DOI QR코드

DOI QR Code

골심지의 흡습제 함침에 의한 종이 재질 판형 전열교환 소자의 성능 향상

Performance Improvement of a Paper Enthalpy Exchange Element by Impregnation of the Spacer

  • 김내현 (인천대학교 기계시스템공학부)
  • 투고 : 2016.09.09
  • 심사 : 2016.12.13
  • 발행 : 2017.03.10

초록

Improvement of the enthalpy exchange element's energy efficiency is of current interest from anenergy-saving viewpoint. In this study, a LiCl-impregnated spacer was devised as a means to improve the performance of the enthalpy exchange element. Two samples were tested : one with and one without impregnated spacers of $338{\times}338{\times}380mm$ sizes with 2.0 mm channel spacing. The results showed that the temperature efficiencies of the two samples were approximately the same. The humidity efficiency, however, was strongly affected by the LiCl impregnation. The impregnated sample yielded a 9% higher humidity efficiency under cooling and the difference increased to 14% under aheating condition. It was anticipated that more moisture would beadsorbed on the LiCl-impregnated spacers, which was delivered to their roots and eventually to the air in neighboring channels. Separate moisture adsorption tests revealed that both the adsorption rate and the amount of the adsorbed moisture are higher for the LiCl-impregnated specimen.

키워드

참고문헌

  1. Shin, S.-Y., Cho, M.-C., Lee, S.-H., Kim, B.-S., Kim, I.-K., and Lee, G.-G., 2004, Performance test of heat recovery ventilator element, Proceedings of the Summer Conference, The Society of Air-Conditioning and Refrigeration Engineers, pp. 729-733.
  2. Cho, M.-C., Lee, S.-H., Shin, S.-Y., Hong, Y.-K., Lee, S.-H., and Kang, T.-W., 2003, Development of HRV element using functional paper, New Technology Presentation, HARFKO Exhibition, pp. 73-77.
  3. Kistler, K. R. and Cussler, E. L., 2002, Membrane modules or building ventilation, Trans. IChemE, Vol. 80, Part A, pp. 53-64. https://doi.org/10.1205/026387602753393367
  4. Johnson, J. E., 1997, Heat and mass transfer between two fluid streams separated by a thin, permeable barrier, Ph.D thesis, University of Minnesota, Department of Mechanical Engineering.
  5. Zhang, L. Z. and Niu, J. L., 2002, Effectiveness correlations for heat and moisture transfer processes in an enthalpy exchanger with membrane cores, J. Heat Tranfer, Vol. 124, pp. 922-929. https://doi.org/10.1115/1.1469524
  6. Zhang, L. Z., 2008, Heat and mass transfer in plate-fin sinusoidal passages with vapor permeable wall materials, Int. J. Heat Mass Transfer, Vol. 51, pp. 618-629. https://doi.org/10.1016/j.ijheatmasstransfer.2007.04.050
  7. Kim, N.-H., Cho, J.-P., Song, K.-S., and Kim, D.-H., 2008, Performance of a plate-type enthalpy exchanger made of papers having different properties, Korean J. Air-Cond. Refrig., Vol. 20, No. 8, pp. 547-555.
  8. Kim, K.-H., Kim, H.-Y., and Lee, J.-J., 2007, A performance evaluation on the element cores of total heat recovery ventilator according to spacer's materials and manufacturing methods, J. Architectural Institute of Korea, Vol. 23, No. 9, pp. 189-196.
  9. Kim, N.-H., 2016, An Experimental study on the longterm performance variation of the plate-type enthalpy exchange element made of paper, Korean J. Air-Cond. Refrig., Vol. 28, No. 4, pp. 165-170.
  10. KS M 7020, 2001, Paper and board-Determination of air permeability (medium range)-Part 5 : Gurley method.
  11. KS M 7019, 2001, Sheet materials-Determination of water vapor transmission rate-Gravimetric(dish) method.
  12. ASHRAE Standard 41.2, 1986, Standard method for laboratory air-flow measurement, ASHRAE.
  13. ASHRAE Standard 41.1, 1986, Standard method for temperature measurement, ASHRAE.
  14. KS B 6879, 2007, Heat-recovery ventilators.
  15. ASHRAE Standard 41.5, 1986, Standard measurement guide, engineering analysis of experimental data, ASHRAE.
  16. Lee, E.-J., Lee, J.-P., and Kim, N.-H., 2013, Moisture transfer characteristics of a LiCl-impregnated paper membrane used for an enthalpy exchanger, J. Mech. Sci. Tech., Vol. 25, No. 5, pp. 1527-1537.