• 제목/요약/키워드: 화재성상

검색결과 130건 처리시간 0.023초

아트리움 공간에 있어서 화재온도성상에 관한 이론해석 (The Analytical Study of Fire Properties in Atrium Space)

  • 김화중;이지희;최금란;김경례
    • 한국전산구조공학회:학술대회논문집
    • /
    • 한국전산구조공학회 1993년도 가을 학술발표회논문집
    • /
    • pp.113-119
    • /
    • 1993
  • Atrium being on fire, the flame is spread vertically, the methods of fire protection and the standards of security are different respectively. Therefore, in the case of atrium, it has many problems on the fire protection and the application of statute according to the space properties. So it is important to analysis, atrium being on fire, fire properties to space properties. From these points of view, the purpose of this study is to analysis the fire properties of atrium .

  • PDF

무피복 FR강을 사용한 철골주차장의 화재시 거동성상 예측에 관한 연구 (The Study on Predicting Behavior of Open Car Parks Using The Bare FR Steel Exposed to Fire)

  • 김화중;이지희;이창준;추연희
    • 한국전산구조공학회:학술대회논문집
    • /
    • 한국전산구조공학회 1998년도 봄 학술발표회 논문집
    • /
    • pp.398-405
    • /
    • 1998
  • This study investigated to the stability of open car parks below $600^{\circ}C$, as to predict behavior of bare FR steel structure noosed to fire. Especially, This study evaluated deformation of steel structure members of open car parks, considering change of material property by temperature. From the numerical analysis, we know the fact that the deformations comparing of standard values are stable to use the FR steel below 600 $^{\circ}C$ in open car parks plan

  • PDF

실물화재실험을 통한 공동주택의 화재안전성 연구 (The Real Scale Fire Test for Fire Safety in Apartment Housing)

  • 유용호;권오상;김흥열
    • 한국화재소방학회논문지
    • /
    • 제23권5호
    • /
    • pp.57-65
    • /
    • 2009
  • 본 연구에서는 화재 시 많은 인명피해가 예상되는 공동 주택을 대상으로 단위공간별 화재 성상을 예측하기 위한 실물화재실험을 실시하였다. 실험 모델 주택을 구성하고 있는 내부 가연물을 선정한 후 각 단위 품목에 대한 화재특성 실험을 실시하였으며, 주방, 거실, 침실, 공부방 등 4종류의 단위 공간으로 구분하여 각각 실물화재실험을 실시하였다. 실험결과 침실의 경우 점화 후 약 5분이 경과되었을 때 플래쉬오버 상태에 이르게 되어 매우 급격한 성장을 보였으며, 최대 열방출율 약 7,433.3kW, 최대 CO 578.6ppm, 최대 $CO_2$ 1.25%, 내부 최대온도 $1,350^{\circ}C$로 측정되었다. 특히, 화재 발생 초기에 가연 공간에서 화재의 진화가 이루어지지 않으면 약 3분 내에 인체에 급격한 피해를 줄 수 있는 한계온도 이상으로 화재가 성장하기 때문에 신속한 초기 대응이 필요함을 확인하였으며, 장롱, 침구류 등 비교적 화재가 급속히 전이 될 수 있는 가연물량이 다수 배치되어 있는 침실에서 용도별 가연 공간 중 가장 위험도가 높은 것으로 측정되었다. 단위 가연물에서 발생되는 유독가스가 임계수준 이상으로 발생되어 이로 인해 인체에 심각한 피해를 줄 수 있을 것으로 판단된다. 이러한 실물화재실험에서 얻어낸 결과는 향후 화재확대 예측 시뮬레이션 결과와 비교함으로써 각 용도별 공간에서의 화재 확산 예측에 적용될 수 있을 것이다.

건축물의 적재가연물 특성에 관한 연구 -대형서점의 적재가연물 연소발열성상- (Characterization of Live Fire Load in Buildings - Heat Release Characteristics of Typical Live Fire Load in Bookstore -)

  • 남동군;장곡견웅이;정종진;임우섭;사공성호
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 추계학술논문발표회 논문집
    • /
    • pp.3-6
    • /
    • 2008
  • Heat release characteristics of live fire load are an important parameter for performance oriented fire safety design of a building. While investigations have been carried out on the fire load and its burning behavior in office, residential and commercial buildings and so on, little effort has been paid for the rational treatment of fire load in bookstore. In this report, burning behavior of typical combustible objects in bookstore are studied by measuring heat release rates of bookshelf with book.

  • PDF

건축물의 적재가연물 특성에 관한 연구 -우체국 적재가연물의 연소성상 - (Characterization of Live Fire Load in Buildings - Heat Release Characteristics of Typical Live Fire Load in Post Office Building -)

  • 남동군;장곡견웅이;사공성호;정종진
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 춘계학술논문발표회 논문집
    • /
    • pp.7-10
    • /
    • 2008
  • Heat release characteristics of live fire load are an important parameter for performance oriented fire safety design of a building. While investigations have been carried out on the fire load and its burning behavior in office, residential and commercial buildings and so on, little effort has been paid for the rational treatment of fire load in post office buildings in Japan. In this report, burning behavior of typical combustible objects in post office buildings are studied by measuring heat release rates of plastic palettes with and without postal envelopes or packages and special containers loading numbers of palettes. The test results suggest that dynamic heat release rate is highly dependent on the condition of palettes especially if they load appropriate amount of postal envelopes or not.

  • PDF

업무시설의 화재성상예측을 위한 가연물 조사 및 화재하중 제안 (A Suggestion on the Fire load and Combustible survey for Prediction of Fire in office Facilities)

  • 이병흔;권영진
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2019년도 추계 학술논문 발표대회
    • /
    • pp.98-99
    • /
    • 2019
  • In Korea, buildings are becoming skyscrapers due to restrictions on land. The performance-oriented design was introduced in 2009 for fire safety of such buildings, but the application of the combustible data through engineering design and experiment is a poor reality. Large buildings are used for complex purposes, especially since the density of the office facilities is high, the study conducted a study on the combustible materials of the office facilities and the thermal speed and fire load of the main combustibles of the office facilities were calculated.

  • PDF

바이메탈식 온도센서를 적용한 건조설비에서의 화재 위험성 연구 (Study of the Fire Risk Caused by the Use of a Bimetal type Thermometer in the Drying Equipment)

  • 박남규;김진표;남정우;박종택;송재용
    • 한국화재소방학회논문지
    • /
    • 제31권3호
    • /
    • pp.73-78
    • /
    • 2017
  • 본 논문에서는 바이메탈식 온도센서를 적용한 건조설비에서의 화재 위험성에 대하여 연구하였다. 건조설비는 산업현장 등에서 광범위하게 사용되고 있으며, 건조 대상물이 가열될 때 발생하는 가연성 가스 및 증기에 의한 폭발 및 화재 등이 일어나기 용이하기 때문에 구조와 사용방법 등에 대한 규제가 엄격하게 이루어지고 있지만 부적합한 온도센서를 활용한 건조로 등의 내부온도 측정시 정확한 온도 측정이 이루어지지 못하는 경우에는 그만큼 화재 위험성이 증가하게 된다. 따라서 본 논문에서는 건조설비에 광범위하게 사용되고 있는 바이메탈식 온도센서의 구조를 분석하고, 측정 대상물의 성상에 따른 온도 측정 실험을 수행하였다. 측정 대상물에 따른 온도 측정 결과, 기체 및 고체에 대한 온도 측정에 있어서는 실제 온도에 비해 낮은 온도로 측정되었으며, 액체 대상물의 경우에는 비교적 정확한 온도 측정이 가능하였다. 이러한 실험 결과로부터 바이메탈식 온도센서는 기체 및 고체의 온도 측정에는 부적합하며, 액체의 온도 측정에 보다 적합한 특성을 나타내었다.

스프링클러 소화설비의 목조문화재 소화성능에 관한 연구 (The Study of Fire Suppression Capability of Sprinkler System for Wooden Cultural Properties)

  • 노삼규;함은구;김동철
    • 한국화재소방학회논문지
    • /
    • 제25권6호
    • /
    • pp.51-57
    • /
    • 2011
  • 본 연구는 국내 목조문화재의 화재에 대한 수계 자동소화시스템 중에 범용의 스프링클러 소화시스템에 대한 소화성능을 소화실험을 통하여 확인해 보았다. 목조문화재는 가연성의 재질로 구성되어 있어 화재에 취약하며, 방화의 경우 화재의 성상 초기부터 화원의 규모가 커질 수 있다. 본 실험에 적용된 스프링클러 헤드는 방사압 1 bar, 방수량 80 lpm의 사양을 지니고 있다. 소화실험의 유형은 화원의 규모별, 문화재 규모별로 각각 둘로 구분하여 소화성능을 실험하였다. 소화실험을 통해 확인된 사항은 천장이 높으면 소화 시간이 지연되는 결과가 발생하며, 화원의 규모가 2단위에서는 소화는 가능하였지만 소화가 지연되는 것으로 나타났다. 그 결과 천장이 높고, 화원의 규모가 2단위 이상이 되면 소화성능이 낮을 것으로 예측된다. 실제 목조문화재의 화재 성장 환경이 소화실험 모형보다 유리하다는 측면을 고려해야 한다. 그러므로 스프링클러 소화설비를 목조문화재에 적용 할 때에 헤드간 거리 헤드의 선정 등 충분한 검증이 요구된다.

목조 건축 문화재 적심부 실물화재 실험을 통한 연소 특성 연구 (A Study on Characteristics of Roof 'Jucsim' Structure Combustion Real Scale Fire Test on Wooden Structure Heritage Building)

  • 노삼규;함은규
    • 한국화재소방학회논문지
    • /
    • 제24권1호
    • /
    • pp.95-102
    • /
    • 2010
  • 본 연구에서는 목조한옥구조 적심부 실물화재 실험을 통하여 목조건축문화재 지붕 상부구조 내부의 연소특성을 분석하였다. 실험체는 숭례문 지붕 내부 구조의 특성을 고려하여 제작하였으며, 기와를 제외한 강회, 보토, 적심, 개판 순으로 구성하고 위치별로 열 측정 장치를 설치하였다. 첫 번째 실험은 목조건축 문화재의 적심 지붕구조를 가지는 경우 연소 및 화재 성상을 알아보았다. 두 번째 실험은 화염이 직접 접촉하는 서까래와 천정 개판 상 하부에 방염도료를 도색하여 방염도료 내화 성능을 알아보았다. 세 번째 실험은 적심부와 개판 사이에 방염천을 넣어 적심부 및 강회층에 화염 전파에 어떤 영향을 미치는지 알아보았다. 그 결과 목조 한옥구조 지붕의 적심부 화재 전파는 외부 화염의 제거 후에도 내부에 장시간에 걸쳐 연기와 화염이 계속 진행함을 보였다. 또한, 방염도료의 경우 내열효과를 보였으며, 방염천의 경우 화염전파온도를 $100^{\circ}C$ 이하로 유지할 때 적심부로부터 화염전파차단 효과를 보였다.

Performance-based Fire Protection Design of Domestic Super High-rise Buildings - Evaluation by ASET and RSET -

  • Roh, Hyeong-Ki
    • 한국방재학회 논문집
    • /
    • 제11권2호
    • /
    • pp.9-13
    • /
    • 2011
  • 초고층 빌딩 건설 시 요구되는 성능위주 소방설계는 인명 안전을 확보할 수 있는 능동적인 대책으로서 화재 위험성을 평가하고, 공학적 분석 결과를 토대로 하여 방재시스템을 구축하는 것으로 관련 법규 및 기준을 적용하여 수행하는 기존의 설계 방식보다 인명 안전의 확보에 있어서 매우 효율적이고 타당하다고 보여진다. 본 연구는 피난 요구 시간인 RSET과 피난이 가능한 시간인 ASET에 의한Time-line Analysis을 적용하였으며 또한 ASET과 RSET을 비교, 분석하기 위하여 화재 및 피난 시뮬레이션을 수행하였다. 연구 결과, 스프링클러설비가ASET을 증가시켰으며, 화재감지 및 경보시간의 단축이 RSET을 효과적으로 감소시켜 주고 있다. 단축된 시간은 인명의 안전을 확보하는데 많은 영향을 미치는 것으로 확인되었다. 또한 소화설비, 화재 감지 및 경보설비가 정상적으로 작동되도록 유지 관리되는 것도 중요한 것으로 파악되었다. 화재의 성상을 데이터 베이스화하고 피난 대응 프로그램 등이 구축되면 성능위주 설계에 유용한 자료로 이용될 수 있다.