• Title/Summary/Keyword: $V_{rated}$

Search Result 232, Processing Time 0.025 seconds

Development and Testing of a 10 kV 1.5 kA Mobile DC De-Icer based on Modular Multilevel Converter with STATCOM Function

  • Hu, Pengfei;Liang, Yiqiao;Du, Yi;Bi, Renming;Rao, Chonglin;Han, Yang
    • Journal of Power Electronics
    • /
    • v.18 no.2
    • /
    • pp.456-466
    • /
    • 2018
  • This paper introduces the development of a de-icer based on a full-bridge modular multilevel converter (FMMC). The FMMC can generate a wide range of DC voltages owing to its modularity, scalability, and redundancy, which makes it suitable for ice-melting applications. First, operating principles and voltage ranges are analyzed when FMMC is applied as a mobile de-icer. Second, two new startup strategies, constant modulation index and constant power startup strategies, are proposed. Third, the main control strategies of the de-icer are proposed. Fourth, a novel rated-current zero-power test scheme is proposed to simplify test conditions. Finally, a 10 kV 1.5 kA mobile MMC de-icer is designed and built, and experiments are carried out to validate the proposed startup, control strategies, and rated-current zero-power test scheme.

Simulation Modeling cnd Analysis of Pitch Controlled Variable Speed Wind Turbine System (피치제어형 가변속 풍력터빈 시스템의 시뮬레이션 모델링과 해석)

  • Kim, Eel-Hwan;Kang, Geong-Bo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.2
    • /
    • pp.124-130
    • /
    • 2005
  • This paper presents the simulation modeling and analysis of variable wind speed turbine system(VWTS) using Psim program In the simulation, using the Vestas V47 VWTS located in Hangwon wind farm in Jeju-Do as a model, wind model, blade model, pitch control model and grided connected generator are modeled. The VWTS is controlled by the optimal pitch angle for maximum output power under the rated wind speed and for the rated output power over the rated wind speed. To verify the effectiveness of proposed method, simulation results are compared with the actual data from the model system According to the comparison of these results, this method shows excellent performance. So it is very useful for understanding and applications of wind power control system.

Association between Obesity and Self-Rated Health in Korean Males and Females (우리나라 성인 남녀의 비만이 주관적 건강상태 지각에 미치는 영향)

  • Ha, Yeongmi;Park, Hyunju
    • Journal of Korean Biological Nursing Science
    • /
    • v.14 no.3
    • /
    • pp.203-211
    • /
    • 2012
  • Purpose: The purpose of this study was to investigate effects of obesity on self-rated health in Korean males and females. Methods: The 2010 Korean National Health and Nutrition Examination Survey (KNHANES V-1) data were used. Participants included 1,231 males and 1,289 females aged 20 years or older and had no disease. Chi-square test, t-test, and multiple logistic regression with dummy variables using SAS 9.2 were performed. Results: From univariate analysis, total body fat was significantly greater in males with a self-perception of poor health (p=.006), and the percentage of total body fat was significantly greater in males and females with a self-perception of poor health (p for all=.001). After controlling for demographic and health behavior variables, similar results were found. Females with higher education had a healthy perception of their health. Smoking for males and drinking for females were significantly related to unhealthy perception of their health. Conclusion: The current study provides evidence that obese Korean males and females had worse self-rated health, even though they had no disease. In particular, it is important to note that the relatively direct obesity measures from Dual Energy X-Ray Absorptiometry, such as total body fat and percentage of body fat, were significantly related to self-rated health.

Analysis of Insulation Aging in High Voltage Motor Stator Windings (고압전동기 고정자 권선의 절연열화 분석)

  • Kim, Hee-Dong;Kong, Tae-Sik;Lee, Young-Jun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.06a
    • /
    • pp.200-203
    • /
    • 2006
  • Prior to destructive testing, diagnostic tests were performed in eight high voltage motors. Diagnostic tests included polarization index, ac current, dissipation factor($tan{\delta}$) and partial discharge magnitude. The rewind of motor stator insulation at rated voltage is assessed by the results of these tests. After completing the diagnostic tests, the stator windings of motors were subjected to gradually increasing ac voltage, until the insulation punctured. No. 1 motor failed near rated voltage of 12.96 kV. The breakdown voltage of No. 4 motor was 6.99 kV which is lower that expected for good quality coils in 6.6 kV class motors. The failure was located in a line-end coil at the exit from the core slot. These two motors began operation in 1994. While testing No. 7 motor, flashover occurred between the stator winding and the stator frame at 15 kV. The relationship between the diagnostic test and the drop in insulation breakdown voltage was analyzed.

  • PDF

Mathematical modeling of wind power estimation using multiple parameter Weibull distribution

  • Chalamcharla, Seshaiah C.V.;Doraiswamy, Indhumathy D.
    • Wind and Structures
    • /
    • v.23 no.4
    • /
    • pp.351-366
    • /
    • 2016
  • Nowadays, wind energy is the most rapidly developing technology and energy source and it is reusable. Due to its cleanliness and reusability, there have been rapid developments made on transferring the wind energy systems to electric energy systems. Converting the wind energy to electrical energy can be done only with the wind turbines. So installing a wind turbine depends on the wind speed at that location. The expected wind power can be estimated using a perfect probability distribution. In this paper Weibull and Weibull distribution with multiple parameters has been used in deriving the mathematical expression for estimating the wind power. Statistically the parameters of Weibull and Weibull distribution are estimated using the maximum likelihood techniques. We derive a probability distribution for the power output of a wind turbine with given rated wind speeds for the regions where the wind speed histograms present a bimodal pdf and compute the first order moment of this distribution.

A Study on Arc Conductance of Puffer Type SF6 GCB at Current Zero Period (전류영점 영역에서 파퍼식 SF6 가스차단기의 아크 컨덕턴스에 관한 연구)

  • Chong, Jin-Kyo;Song, Ki-Dong;Lee, Woo-Young;Kim, Gyu-Tak
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.2
    • /
    • pp.328-332
    • /
    • 2010
  • The SLF(Short Line Fault) breaking capability test for high voltage class $SF_6$ GCB(Gas Circuit Breaker) was conducted. Simplified LC resonant circuit test facility was used for SLF breaking test. During test, Test current was measured by Rogwski coil and arc voltage was measured by voltage divider. Arc conductance was calculated by using these test results before 200ns at current zero. Critical arc conductance value at rated voltage 145kV class is about 2.3mS regardless of breaking current magnitude and arc conductance value at rated voltage 170kV class is about 2.6mS.

Digital Control Techniques for Bidirectional CRM Buck/Boost Converter (양방향 경계모드 벅/부스트 컨버터의 디지털 제어기법)

  • Sang-Youn Lee;Woo-Seok Lee;Il-Oun Lee
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.28 no.1
    • /
    • pp.48-58
    • /
    • 2023
  • This paper presents the digital control techniques of a bidirectional CRM(critical-conduction mode) buck(boost) converter, a dead-time design method that optimizes ZVS(zero-voltage switching) and valley-switching operation, and a switching-frequency limitation that ensures stable converter operation. To verify the feasibility of the design, a Si-MOSFET-based bidirectional CRM buck(boost) converter is built with 260-430 V input, 160-240 V output, and 1.0 kW rated capacity. The bidirectional CRM converter achieves an efficiency of up to 99.6% at buck mode and 98.7% at boost mode under rated load conditions.

Modeling and Analysis of Variable Wind Speed Turbine System Using Back to Back Converter (Back to bock 컨버터를 갖는 가변속 풍력터빈 시스템의 모델링과 해석)

  • Kim, Eel-Hwan;Kang, Keong-Bo;Kim, Jae-Hong;Moon, Sang-Ho;Oh, Sung-Bo;Kim, Se-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.8
    • /
    • pp.150-157
    • /
    • 2005
  • This paper presents the simulation modeling and analysis of variable wind speed turbine system(VWTS) using the doubly fed induction generator(DFIG) connected the back to back converter system in the rotor side. In the simulation, using the model system which has the 660[kW] rated power, blade control and the dual converter system are modeled for verifying the control characteristics. The VWTS is controlled by the optimal pitch angle for maximum output power under the rated wind speed, and for the rated output power over the rated wind speed. And also power factor is controlled by the reactive power. To verify the effectiveness of the proposed method, simulation results are compared with the actual data from the V47 VWTS located in Hangwon wind farm in Jeju-Do. According to the comparison of these results, this method shows excellent performance.

Production of English Alphabets by Koreans

  • Yun, Yung-Do;Lee, Hyun-Gu
    • English Language & Literature Teaching
    • /
    • v.11 no.4
    • /
    • pp.97-120
    • /
    • 2005
  • Production and perception of second language sounds are typically influenced by second language learners' native language sounds. In this study we investigate how the Korean language influences Korean speakers' production of English alphabets. In the experiment conducted to prepare for this study 16 native speakers of Korean pronounced English alphabets. Then three native speakers of English evaluated the Korean subjects' pronunciation of them. The results show that the Korean subjects' native language (i.e., Korean) influences their production of the English alphabets. When Korean has sounds corresponding to English alphabets, the English subjects rate the Korean subjects' production of them good. For instance, Korean has voiceless stop phonemes, hence their production of English alphabets was rated good by the English subjects. The Korean subjects' production of English alphabets containing the sounds that do not exist in Korean was rated poor by the English subjects. For instance, Korean does not have voiced fricative phonemes, hence their production of English alphabets was rated poor.

  • PDF

The study for function and operation of the excitation equipment for short circuit generator (단락발전기 용 여자장치의 조작과 기능에 대한 고찰)

  • Kim, Sun-Koo
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.735-736
    • /
    • 2008
  • There are many equipments for the Short Circuit Test, for example Short Circuit Generator, Induction Motor, Sequence Timer, CLR, Back Up Breaker, Making Switch and Excitation Equipment etc. Gradually an allowable tolerance of the short circuit test voltage is become smaller by the standards for short circuit test. The excitation equipment of short circuit generator is very important for test voltage is adjusted by the excitation equipment. Especially the excitation equipment must be possessed character of exactitude, durability and inalterability because some times around 10,000 times opening and closing short circuit test is requested by clint, which must be done within one minute. The purpose of this study for function and operation of the excitation equipment which rated DC voltage is 1,000V, rated DC current is 300A, rated out put is 30kW and type is YNEX 97S-441/609, is to help operation of short circuit generator.

  • PDF