DOI QR코드

DOI QR Code

Experimental Study on Spray Performance of Nozzles for Autonomous Fire Fighting Monitor

자율형 소화모니터 노즐의 분사 성능에 대한 실험 연구

  • Rhyu, SeongSun (Institute of Advanced Transportation Vehicles, Chungnam National University) ;
  • Kim, HyoungTae (Department of Naval Architecture & Ocean Engineering, Chungnam National University) ;
  • Seo, JeongHwa (Department of Naval Architecture & Ocean Engineering, Chungnam National University)
  • 유성선 (충남대학교 첨단수송체연구소) ;
  • 김형태 (충남대학교 선박해양공학과) ;
  • 서정화 (충남대학교 선박해양공학과)
  • Received : 2021.09.23
  • Accepted : 2022.01.24
  • Published : 2022.04.20

Abstract

A systematic experimental study is carried out for the fire fighting monitor nozzle of 65A diameter to design and manufacture a new nozzle with better water spray performance than available domestic nozzles. The nozzle inlet pressure, flow rate and reach for the discharged water from the nozzle are measured by utilizing the experimental facility consisting of two pumps and piping system with a flow meter and pressure gauges. It was found that the baffle position and baffle head chamfering were the most sensitive design factors to be remarkably changed in the flow rate of the discharged water. Also, It was confirmed that the baffle position and the water exit area had the significant effect on the change in reach distance. The results obtained from this study are expected to be used effectively to design new nozzles with excellent spray performances and also to validate numerical analysis results for evaluating the water spray performance of fire fighting monitor nozzles.

Keywords

Acknowledgement

본 연구는 대한민국 정부(산업통상자원부 및 방위사업청) 재원으로 민군협력진흥원에서 수행하는 민군기술협력사업의 연구비 지원으로 수행되었으며(협약번호 UM19304RD3), 이에 감사드립니다.

References

  1. Back, Gerard G. et. al., 2015. Suppression of shipboard fires in large volume spaces using monitors, Report of National Research Laboratory.
  2. Chen, T., Yuan, H., Su, G. & Fan, W., 2004. An automatic fire searching and suppression system for large spaces. Fire Safety Journal, 39(4), pp.397-309.
  3. Choi, B.I., Han, Y.S., Oh, C.B., Kim, M.B. & Kim, C., 2007. The assessment of fire suppression capability of water-mist system for machinery engine room, Fire Science and Engineering, 21(2), pp.111-117.
  4. Elkhart Brass Manufacturing Company(EBa), Full line catalogue F8.1, Available at: http://www.elkhartbrass.com/downloads/ performance. [Accessed 18 September 2019a].
  5. Elkhart Brass Manufacturing Company(EBb), Performance documents of monitors and master stream, Available at: http://www.elkhartbrass.com/downloads/performance [Accessed 23 September 2019b].
  6. Im, D.B., Seo, J.H, Ruy W.S. & Lee, H., 2021. Modeling of water jet behavior of a fire monitor for a surface vessel in seaways, Korean Journal of Computational Design and Engineering, 26(1), pp. 50-58 https://doi.org/10.7315/CDE.2021.050
  7. Joong Ang Industrial Co., Ltd.(JA), JA+E-Catalog, Available at: http://www.fireja119.com/library/ecatalogue analysis of water discharge trajectory with large capacity monitor [Accessed 3 September 2019], Fire Safety Journal, 63, pp.1-8.
  8. Jung, I.S., Chung, H.T. & Han, Y.S., 2016. Computational simulation of fire suppression system for cabins of shipboard enclosure. Journal of Computational Fluids Engineering, 21(4), pp.40-45. https://doi.org/10.6112/kscfe.2016.21.4.040
  9. McNeil, J.G. & Lattimer, B.Y., 2016. Autonomous fire suppression system for use in high and low visibility environments by visual servoing. Fire Technology, 52(5), pp.1343-1368. https://doi.org/10.1007/s10694-016-0564-8
  10. Miyashita, T., Sufawa, O., Imamura, T., Kamiya, K. & Kawaguchi, Y. 2014. Modeling and analysis of water discharge trajectory with large capacity monitor. Fire Safety Journal, 63, pp.1-8. https://doi.org/10.1016/j.firesaf.2013.09.028
  11. Park, J., Yoo, Y., Kim, Y., Park, B., Kim, W., & Park, S., 2019. Development of remote control automatic fire extinguishing system for fire suppression in double-deck tunnel. Journal of Korean Tunnelling and Underground Space Association, 21(1) pp.167-175. https://doi.org/10.9711/KTAJ.2019.21.1.167