• Title/Summary/Keyword: 태양열 온수 시스템

Search Result 76, Processing Time 0.029 seconds

Underground hot water heating system development using exhaust gas heat in the hot air heater (온풍난방기의 배기열을 이용한 지중난방용 온수시스템 개발)

  • 김영중;이건중;신정웅;유영선;장진택
    • Proceedings of the Korean Society for Bio-Environment Control Conference
    • /
    • 1999.11a
    • /
    • pp.100-103
    • /
    • 1999
  • 온풍난방은 우리 나라 대부분의 온실난방지역에서 가장 많이 채택하고 있는 온실난방방법으로 간주되고 있다. 온풍난방은 기본적으로 화석연료를 연소열로 변환시켜 온실난방에 사용하는 방법으로 온수난방, 태양열난방 보다 열효율이 높다. 가장 보편적 온실난방열원으로는 경유나 보일러등유를 연소실에서 연소하여 열교환기를 거친 후 온풍기의 상부에 부착되어 있는 송풍팬으로 강제적으로 온실 내로 온풍을 불어넣는다. (중략)

  • PDF

Evaluation of thermal performance for solar cooling and heating system (태양열 냉.난방 및 급탕 시스템 열성능)

  • Kwak, Hee-Youl;Joo, Hong-Jin;Lee, Ho
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2009.04a
    • /
    • pp.203-208
    • /
    • 2009
  • This paper presents demonstration study results derived through field testing of a solar assisted cooling and heating system for the library of a cultural center building located in Gwangju, Korea. The area of demanded cooling and heating for building was about 350m2. Solar hot water was delivered by means of a 200m2 array of evacuated tubular solar collector (ETSC) to drive a single-effect (LiBr/H2O) absorption chiller of 10RT nominal cooling capacity. From March in 2008 to February in 2009, demonstration test were performed for solar cooling and heating system. After experiments and analysis, this study found that solar thermal system was 84% for the solar hot water supply and 12% for space heating and 4% for space cooling.

  • PDF

A Study of Bubble Pump that is applied Solar Heating Water System (태양열 온수 시스템에 적용한 기포펌프의 동작특성에 관한 연구)

  • Park, G.T.;Song, L.;Shim, K.J.;Jeong, H.M.;Chung, H.S.
    • Journal of Power System Engineering
    • /
    • v.11 no.4
    • /
    • pp.32-37
    • /
    • 2007
  • Regarding the need of energy in advance and the depletion of fossil fuel energy, all researches around the world now are trying to extract energy from many alternative sources especially the renewable one. Solar, ocean tidal, wind and geothermal energy are renewable energy fields which many researches are focused on. This paper explains about effort to replace electric pump used in solar water heating system by bubble pump. The utilization of bubble pump in this system is very efficient since it needs heat energy for its operation that can be obtained easily. In addition, it can also simplify the construction of the system. Bubble pump also functions as a controller to circulate water inside the system. Before the installation of bubble pump, the special quality and performance of bubble pump should be analyzed. The result got from the analysis could show the fluctuation of water flow rate occurred because it sensitively reacts to the heat quantity. Here the heat quantity is taken from the solar that, as we know, is not stable in a whole day. Problems often occurred are the flow rate in this system is very low moreover it could be stop if the pressure exceeds the limit.

  • PDF

The R&D of hot water production by the combination of solar thermal and a large sized flower cooling system(I) (꽃 저장용 냉장시스템과 태양열 복합형 급탕기 개발연구(I))

  • Jung, Hyun-Chai;Kim, Ki-Sun;Sun, Kyung-Ho
    • Solar Energy
    • /
    • v.12 no.3
    • /
    • pp.84-93
    • /
    • 1992
  • Solar assisted heat pump with freon circulating system has been developed. Revising the cool chamber(flower storage) with the solar thermal hot water producing system, the more amount of hot water can be produced, which can be even used for room panel heating. The compressor was cooled by water jaket instead of air cooled so that the system energy efficiency was improved quite well.

  • PDF

A Study on Heat and Mass Transfer with the Different Flows in a Solar Desiccant Cooling System (태양열제습냉방시스템에서의 유량에 따른 열전달 및 물질전달에 관한 연구)

  • Eflita, Yohana;Choi, Kwang-Hwan
    • Journal of the Korean Solar Energy Society
    • /
    • v.30 no.5
    • /
    • pp.17-24
    • /
    • 2010
  • 태양열 제습냉방은 액체흡수제를 이용한 냉각효과로 기존의 전기에너지를 가능케 하는 해결책중 하나이다. 따라서 태양열을 거의 활용하지 않는 여름에 가열온수를 열원으로 활용하여 쾌적조건을 구현하는 본 연구의 대상인 태양열냉방시스템은 제습기와 재생기로 크게 이루어져 있다. 본 논문은 제습기의 유량 변화에 따른 열전달 및 물질전달의 변화를 실험과 이론적 해석으로 규명하고 있는데, 흐름의 양상은 병렬형과 대향류형을 대상으로 하고 있다. 실험결과와 이론해석이 비교적 잘 일치하였으며, 대향류형이 병렬형보다도 물질전달 면에서 유리하게 나타났으며, 입 출구의 엔탈피 차이에서도 크서 열전달에서도 우수한 것으로 나타났다. 또한 그 차이를 본 논문에서는 나타내었으며, 일정한 높이나 길이 이상에서는 항상 일정함을 알 수 있었다. 따라서 본 논문의 결과들은 제습기의 유동흐름을 통한 태양열냉방시스템 중 제습기의 설계 및 성능 향상에 도움을 줄 것이다.

Verification Experiment and Analysis for 6kW Solar Water Heating System(Part 3 : Optimum Design and Economic Evaluation) (6kW급 태양열 온수급탕 시스템의 실증실험 및 분석(제3보 최적설계 및 경제성평가))

  • Choi Bong Su;Lee Bong Jin;Kang Chaedong;Hong Hiki
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.1
    • /
    • pp.16-24
    • /
    • 2005
  • The goal of the present paper is to show the optimum design and operation conditions on 6 kW solar water heating system by using computer simulation with verified modelling. As the object functions, we took not only the amount of acquired and auxiliary heat but LCC, which has a relative importance and decisive role in economy. As expected, the maximum heat is acquired at the slope of collector with the equal degree to the latitude, facing the south. The capacity increase of the circulation pump and the storage tank lead to the increase of acquired heat and the decrease of auxiliary heat, but do not necessarily give economical advantages owing to additional electrical power consumption. In the present system, the minimum LCC can be obtained at the storage tank volume of 450 L and the mass flow rate of 0.344 kg/s.

The Development of Monitoring System for Performance Evaluation of Solar Hot Water Heater (태양열 온수기 성능평가 위한 모니터링 시스템 개발)

  • Kim, Jae-Yeol;Choi, Seung-Hyun;Yang, Dong-Jo
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2009.11a
    • /
    • pp.417-417
    • /
    • 2009
  • The application of solar energy, in the field of alternative energy, was on the increase tendency. In the case of advanced nations, through continuous R&D, solar hot water heater with high efficiency has been used for the house and the industrial process on business, advanced nations were reached up the experimental stage of solar generation system. But, the actual circumstance of the domestic has been not accomplished the popularization of solar hot water heater and the settlement of it which is the fundamental stage of the solar energy usage. This trouble, the domestic was flooded with small enterprise for producing solar hot water heater, was caused by the popularization and the production without verification of performance. To supply the monitoring program for evaluating solar hot water heater, this research was purpose to improve the technical development of the enterprise for producing solar-heat hot-water-boiler and served as an aid for the enlargement and the popularization on solar energy.

  • PDF

Design Modification of a Thermal Storage Tank of Natural-Circulation Solar Water Heater for a Pressurized System (자연순환형 태양열 온수기 축열조의 압력식 설계 개조)

  • Boo, Joon-Hong;Jung, Eui-Guk
    • Journal of the Korean Solar Energy Society
    • /
    • v.27 no.3
    • /
    • pp.45-54
    • /
    • 2007
  • For a conventional natural-circulation type solar water heater, the pressure head is limited by the height between the storage tank and hot water tap. Therefore, it is difficult to provide sufficient hot water flow rate for general usage. This study deals with a design modification of the storage tank to utilize the tap-water pressure to increase hot-water supply Based on fluid dynamic and heat transfer theories, a series of modeling and simulation is conducted to achieve practical design requirements. An experimental setup is built and tested and the results are compared with theoretical simulation model. The storage tank capacity is 240 l and the outer diameter of piping was 15 mm. Number of tube turns tested are 5, 10, and 15. Starting with initial storage tank temperature of $80^{\circ}C$, the temperature variation of the supply hot water is investigated against time, while maintaining minimum flow rate of 10 1/min. Typical results show that the hot water supply of minimum $30^{\circ}C$ can be maintained for 34 min with tap-water supply pressure of 2.5 atm, The relative errors between modeling and experiments coincide well within 10% in most cases.

분산형 발전시스템의 기술개발 동향 - 소형 스털링 엔진 발전시스템 기술개발 동향

  • Go, Jun-Seok;Park, Seong-Je;Kim, Hyo-Bong;Hong, Yong-Ju
    • 기계와재료
    • /
    • v.26 no.1
    • /
    • pp.28-36
    • /
    • 2014
  • 소형 스털링엔진 발전시스템은 전력을 생산하기 위해 스털링엔진을 적용하는 시스템으로, 천연가스가 풍부한 북유럽 국가들을 중심으로 난방, 온수와 전기에너지를 동시에 공급할 수 있는 가정용 소형 열병합 발전시스템으로 각광받고 있다. 외연기관인 스털링엔진은 연료의 종류에 제한을 받지 않기 때문에, 태양열, 폐열, 천연가스 등의 다양한 열원을 이용한 발전시스템에 적용이 가능하다. 수 kW급의 스털링엔진을 적용한 소형 열병합 발전시스템의 기술개발 동향을 소개하고자 한다.

  • PDF

Performance Analysis of Solar Thermal System with Heat Pump for Domestic Hot Water and Space Heating (온수 급탕 및 난방을 위한 히트 펌프 태양열 시스템의 성능 분석)

  • Sohn, Jin-Gug
    • Journal of the Korean Solar Energy Society
    • /
    • v.38 no.5
    • /
    • pp.49-62
    • /
    • 2018
  • This study aims to analyze the performance of solar thermal system with heat pump for domestic hot water and heat supply. There are four types of system. Systems are categorized based on the existence of a heat pump and the ways of controlling the working fluid circulating from the collector. Working fluid is controlled by either temperature level (categorized as system 1 and 2) or sequential flow (system 3 and 4). Heat balance of the system, the solar fraction, hot water and heating supply rates, and performance of heat pump are analyzed using TRNSYS and TESS component programs. Technical specifications of the main facilities are as follow; the area of the collector to $25m^2$, the volumes of the main tank and the buffer tank to $0.5m^3$ and $0.8m^3$, respectively. Heating capacity of the heat pump in the heating mode is set to 30,000 kJ / hr. Hot water supply set 65 liters per person each day, total heat transfer coefficient of the building to 1,500 kJ / kg.K. Indoor temperature is kept steadily around $22^{\circ}C$. The results are as follows; 6 months average solar fraction of system 1 turns out to be 39%, which is 6.7% higher than system 2 without the heat pump, indicating a 25% increase of solar fraction compared to that of system 2. In addition, the solar fraction of system 1 is 2% higher than that of system 3. Hot water and heating supply rate of system 1 are 93% and 35%, respectively. Considering the heat balance of the system, higher heat efficiency, and solar fraction, as whole, it can be concluded that system 1 is the most suitable system for hot water and heat supply.