generally, a heat pump is designed for maximum capacity rate, but it actually operates at part load condition in most cases. Therefore, an information on the part-load characteristic is very important in view of the system overall performance. In this study, part-load performance tests of a R134a 2-stage compression heat pump were carried out over the river water and supply heating water temperature changes.

  • PDF

저온수열원이용 열펌프시스템의 전처리 및 성능분석 (Performance Analysis and Prior-Treatment of Heat Pump System with Low-Temperature Water Heat Source)

  • 박성룡;장기창;이상남;라호상;박준택
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2000년도 춘계학술대회논문집B
    • /
    • pp.258-263
    • /
    • 2000
  • River water is higher in temperature than the surrounding environment during the winter. It is highly suitable a heat source for heat pump system. Despite its suitability, however, it is not widely used, due to its fouling and corrosive nature in heat exchanger tubes of evaporator. It is designed prior-treatment system which come into direct contact with the river water, such as auto-seamer, ozone generator for bactericidal test and auto-cleaning system. And it is analyzed treatment effects for its operation. It is designed two-stage compression heat pump system using R-134a with heating load 35.16kW, ad analyzed its performance. As a result it is obtained 3.08 COP when mid-point pressure is 1,200kPa, and bypass ratio of flowing refreigerant to high-stage compressor is 25.1%

  • PDF

스크류 열펌프 시스템의 운전제어 방안에 관한 연구 (A Study on the Operating Control of a Heat Pump System with Screw Compressors)

  • 박준택;이영수;김지영;채규정;양희정
    • 설비공학논문집
    • /
    • 제25권3호
    • /
    • pp.168-172
    • /
    • 2013
  • A preliminary performance test of a 30RT 2-stage screw heat pump was carried out in order to develop a high performance large-scale unutilized energy source heat pump system, which will be used for district heating and cooling. In this study, two issues of the system operating control were investigated. The first issue is the mode switching control from 1-stage to 2-stage. A stable 2-stage heating operation is guaranteed, only if the load-side water inlet temperature is over a certain value, where the 1-stage heating operation should be done first from a cold start. The second issue is oil level control. An oil shortage problem in the low stage compressor, which depends on the degree of suction superheat, was solved by a proper oil level control scheme.