DOI QR코드

DOI QR Code

Performance Evaluation of a Two-Stage Compression Heat Pump System for District Heating

지역난방용 2단 압축 히트펌프 시스템 성능평가

  • Park, Cha-Sik (School of Mechanical Engineering, Hoseo University) ;
  • Cha, Dong-An (Energy System R&D Group, Korea Institute of Industrial Technology) ;
  • Kwon, Oh-Kyung (Energy System R&D Group, Korea Institute of Industrial Technology)
  • 박차식 (호서대학교 기계공학부) ;
  • 차동안 (한국생산기술연구원 에너지시스템연구그룹) ;
  • 권오경 (한국생산기술연구원 에너지시스템연구그룹)
  • Received : 2012.04.10
  • Published : 2012.07.10

Abstract

The objective of this study is to investigate the performance of a two-stage compression heat pump system for district heating. The experimental setup of heat pump consists of compressor, condenser, evaporator, expansion device, intercooler, flash tank, oil separator and accumulator. The experimental evaluations on the two-stage compression cycle were carried out under various operating conditions which were heat source temperature, the degree of compressor inlet superheat, and intermediate pressure. The temperature ranges of unutilized energy as the heat source were used in the test conditions. As the heat source temperature increased from $10^{\circ}C$ to $30^{\circ}C$, the COP and heating capacity of the heat pump system increased by 22.6% and 45.8%, respectively. The performance of the two-stage heat pump system increased by 5.2% with the variation of the intermediate pressure in the same heat source temperature conditions.

Keywords

References

  1. Kim, Y. K., Lee, T. W., and Kim, D. H., 2011, An analysis of heating operation characteristics of user-side facilities in the district heating system, Proceedings of the SAREK winter annual conference, pp. 75-78.
  2. Kim, J. W., Baik, Y. J., Lee, Y. S., Cho, S. H., and Chung, D. H., 2011, An experimnetal study on the performance of heat exchanger for district heating substation, Proceedings of the SAREK summer annual conference, pp. 1331- 1336.
  3. Byun, J. K., Choi, Y. D., and Shin, J. K., 2011, Study on the development of optimal heat supply control algorithm in district heating apartment building according to the variation of outdoor air temperature, Proceedings of the SAREK summer annual conference, pp. 1222- 1226.
  4. Hong, S. K., Lyu, S. B., and Cho, S. H., 2011, An application study of predictive optimal control for apartment house by district heating system, Proceedings of the SAREK summer annual conference, pp. 527-532.
  5. Shu, H., Duanmu, L., Li, X., and Zhu, Y., 2010, Energy-saving judgment of electric-driven seawater source heat pump district heating system over boiler house district heating system, Energy and buildings, pp. 889-895.
  6. Eriksson, M. and Vamling, L., 2007, Future use of heat pumps in Swedish district heating systems: Short- and long-term impact of policy instruments and planned investments, Applied energy, pp. 1240-1257.
  7. Comakli, K., Yuksel, B., and Comakli, O., 2004, Evaluation of energy and exergy losses in district heating network, Applied energy, Vol. 24, pp. 1009-1017. https://doi.org/10.1016/j.applthermaleng.2003.11.014
  8. Zubair, S. M., Yaqub, M., and Khan, S. H., 1996, Second-law-based thermodynamic analysis of two-stage ad mechanical subcooling refrigeration cycles, International Journal of Refrigeration, Vol. 19, No. 8, pp. 506-516. https://doi.org/10.1016/S0140-7007(96)00045-X
  9. Ratts, E. B. and Brown, J. S., 2000, A generalized analysis for cascading single fluid vapor compression refrigeration cycles using an entropy generation minimization method, International Journal of Refrigeration, Vol. 23, No.5, pp. 353-365. https://doi.org/10.1016/S0140-7007(99)00070-5
  10. Park, C. S., Jung, T. H., Joo, Y. J., and Kim, Y. C., 2009, An experimental study on the optimlal intermediate pressure of a 2-stage compression heat pump using river water, SAREK, Vol. 21, No. 6, pp. 333-339.
  11. Kim, S. H., 2011, Applications instnance of heating and cooling system using the sewage water, Proceedings of the SAREK summer annual conference, pp. 160-165.
  12. Lee, S. R., Noh, K. C., Park, D. Y., and Oh, M. D., 2009, A study on utilization of temperature difference energy from waste water in urban building, Proceedings of the SAREK winter annual conference, pp. 537-543.