• 제목/요약/키워드: 열교환기 휜

검색결과 86건 처리시간 0.022초

Experimental study of performance characteristics of various fin types for fin-tube heat exchanger (휜-관 열교환기에 있어서 각종 휜 형상의 성능 특성에 관한 실험적 연구)

  • Yoon, Baek;Kim, Young-Saeng;Park, Hwan-Young;Park, Hyun-Yeon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • 제11권4호
    • /
    • pp.484-491
    • /
    • 1999
  • Air side heat transfer and pressure drop for ø9.52 fin-tube heat exchanger with various types of slit and louver fins were measured, and compared with wave-slit fin. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively. Actual heat exchanger was tested using water, and the tests were performed for 2 row heat exchangers with 3 different fin spacings, 1.3, 1.5 and 1.7mm. The overall performance of the enhanced fins was evaluated by comparing heat transfer coefficient with respect to fan power.

  • PDF

Convective Heat Transfer Correlations for the Compact Heat Exchanger with Circular Tubes and Flat Tubes-Plate Fins (원형관 및 납작관-평판휜 형상의 밀집형 열교환기에 대한 대류열전달 상관관계식)

  • Moh, Jeong-Hah
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • 제34권3호
    • /
    • pp.291-299
    • /
    • 2010
  • Aspect-ratio-based numerical analysis is carried out to investigate the air-side convective heat transfer characteristics in compact heat exchangers with circular tubes and flat tubes-plate fins. The RNG $k-{\varepsilon}$ model is adopted for turbulence analysis. The numerical analysis is carried out for aspect ratios ranging from 3.06 to 5.44 and for Reynolds numbers ranging from 1,000 to 10,000. The calculated results indicate a correlation between the friction factor and Colburn j factor in the compact heat exchanger system for the range of aspect ratios under consideration. The results obtained for circular tubes and flat tubes-plate fins in this study can be utilized to realize the optimal design of an air conditioning system.

A Study on the Thermal Performance of Fin and Tube Sensible Heat Exchanger according to Fin Geometry and Flowrate (휜 형상 및 유량에 따른 휜-관 현열 열교환기의 전열성능에 관한 연구)

  • Lee, Min-Su;Jeon, Chang-Duk;Lee, Jin-Ho
    • Proceedings of the SAREK Conference
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.402-407
    • /
    • 2008
  • This study is performed to investigate heat transfer characteristics for thermal performance of fin-and-tube sensible heat exchangers under the low air flowrate according to fin geometry combination and coolant flowrate control. Fins and tubes of samples were separated between front row and rear row. Experiment results are plotted heat transfer rate of each row, heat transfer coefficient and sensible heat ratio against water flowrate control of each row. It is observed that thermal performance can be enhanced by fin geometry combination and water flowrate control of each row under the low air flowrate.

  • PDF

Experimental Study of Air Side Pressure Drop and Heat Transfer Characteristics of Enhanced Fin-Tube Heat Exchangers (열전달 촉진 핀-관 열교환기의 공기측 압력강화 및 열전달 특성에 관한 실험)

  • Youn, Baek;Kil, Yong Hyun;Park, Hyun Yeon;Kim, Young Saeng
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • 제22권11호
    • /
    • pp.1555-1563
    • /
    • 1998
  • Heat transfer and pressure drop for ${\phi}10.07$ dry surface fin-tube heat exchanger with wave and wave-slit fins were measured for different fin spacings and number of tube rows. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively, and wave depth of wave fin is 1.5mm. The experiments were performed for 4 different fin spacings, 1.3, 1.5, 1.7 and 2.0mm, and the number of tube rows were 1,2 and 3 rows. The present results were compared with the previous results for the wave depth of 2mm. Also hydrophilic coated and bare fins were tested. Correlations for Colburn j-factor and friction factor were developed.

Natural Convection Correlation of Circular Finned Tube Heat Exchanger (원형휜-원형관 열교환기에 대한 자연대류 열전달상관식)

  • Kang, Hie-Chan;Jang, Hyun-Soon
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제32권5호
    • /
    • pp.747-752
    • /
    • 2008
  • An experimental study has been conducted on the natural convection heat transfer for the 7 kinds of circular finned tube heat exchangers. Empirical correlation was suggested at the range of 3,500

A Study on the Characteristics of Lift Fluctuation Power Spectral Density on a Fin Tube in the Heat Recovery Steam Generator (배열회수 보일러 단일 휜튜브의 양력 변동 PSD 특성 연구)

  • Ha, Ji Soo;Lee, Boo Youn;Shim, Sung Hun
    • Journal of Energy Engineering
    • /
    • 제24권4호
    • /
    • pp.211-216
    • /
    • 2015
  • Heat exchanger tube array in a heat recovery steam generator is exposed to the hot exhaust gas flow and it could cause the flow induced vibration, which could damage the heat exchanger tube array. It is needed for the structural safe operation of the heat exchanger to establish the characteristics of flow induced vibration in the tube array. The researches for the flow induced vibration of typical heat exchangers have been conducted by using single cicular tube or circular tube array and the nondimensional PSD(Power Spectral Density) function with the Strouhal number, fD/U, had been derived by experimental method. From the present study, the basis for the application of flow induced vibration to the heat recovery steam generator tube array would be prepared. For the previous mentioned purpose, the present CFD analysis introduced a single fin tube and calculated with the unsteady laminar flow over the single fin tube. The characteristics of vortex shedding and lift fluctuation over the fin tube was investigated. The derived nondimensional PSD was compared with the results of the previous experimental researches and the characteristics of lift PSD over a single fin tube was established from the present CFD study.

Simulation on the performance of an automobile climate control system with Internal heat exchanger and TXV (내부열교환기와 TXV를 적용한 자동차용 공조시스템의 성능에 관한 수치적 연구)

  • Park, Cha-Sik
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • 제22권1호
    • /
    • pp.31-36
    • /
    • 2021
  • Recently, automobile air conditioning systems have applied an alternative refrigerant that can replace the high GWP refrigerant R134a due to the global warming problem. This study simulated the performance of an automobile climate control system with an internal heat exchanger and TXV. Refrigerant R1234yf was applied as the working fluid. Amesim, a commercial software program, was used to model the main components of the compressor, condenser, TXV, evaporator, and internal heat exchanger. As the outside temperature increased from 30℃ to 40℃, the cooling capacity of the system decreased by 3.1%, and the power consumption of the compressor increased by 17.1%. In addition, The performance characteristics of the refrigeration cycle were simulated by increasing the fin pitch of the condenser from 0.8 mm to 1.4 mm. When the fin pitch was larger than 1.0 mm, the condenser capacity decreased, and the system COP was lowered by 5.9%. When the fin pitch of the condenser was 0.8 mm, which was smaller than 1.0 mm, there was no significant change in the system performance. Hence, the optimal performance was observed at a fin pitch of 1.0 mm.

CONVECTIVE HEAT TRANSFER CHARACTERISTICS OF OVAL FIN-CIRCULAR TUBE HEAT EXCHANGER (타원형휜-원형관 열교환기의 강제대류 열전달 특성)

  • Kang, H.C.;Lee, J.H.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 한국전산유체공학회 2009년 춘계학술대회논문집
    • /
    • pp.341-346
    • /
    • 2009
  • The purpose of the present study is to investigate the flow resistance and the heat transfer characteristics of oval fin-tube heat exchanger. Six kinds of oval fin having the same fin area and the different diameter ratio tested numerically. Test data for the heat transfer, pressure drop and fin temperature were shown and discussed. The pressure drop and heat transfer increased for increasing the oval fin diameter ratio(diameter of span-wise direction to diameter of longitudinal diameter) up to 50% and 45% respectively.

  • PDF

VERIFICATION OF FIN EFFICIENCY THEORY FOR THE CIRCULAR FINNED-TUBE HEAT EXCHANGER BY NUMERICAL EXPERIMENT (원형휜-원형관 열교환기의 휜효율 이론에 관한 수치적 검증)

  • Kang, H.C.;Lim, B.B.;Lee, J.W.;Chang, B.C.;Ahn, S.W.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 한국전산유체공학회 2008년도 학술대회
    • /
    • pp.137-142
    • /
    • 2008
  • The purpose of the present study is to investigate the convective heat transfer characteristics and the validity of fin efficiency of the circular finned-tube heat exchanger by using commercial CFD code. The heat transfer coefficient obtained by using the laminar model was 22% overestimated to the experimental data. The fin surface temperature compared with the experimental data measured by the liquid crystal method. The fin efficiency by the present numerical experiment, defined as normalized and averaged fin surface temperature, was greater than the theoretical fin efficiency and the difference is increased at high value of the factor m.

  • PDF