Abstract

In this research, results of measuring temperature and relative humidity of underground-air-heat in Jeju showed $15{\sim}18^{\circ}C$ and 70~80% each which are somewhat high compare to other regions. So the Multi-effect dehumidifying and heating Heat Pump system which has merged functions of dehumidification and heating is made to solve this problem mentioned previously. When the suction air was $15^{\circ}C$ with 60% humidity, the outcome was 1.70 on $COP_h$ and 1.797(kg/h) on total amount of dehumidification, and also showed 1.87 $COP_h$ with 1.87 total amount of dehumidification under the condition of $20^{\circ}C$ and 80% humidity of suction air. Furthermore, $COP_h$ showed increased number which is 1.87 and also total amount of dehumidification increased which was 3.269(kg/h). The highest COP can be achieved at $17^{\circ}C$ and 70% relative humidity condition.

화산지형인 제주도의 지열에너지를 사용하기 위하여 지하공기를 측정하였을 때 지중 온도는 $15{\sim}18^{\circ}C$이며, 상대습도는 70~80%로 타 지역에 비하여 매우 높은 경향을 나타내고 있다. 본 연구는 제습기능 및 난방기능을 구비한 다단 제습 가열 열펌프 시스템의 개발에 관한 연구로써, 개발된 열펌프의 성능실험을 수행한 결과 흡입공기의 상태가 최저 $15^{\circ}C$, 60%인 경우 총제습량이 1.797(kg/h)로 나타났으며, 최고 $20^{\circ}C$, 80%인 경우 총제습량이 45% 증가한 3.269(kg/h)로 증가하여 충분한 제습이 이루어짐을 알 수 있다. 또한, 난방능력은 흡입온도 $17^{\circ}C$ 상대습도 70% 일 때 1.91로 가장 높은 효율을 얻을 수 있다.

Keywords

References

  1. Ministry of Commerce Industry and Energy, "Alternative energy development and promotion of dissemination", Article 11, paragraph 2, 2004.
  2. H. B. Chae and Y. J. Nam, "Study on the method to predict the heat exchange rate of horizontal ground heat pump system using underground heat transfer analysis model", Korean Journal of Air-Conditioning and Refrigeration Engineering, vol. 2012, no. 11, pp. 339-402, 2012.
  3. J. W. Ko, Y. C. Park, and G. S. Ko, "The performance evaluation of a ground air source heat for an air conditioning system", Korean Journal of Air-Conditioning and Refrigeration Engineering, vol. 2012, no. 6, pp. 781-784, 2012.
  4. H. J. Shin, C. H. Ahn, and C. S. Cho, "Overview for the effective use of geo-thermal energy", Korean Journal of Air-Conditioning and Refrigeration Engineering, vol. 24, no. 4, pp. 409-419, 1995.
  5. H. Zeng, N. Diao, and Z. Fang, "Heat transfer analysis of boreholes in vertical ground heat exchangers", International Journal of Heat and Mass Transfer, vol. 46, no. 23, pp. 4467-4481, 2003. https://doi.org/10.1016/S0017-9310(03)00270-9
  6. A. Hepbasli, O. Akdemir, and E. Hancioglu, "Experimental study of a closed loop vertical ground source heat pump systems", American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2003.
  7. Y. Bi, L. Chen, and C. Wu, "Ground heat exchanger temperature distribution analysis and experimental verification", Applied Thermal Engineering, vol. 22, no. 2, pp. 183-189, 2002. https://doi.org/10.1016/S1359-4311(01)00073-4
  8. M. Inalli and H. Esen, "Experimental thermal performance evaluation of a horizontal ground-source heat pump system", Applied Thermal Engineering, vol 24, no. 14-15, pp. 2219-2232, 2004. https://doi.org/10.1016/j.applthermaleng.2004.01.005
  9. K. W. Lee, "Earth-coupled heat pump technology", Korean Journal of Air-Conditioning and Refrigeration Engineering, vol. 21, no. 4, pp. 306-315, 1992.
  10. H. J. Shin, C. H. Ahn, and C. S. Cho, "Overview for the effective use of geothermal energy", Korean Journal of Air-Conditioning and Refrigeration Engineering, vol. 24, no. 4, pp. 409-419, 1995.
  11. B. C. Kim, H. j. Shin, and C. S. Cho, "The measurement and analysis of performance of ground source heat pump system in winter", Korean Journal of Air-Conditioning and Refrigeration Engineering, vol. 2003, pp. 190, 2003.
  12. Y. C. Park and S. K. Park, "In-situ performance evaluation of a ground source heat pump for an air conditioning system", Journal of the Korean Society of Marine Engineering, vol. 32, no. 1, pp. 66-72, 2008. https://doi.org/10.5916/jkosme.2008.32.1.66
  13. D. G. Ko, "A study on heating system applied ground source heat pump(GSHP) for the agriculture", Graduate Degree Research paper, Department of Mechanical Engineering, Jeju Nationa University, korea, 2010.
  14. J. W. Ko, Y. C. Park, and G. S. Ko, "An experimental study on a heat pump with dehumidification function to utilizing underground air heat", Korean Journal of Air-Conditioning and Refrigeration Engineering, vol. 26, no. 2, pp. 55-60, 2014. https://doi.org/10.6110/KJACR.2014.26.2.055