• Title/Summary/Keyword: 아크감시

Search Result 19, Processing Time 0.034 seconds

Highly Sensitive Partial Discharge Sensor with Remote Monitoring Capabilities (원격감시 기능을 갖는 고감도 부분방전센서)

  • Choi, Kyoo-Nam
    • The Journal of the Korea institute of electronic communication sciences
    • /
    • v.10 no.3
    • /
    • pp.349-356
    • /
    • 2015
  • Remote monitoring partial discharge sensor, equipping with hybrid filter combining optical and electrical noise reduction capabilities and with signal integrating function to calculate total arc energy, was investigated. Hybrid filter showed insensitivity to fluorescent and incandescent lamps under simulated distribution panel condition. Signal integrating function showed selective detection capability corresponding to different arc energy levels, while convention arc sensor had difficulty to discriminate arc energy level due to bursty arc waveform and peak level detection characteristics. The sensor showed possibility for application to remote monitoring partial discharge sensor, since it detected arc energy level corresponding to normal open and close discharge in low voltage 100A MCCB at 2m distance.

Arc Discharge Sensor having Noise Immunity to Ambient Light (주변광 영향을 받지 않는 아크방전 감지 센서)

  • Roh, Hee Hyuk;Seo, Yong Ma;Khishigsuren, J.;Choi, Kyoo Nam
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • 2013.05a
    • /
    • pp.726-728
    • /
    • 2013
  • Optoelectronic arc discharge sensor was used to detect arc discharge inside power distribution panel. Arc discharge is fatal to power system once it begins, thus preventive detection is necessary before power failure occurs. Optoelectronic detection method was used to avoid direct electrical contact to power apparatus inside power distribution panel. 180 degree detection angle and detection range far exceeding 6m, which was sufficient for monitoring purpose, was achieved using the photodiode having $7.5mm^2$ of active surface area and flash source with $0.4cal/cm^2$ energy density, which is equivalent to 1.9J with $2.16cm^2$ emitting area. The response speed of arc discharge sensor was measured to be below 1 msec. The above optoelectronic arc discharge sensor was measured to be sensitive enough to detect 0.94 pC charge.

  • PDF

A Study on the UL1699 based on Arc Generator (UL1699 기반 아크모의발생장치에 관한 연구)

  • Kwon, Wan-Sung;Kim, Young-Sik;Lee, Young-Jin;Choi, Jung-Muk;Yoo, Jae-Geun;Choe, Myeong-Il;Choe, Gyu-Ha
    • Proceedings of the KIPE Conference
    • /
    • 2008.10a
    • /
    • pp.91-93
    • /
    • 2008
  • 전기로 인한 화재의 주요원인 중 하나는 전기회로에서 발생되는 아크이며, 기존 사용되고 있는 보호장치인 휴즈나 배선용 차단기가 제공하는 과부하, 누전, 단락뿐만 아니라 아크현상에 대한 보호기능을 갖춘 통합 전기화재 감시 및 보호장치의 필요성과 이에 대한 효율적인 운용시스템이 요구된다. 이처럼 다양한 전기화재 사고 중에서 주요 사고 사례 중의 하나가 선로 혹은 전선의 절열 파괴로 일어나는 직렬아크, 스파크(series arc, spark) 현상(누전차단기 혹은 과전류차단기가 동작하지 않는 범위의 아크사고 모의)이다. 이러한 사고를 모의하기 위한 아크발생장치를 설계하여 UL-1699에서 규정하는 아크의 발생여부를 확인할 수 있다.

  • PDF

Design and Implementation of a ZigBee Nework-based Integrated AFCI (지그비 네트워크 기반 복합형 AFCI 설계 및 구현)

  • Chang, Ki-Heung;Kim, Kee-Min;Kim, Jae-O;Ahn, Hyun-Sik
    • The Journal of the Institute of Internet, Broadcasting and Communication
    • /
    • v.10 no.4
    • /
    • pp.41-48
    • /
    • 2010
  • In this paper, a new type of integrated AFCI is designed and implemented by combining individual circuit breaker characteristics, which can effectively detect arc fault signals in real-time. The proposed integrated AFCI satisfies the UL1699, the USA certification standard, and the Korean circuit breaker standards such as KS C4613 and KS C8321. Data signals are transferred to the management server via ZigBee network to analyze dangerous factors and to prevent unwanted trip. It is also shown by experiments that arc fault signals are detected and analyzed by using the integrated AFCI with ZigBee networks.

A Study on the Remote Inspection System in compliance with the application of Electrical Safety Remote Terminal Unit (전기안전감시장치의 적용에 따른 원격점검체계에 관한 연구)

  • Yoo, Jae-Geun;Choe, Myeong-Il
    • Proceedings of the KAIS Fall Conference
    • /
    • 2009.05a
    • /
    • pp.705-708
    • /
    • 2009
  • 본 논문에서는 전기안전감시장치의 적용에 따른 원격점검체계에 대하여 연구하였다. 현재 일반용 수용가는 1, 2, 3년 주기로 인력점검에 의해 전기안전점검을 수행하고 있다. 그러나 상시감시를 할 수 없고, 1회 부재시 점검주기의 2회의 기간만큼 안전을 확보할 수 없다는 단점이 있다. 따라서 아크차단기능이 내장된 전기안전감시장치의 일반용 수용가 적용에 따른 점검절차, 체계의 변화에 대하여 연구하였다. 또한 원격점검장치 도입시 문제점을 검토하고 이에 대한 해결방안에 대하여 연구하였다.

  • PDF

A study Improvement Direction for Arc Interruption Equipment and On-line Monitoring System of Consumer Low Voltage Facilities (수용가 저압 전기설비의 원격 감시시스템 및 아크차단 장치 활성화 방안에 관한 연구)

  • Kim, Gi-Hyun;Park, Chee-Hyun;Lim, Young-Bai;Choi, Myeong-Il;Bae, Suk-Myong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.1
    • /
    • pp.79-86
    • /
    • 2008
  • Domestic and foreign follows the trend which is that safety checkup of electrical facilities is serviced by on-line system with joining information technology. This paper research improvement of what kind of system and law for market environment of electric power value added service. For improvement of market environment of electric power value added service, this paper researches improvement of on-line monitoring system and necessity of arc interruption and revision of arc related law.

A Study on Development of App-Based Electric Fire Prediction System (앱기반 전기화재 예측시스템 개발에 관한 연구)

  • Choi, Young-Kwan;Kim, Eung-Kwon
    • Journal of Internet Computing and Services
    • /
    • v.14 no.4
    • /
    • pp.85-90
    • /
    • 2013
  • Currently, the electric fire prediction system uses PIC(Peripheral Interface Controller) for controller microprocessor. PIC has a slower computing speed than DSP does, so its real-time computing ability is inadequate. So with the basic characteristics waveform during arc generation as the standard reference, the comparison to this reference is used to predict and alarm electric fire from arc. While such alarm can be detected and taken care of from a remote central server, that prediction error rate is high and remote control in mobile environment is not available. In this article, the arc detection of time domain and frequency domain and wavelet-based adaptation algorithm executing the adaptation algorithm in conversion domain were applied to develop an electric fire prediction system loaded with new real-time arc detection algorithm using DSP. Also, remote control was made available through iPhone environment-based app development which enabled remote monitoring for arc's electric signal and power quality, and its utility was verified.