Abstract

We proposed and demonstrated DC(direct current) optical current sensor based on Faraday effect for HVDC(high voltage direct current). The RIG((Bi1.3Gd0.43Y1.27)Fe5O12) was adopted as Faraday device because of its high Verdet constant and good thermal stability. The differential amplification scheme for signal processing was present. The sensor showed high linear response for the input current. Measurement range of the sensor was 0~200A and measurement error was less than 1%.

Keywords

HSSHBT_2019_v28n3_187_f0001.png 이미지

Fig. 1. Polarization rotation induced by Faraday effect in faraday device.

HSSHBT_2019_v28n3_187_f0002.png 이미지

Fig. 2. Schematic structure of proposed optical current sensor.

HSSHBT_2019_v28n3_187_f0003.png 이미지

Fig. 3. Fabricated optical current sensor.

HSSHBT_2019_v28n3_187_f0004.png 이미지

Fig. 4. Electronic circuit for signal processing.

HSSHBT_2019_v28n3_187_f0005.png 이미지

Fig. 5. Experimental set-up for measuring the performance of current sensor.

Table 1. Material and function of the optical devices

HSSHBT_2019_v28n3_187_t0001.png 이미지

Table 2. Applied current Vs. acquired current value after signal processing.

HSSHBT_2019_v28n3_187_t0002.png 이미지

References

  1. https://www.devicemart.co.kr/ (retrieved on May. 30, 2019)
  2. J.-G. Park, G.-S. Cha, and M.-H. Ku, "Design and fabrication of a 300A class general-purpose current sensor", J. Korea Acad. Ind. Coop. Soc., Vol. 17, No. 6, pp. 1-8, 2016. https://doi.org/10.5762/KAIS.2016.17.6.1
  3. C. Antonio and D. Cara, "Hall effect current transducer characterization under nonsinusoidal conditions", 2009 IEEE Instrum. Meas. Technol. Conf., Vol. 2009, pp. 98-103, Singapore, Singapore, 2009.
  4. C. Antonio, D. Cara, D. Emanuel, A. E,Nuccio, Salvatore, "Improvement of Hall Effect Current Transducer Metrological Performances in the Presence of Harmonic Distortion", IEEE Trans. on Instrum. Meas., Vol. 59, No. 5, pp. 1091-1097, 2010. https://doi.org/10.1109/TIM.2009.2038308
  5. C. Xiangxun "Fiber-optic current/voltage transducer for power system", Precis. Electromagn. Meas. Dig. Conf., pp. 567-568, Braunschweig, Germany, 1996.
  6. T. Mitski. K. Hosoe, H. Usami, and S. Miyamoto, "Development of fiber-optic voltage sensors and magnetic field sensors", IEEE Trans. Power Deliv., Vol. 2, No. 1, pp. 87-93, 1987. https://doi.org/10.1109/TPWRD.1987.4308077
  7. A. Papp and H. Harms, "Magneto-Optical Current Transformer", Appl. Opt., Vol. 19, No. 22, pp. 3729-3734, 1980. https://doi.org/10.1364/AO.19.003729
  8. T. W. Cease and P. Johnston, "Magneto-Optical Current Transformer", IEEE Trans. Power Deliv., Vol. 5, No. 2, pp. 548-555, 1990. https://doi.org/10.1109/61.53056
  9. N. Y. Jung, P. S. Chio, J. J. Eun, and H. S. Park, "A study on the fabrication of polarimetic fiber optic current sensor", J. Inst. Electron. Eng. Korea, Vol. 4, No. 6, pp. 443-451, 2004.