• 제목/요약/키워드: $COP_c$

검색결과 318건 처리시간 0.029초

대체냉매를 사용한 이원냉동 시스템의 성능에 관한 연구 (Study on the Performance of the Cascade System Using Alternative Refrigerants)

  • 박종훈;조금남
    • 설비공학논문집
    • /
    • 제13권7호
    • /
    • pp.564-571
    • /
    • 2001
  • The present study investigated the effect of key parameters on the performance of a cascade system using R-22 and R-23 refrigerants. Experimental data for the cascade system have been compared with simulation results using thermodynamic analysis. The cascade system tested at the evaporating temperature of $-80^{\circ}C $ and the condensing temperature of$40^{\circ}C $. The key experimental parameters were the evaporating temperature of the HTC(-35, -30, -25, -20, $-15^{\circ}C $) and mass flux of the HTC(200, 250, 300kg/$m^2$s). As the evaporating temperature and the mass flux of the HTC were increased respectively, the COP and the refrigerating efficiency were increased and then decreased while the volume flow rate per unit refrigeration capacity showed the opposite trend. The maximum COP and refrigerating efficiency were obtained at the evaporating temperature of the HTC of $-25^{\circ}C $ and the mass flux of 250 kg/$m^2$s.

  • PDF

Depletion of ${\varepsilon}$-COP in the COPI Vesicular Coat Reduces Cleistothecium Production in Aspergillus nidulans

  • Kang, Eun-Hye;Song, Eun-Jung;Kook, Jun Ho;Lee, Hwan-Hee;Jeong, Bo-Ri;Park, Hee-Moon
    • Mycobiology
    • /
    • 제43권1호
    • /
    • pp.31-36
    • /
    • 2015
  • We have previously isolated ${\varepsilon}$-COP, the ${\alpha}$-COP interactor in COPI of Aspergillus nidulans, by yeast two-hybrid screening. To understand the function of ${\varepsilon}$-COP, the $aneA^+$ gene for ${\varepsilon}$-COP/AneA was deleted by homologous recombination using a gene-specific disruption cassette. Deletion of the ${\varepsilon}$-COP gene showed no detectable changes in vegetative growth or asexual development, but resulted in decrease in the production of the fruiting body, cleistothecium, under conditions favorable for sexual development. Unlike in the budding yeast Saccharomyces cerevisiae, in A. nidulans, over-expression of ${\varepsilon}$-COP did not rescue the thermo-sensitive growth defect of the ${\alpha}$-COP mutant at $42^{\circ}C$. Together, these data show that ${\varepsilon}$-COP is not essential for viability, but it plays a role in fruiting body formation in A. nidulans.

수용성 모형계에서 콜레스테롤의 산화 안정성에 대한 Erythrosine의 영향 (Effects of Erythrosine on the Cholesterol Oxidative Stability in an Aqueous Model System)

  • 정만곤;김종승;신효선
    • 한국식품과학회지
    • /
    • 제28권1호
    • /
    • pp.197-202
    • /
    • 1996
  • 콜레스테롤을 함유하는 수용성 모형계에서 erythrosine의 첨가농도, 광도, tocopherol과 ${\beta}-carotene$의 첨가에 따른 headspace내의 산소량의 변화와 콜레스테롤 산화물의 생성량의 변화를 연구하였다. Erythrosine의 첨가량이 증가할수록 headspace내 산소량의 감소가 컸고, 각종 COP 생성량은 증가하였다. 형광등의 조도가 증가할수록 headspace내 산소량의 감소가 컸고, 이에 비례하여 콜레스테롤은 감소하였고 총 COP의 생성량은 증가하였다. 일중항 산소 소거제로 tocopherol과 ${\beta}-carotene$을 첨가하였을 때 headspace내의 산소량은 완만하게 감소하였으며, 이에 비례하여 콜레스테롤의 감소가 완만하였고 총 COP의 생성량 또한 감소하였다.

  • PDF

지열원 멀티열펌프 시스템의 용량가변 특성 연구 (Capacity Modulation of a Ground Source Multi-Heat Pump in the Part Load Condtions)

  • 조찬용;오명석;최종민
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2010년도 추계학술대회 초록집
    • /
    • pp.120-120
    • /
    • 2010
  • 에너지 절약적 차원에서 한 대의 실외기에 다수의 실내기가 접속되는 개별공조형 멀티 열펌프에 관한 연구 및 개발과 보급이 증대되고 있다. 본 연구에서는 복수의 실내기를 갖고 가변속 압축기를 채용한 지열원 물대공기 멀티열펌프시스템을 학교 현장에 설치하여 제조사의 운전 제어 알고리즘에 따라 일일 냉난방 실증 성능 특성을 분석하였다. 2008년 9월 30일의 냉방부하가 낮은 일자에 대하여 시간에 따른 부하 변동에 따라 압축기의 용량가변으로 실내기 냉방용량은 정격용량 대비 17.1%에서 111.3%의 범위에서 변이되었으나, 열펌프 유닛의 일일 최대 COP는 6.2를 나타냈으며, 일일 평균 열펌프 유닛 COP는 4.5로 열펌프 유닛 인증 기준 이상의 성능을 나타냈다. 2008년 11월 10일 대비 2008년 12월 15일에는 시스템 가동 중의 평균 외기온도가 $9.6^{\circ}C$ 감소하였으나, 각 재실공간의 용도별 부분 부하특성으로 11월 10일 보다 난방 부하량이 작게 나타났다. 하지만, 12월 15일에는 부하량이 매우 작아서 11월 10일보다 잦은 압축기 가변에 따른 손실로 일일 평균 COP가 낮게 나타났다. 2009년 1월 12일에는 정격 용량대비 94%의 부하율로 11월 10일과 12월 15일 대비 4배 이상의 부하량으로 압축기 용량 가변율이 작아서 난방용량과 COP 변화율이 작게 나타났다. 2009년 1월 12일에는 지중순환수의 실외열교환기 유입온도가 2008년 12월 15일보다 감소하고, 시스템의 난방용량 증가로 상대적으로 응축기와 증발기 크기가 감소한 효과로 히트펌프 유닛 COP가 감소하였으나, 본 지열원 열펌프 제조사에서 생산하고 있는 본 지열원 시스템과 동일한 압축기 등을 채용한 동일 용량의 공기열원 열펌프의 1월 12일 외기온도 $-10^{\circ}C$에서의 열펌프 유닛 COP 대비 70% 우수한 성능을 나타냈다. 본 지열원 히트펌프의 2008년 11월 10일의 일일 평균 히트펌프 유닛 COP는 외기온도가 낮고 일일 부하량이 크게 나타난 1월 12일의 일일 평균 히트펌프 유닛 COP 대비 37% 높게 나타났으나, 지중순환펌프의 정속운전으로 시스템 요구 지중순환수 유량 증가에 따른 성능 향상보다 소비전력 증가 영향이 커서 1월 12일의 시스템 COP 보다 33.3% 작은 값을 나타냈다. 본 연구의 용량 가변형 압축기를 채용한 지열원 멀티 히트펌프 유닛을 지열원 냉난방 시스템의 히트펌프 유닛으로 사용할 경우 시스템 최적화를 통한 시스템 COP 향상과 연간에너지 절감을 이루기 위해서는 히트펌프의 용량 변화 시에 지중순환펌프의 순환 유량 최적화를 위한 효율적 운전 제어 알고리즘 개발이 요구된다.

  • PDF

외기온도와 부하변화에 따른 산업용 냉각기의 인버터제어 특성 (The Characteristic of Inverter Control by Variation of Refrigeration Load and Outdoor Temperature on Industrial Cooler)

  • 백승문
    • 동력기계공학회지
    • /
    • 제18권5호
    • /
    • pp.150-155
    • /
    • 2014
  • This paper presents The performance analysis of inverter control type-industrial cooler with respect to refrigeration load and outdoor temperature. Aside from materials about simulations and foundation data regarding inverter control compressors, currently, data about commercial coolers with inverter control still lack information for performance comparison. Thus, in this paper, the experiments are done to see characteristics of condensation capacity, evaporation capacity, compressor power and COP with respect to outdoor temperature and load by using a commercial inverter control cooler model. As a result, COP difference of the inverter control cooler with respect to load is 30% at the outdoor temperature of $35^{\circ}C$, 29% at the outdoor temperature of $30^{\circ}C$, 34% at $25^{\circ}C$, respectively.

지열히트펌프 냉매자동조절에 따른 냉·난방 성능실험에 관한 연구 (A Study on the Cooling Heating Performance Experiment by Refrigerant Auto Control of Geothermal Heat Pump)

  • 구남열;서승일
    • 한국지열·수열에너지학회논문집
    • /
    • 제11권1호
    • /
    • pp.1-6
    • /
    • 2015
  • This study presents analysis of the experimental data meeting conditions of several applications in real time. The results of this experimental study are as follows: Respectively in cooling and heating performance, a refrigerant charge tank can take automatic control of variation of the refrigerant quantity by controling pressure and temperature of system and outlet water temperature. The COP shows 3.5 in cooling operation and 3.2 in heating operation. The refrigerant quantity increases 0.69 kJ/h. When the outdoor temperature decreases $1^{\circ}C$, Therefore if the temperature become lower from $25^{\circ}C$ to $-16^{\circ}C$, the refrigerant quantity increases about 9.5%. Compared to the normal state experiment results, the COP in automatic control of the refrigerant quantity rises roughly 10%.

실리카겔-물계 흡착식 냉동기 사이클 시뮬레이션 (Cycle Simulation of an Adsorption Chiller Using Silica Gel-water)

  • 권오경;윤재호
    • 대한기계학회논문집B
    • /
    • 제31권2호
    • /
    • pp.116-124
    • /
    • 2007
  • An adsorption chiller is expected to have high energy-efficiency in utilizing the waste heat exhausted from a process. The objective of this paper is to investigate the performance of silica gel-water adsorption chiller from the cycle simulation and to provide a guideline for design of the adsorption chiller. The effect of cycle time, inlet temperature and water flow rate on the cooling capacity and COP is quantified during the cycle operation. It is found that the performance of adsorption chiller is more sensitive to the change of inlet water temperature rather than the water flow rate. It is concluded that the COP is 0.57 in the standard conditions(hot water $80^{\circ}C$, cooling water $30^{\circ}C$, chilled water inlet temperatures $14^{\circ}C$ and cycle time 420sec).

직렬 제습방식 열펌프 시스템의 성능특성에 관한 연구 (Study on the performance of a heat pump system with serial dehumidification function)

  • 고원빈;고지운;박윤철
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제38권6호
    • /
    • pp.609-614
    • /
    • 2014
  • 화산지형인 제주도의 지열에너지를 사용하기 위하여 지하공기를 측정하였을 때 지중 온도는 $15{\sim}18^{\circ}C$이며, 상대습도는 70~80%로 타 지역에 비하여 매우 높은 경향을 나타내고 있다. 본 연구는 제습기능 및 난방기능을 구비한 다단 제습 가열 열펌프 시스템의 개발에 관한 연구로써, 개발된 열펌프의 성능실험을 수행한 결과 흡입공기의 상태가 최저 $15^{\circ}C$, 60%인 경우 총제습량이 1.797(kg/h)로 나타났으며, 최고 $20^{\circ}C$, 80%인 경우 총제습량이 45% 증가한 3.269(kg/h)로 증가하여 충분한 제습이 이루어짐을 알 수 있다. 또한, 난방능력은 흡입온도 $17^{\circ}C$ 상대습도 70% 일 때 1.91로 가장 높은 효율을 얻을 수 있다.

The Antimicrobial Peptide CopA3 Inhibits Clostridium difficile Toxin A-Induced Viability Loss and Apoptosis in Neural Cells

  • Yoon, I Na;Hwang, Jae Sam;Lee, Joon Ha;Kim, Ho
    • Journal of Microbiology and Biotechnology
    • /
    • 제29권1호
    • /
    • pp.30-36
    • /
    • 2019
  • Numerous studies have reported that enteric neurons involved in controlling neurotransmitter secretion and motility in the gut critically contribute to the progression of gut inflammation. Clostridium difficile toxins, which cause severe colonic inflammation, are also known to affect enteric neurons. Our previous study showed that C. difficile toxin A directly induces neural cell toxicities, such as viability loss and apoptosis. In the current study, we attempted to identify a potent inhibitor of toxin A-induced neural cell toxicity that may aid in managing toxin A-induced gut inflammation. In our recent study, we found that the Korea dung beetle-derived antimicrobial peptide CopA3 completely blocked neural cell apoptosis caused by okadaic acid or 6-OHDA. Here, we examined whether the antimicrobial peptide CopA3 inhibited toxin A-induced neural cell damage. In neuroblastoma SH-SY5Y cells, CopA3 treatment protected against both apoptosis and viability loss caused by toxin A. CopA3 also completely inhibited activation of the pro-apoptotic factor, caspase-3. Additionally, CopA3 rescued toxin A-induced downregulation of neural cell proliferation. However, CopA3 had no effect on signaling through ROS/p38 $MAPK/p27^{kip1}$, suggesting that CopA3 inhibits toxin A-induced neural cell toxicity independent of this well-characterized toxin A pathway. Our data further suggest that ability of CopA3 to rescue toxin A-induced neural cell damage may also ameliorate the gut inflammation caused by toxin A.

R744-R717 캐스케이드 냉동시스템에서 운전조건 변화에 따른 성능 해석 (Performance Simulation of a R744-R717 Cascade Refrigeration System According to Operating Conditions)

  • 유지호;조홍현
    • 설비공학논문집
    • /
    • 제27권10호
    • /
    • pp.497-505
    • /
    • 2015
  • The evaporating temperature range required for the low temperature freezing system is from $-50^{\circ}C$ to $-30^{\circ}C$. Since it is difficult to keep the required capacity in a cabinet, it is advantageous to design the system using a cascade refrigeration system. Use of carbon dioxide and ammonia would be advantageous since ammonia is an environment-friendly working fluid and has a high capacity for performance improvement. To investigate the performance characteristics of the R744-R717 cascade refrigeration system, a theoretical model was developed and performance was analyzed according to cascade heat exchanger operating temperature. The optimal cascade R744 condensing temperature was $-5^{\circ}C$, and maximum COP was 1.13 when the temperature difference of the cascade heat exchanger was $5^{\circ}C$. In addition, the total system COP increased by 1.17 when the cascade temperature gap was $3^{\circ}C$ at the middle temperature of $-7.5^{\circ}C$.